Duct CO2 sensor ?air quality sensor KFTM-LQ-CO2-W, 0..100% r.H. -35..80°C 0..2000/5000ppm 0..100%, 4x 0..10V/4..20mA?1CO, 24VAC/DC ±10%, IP65, S+S RegeltechnikAERASGARD® KFTM-LQ-CO2-W
Item No. 1501-8118-7301-200
EAN 4 251325 613697
Patented quality product (patent no. DE 10 2014 010 719.1)
The maintenance-free microprocessor-controlled duct sensor AERASGARD® KFTM - LQ -
CO2 - W and KLQ - CO2 - W with automatic and manual calibration is used for detecting the overall room climate. It measures CO2 within a range of 0...2000 ppm or 0...5000 ppm, air quality (VOC) in one of three s ensitivity levels that can be selected LOW / MEDIUM (default) / HIGH, temperature within a range of –35...+80 °C as well as relative humidity from 0...100 % r.H. The measured values are converted into standard signals of 0 -10 V or 4...20 mA (selectable via DIP switches). As an option, the measured values can be shown continuously in the illuminated display.
The relative humidity (% r.H.) quotient of water vapour partial pressure divided by the saturation vapour pressure at the respective gas temperature. A digital, long-term stable sensor used as measuring element for relative air humidity and temperature guarantees exact measurement results. The CO2 content of the air is measured using an optical NDIR sensor (non-dispersive infra-red technology). The detection range of the sensors is calibrated for standard applications such as monitoring residential rooms and conference rooms. Room ventilation on an as-needed basis, improved well-being and customer benefit, increased comfort as well as reduced operating costs through energy conservation are just some of the benefits of employing the AERASGARD® CO2 sensor.
The explanations above demonstrate that there are applications for CO2 measurements, for VOC measurem ents, but from our perspective, above all, for a combination of both measurands. The crucial factor in this respect is that both of these measurands are not convertible into each other and derivations to or from one another cannot be made. An NDIR CO2 measuring instrument measures selectively and cannot detect any VOC; a VOC mixed gas sensor cannot recognize CO2 molecules.
Voltage supply |
24 V AC ⁄ DC (± 10 %) |
Power consumption |
< 4.8 W ⁄ 24 V DC typical; < 6.8 VA ⁄ 24 V AC typical; peak current 200 mA |
Sensors |
digital humidity sensor
with integrated temperature sensor,
low hysteresis, high long-term stability
|
Measuring range, humidity |
0...100 % r. H. |
Operating range, humidity |
0...95 % r. H. (without dew formation) |
Deviation of humidity |
typical ± 2 % r. H.(20…80 % r. H. ); at + 25 °C, otherwise ± 3 % r. H.
|
Output, humidity |
0 -10 V or 4...20 mA (selectable via DIP switches)
|
Measuring range, temperature |
–35...+80 °C |
Operating range, temperature |
–10...+60 °C |
Temperature deviation |
± 0.2 K at +25 °C |
Output, temperature |
0 -10 V or 4...20 mA (selectable via DIP switches)
|
Sensor, VOC |
VOC sensor (metal oxide)with automatic calibration
(VOC = volatile organic compounds)
|
Measuring range, VOC |
0...100 % air quality; referred to calibrating gas;
multi-range switching(selectable via DIP switches)
VOC sensitivity low, medium, high
|
Output, VOC |
0 -10 V (0 V = clean air, 10 V = polluted air) or 4...20 mA (selectable via DIP switches,
switchpoint can be adjusted from 0...100 % of the output signal)
|
Measuring accuracy, VOC |
± 20 % of final value (referred to calibrating gas) |
Service life |
> 60 months (under normal load conditions) |
Measuring range, CO2 |
multi-range switching(selectable via DIP switches)
0...2000 ppm; 0...5000 ppm
|
Sensor, CO2 |
optical NDIR sensor (non-dispersive infra-red technology)
including atmospheric pressure compensation (up to 1100 mbar)
with automatic and manual calibration
|
Output, CO2 |
0 -10 V or 4...20 mA (selectable via DIP switches)
|
Measuring accuracy, CO2 |
± 30 ppm ± 3 % of measured value |
Temperature dependence, CO2 |
± 5 ppm ⁄ °C or ± 0.5 % of measured value ⁄ °C
(whichever is higher)
|
Pressure dependence |
± 0,13 % ⁄ mm Hg |
Gas exchange |
by diffusion |
Relay output |
with potential-free changeover contact 24 V (assignment selectable via DIP switches) |
Response time |
< 2 minutes |
Output |
0 -10 V or 4...20 mA (selectable via DIP switches,
selected variant applies for all outputs), working resistance < 800 Ω
|
Sensor protection |
plastic sinter filter, Ø 16 mm, L = 35 mm, exchangeable
(optional metal sinter filter, Ø 16 mm, L = 32 mm)
|
Ambient temperature |
–10...+60 °C |
Process connection |
by mounting flange, plastic
(included in the scope of delivery)
|
Protective tube |
PLEUROFORMTM, material polyamide (PA6), with torsion protection, Ø 20 mm, vmax = 30 m/s (air)
without filter: NL = 202.5 mm / with plastic filter: NL = 235 mm (optional with metal filter: NL = 227 mm)
|
Electrical connection |
0.14 - 1.5 mm² via terminal screws |
Enclosure |
plastic, UV-stabilised, material polyamide,
30 % glass-globe reinforced,
with quick-locking screws
(slotted ⁄ Phillips head - combination),
colour traffic white (similar to RAL 9016)
|
Enclosure dimensions |
126 x 90 x 50 mm (Tyr 2) |
Cable gland |
M 16 x 1.5; including strain relief,
exchangeable
|
Long-term stability |
< 2 % in 15 years |
Protection class |
III (according to EN 60 730) |
Protection type |
IP 65 (according to EN 60 529) enclosure only! (PLEUROFORM IP 30) |
Standards |
CE conformity,
electromagnetic compatibility according to EN 61326,
according to EMC Directive 2014 ⁄ 30 ⁄ EU
|
|