|
|
Image is illustrative
|
Gateway, EtherNet/IP to Modbus TCP/IP, 24VDC, Prosoft Code:
PLX31-EIP-MBTCP
Cena (indicative)
Manufacturer
:
Availability:
ask for dd
|
Weight:
1.35 kg/pc
|
|
|
|
|
|
Gateway PLX31-EIP-MBTCP, EtherNet/IP to Modbus TCP/IP, 24VDC, Prosoft Technology
DESCRIPTIONS
-
EtherNet/IP To Modbus TCP/IP Gateway, Communication Protocol: EtherNet/IP, Modbus TCP/IP, Power Supply: 24 VDC Nominal, 10 - 36 VDC Allowed, Width: 1.99 IN, Height: 5.38 IN, Temperature Rating: -25 To 70 DEG C, Ethernet Port: 10/100 MB Half-Duplex RJ45 Connector Electrical Isolation 1500 VRMS At 50 To 60 HZ For 60 SEC, Applied As Specified In Section 5.3.2 Of IEC 60950: 1991 Ethernet Broadcast Storm Resiliency Is Less Than Or Equal To 5000 [ARP] Frames-Per-Second And Less Than Or Equal To 5 MIN Duration, Serial Port Isolation: 2500 V RMS Port Signal Isolation Per UL 1577 Serial Port Communication Signal Uses Rf(Radio Frequency) Modulation Signal As Isolation Media, IC Chip Model Is Siliconlabs Si844x (Si8440,Si8441,Si8442), Depth: 4.38 IN, Current Rating: 24 VDC Nominal At 300 MA, 10 - 36 VDC At 610 MA Maximum, Environmental Conditions: Storage Temperature: -40 To 80 DEG C, Shock: 15 G At 11 MS Operating, 30 G At 18 MS Non-Operating, Vibration: 5 G From 10 - 150 HZ, Relative Humidity: 5 - 95% (Non-Condensing), Indicator: LED Indicator: Configuration (CFG), Error (ERR), Power (PWR), Hardware Fault (FLT), Network Status (NS), EtherNet/IP™ Class I Or Class III Connection Status (EtherNet/IP Only) Module Status (MS), Module Configuration Status (EtherNet/IP Only), Ethernet Communication Port Link/Activity And 100 MBit, Standard/Approvals: C/UL listed, CE marked, CB safty standard, KC marked
SPECIFICATIONS
-
-
Item Name: EtherNet/IP To Modbus TCP/IP Gateway
-
Communication Protocol: EtherNet/IP, Modbus TCP/IP
-
Power Supply: 24 VDC Nominal, 10 - 36 VDC Allowed
-
Width: 1.99 IN
-
Height: 5.38 IN
-
Temperature Rating: -25 To 70 DEG C
-
Environmental Conditions: Storage Temperature: -40 To 80 DEG C, Shock: 15 G At 11 MS Operating, 30 G At 18 MS Non-Operating, Vibration: 5 G From 10 - 150 HZ, Relative Humidity: 5 - 95% (Non-Condensing)
-
Indicator: LED Indicator: Configuration (CFG), Error (ERR), Power (PWR), Hardware Fault (FLT), Network Status (NS), EtherNet/IP™ Class I Or Class III Connection Status (EtherNet/IP Only) Module Status (MS), Module Configuration Status (EtherNet/IP Only), Ethernet Communication Port Link/Activity And 100 MBit
-
Depth: 4.38 IN
-
Serial Port Isolation: 2500 V RMS Port Signal Isolation Per UL 1577 Serial Port Communication Signal Uses Rf(Radio Frequency) Modulation Signal As Isolation Media, IC Chip Model Is Siliconlabs Si844x (Si8440,Si8441,Si8442)
-
Current Rating: 24 VDC Nominal At 300 MA, 10 - 36 VDC At 610 MA Maximum
-
Ethernet Port: 10/100 MB Half-Duplex RJ45 Connector Electrical Isolation 1500 VRMS At 50 To 60 HZ For 60 SEC, Applied As Specified In Section 5.3.2 Of IEC 60950: 1991 Ethernet Broadcast Storm Resiliency Is Less Than Or Equal To 5000 [ARP] Frames-Per-Second And Less Than Or Equal To 5 MIN Duration
FEATURES
-
The EtherNet/IP to Modbus TCP/IP gateways offers bi-directional data transfers between the EtherNet/IP and Modbus TCP/IP networks. Our EtherNet/IP Driver uses Class 1 I/O connections or Class 3 Message instructions. Our Modbus TCP/IP Driver uses Multiple Clients and Servers for faster data throughput. Protocol conversion gateways are the ideal solution for distributed networks when adding a remote rack becomes too costly. The PLX31-EIP-MBTCP gateways are stand-alone DIN-rail mounted modules that provide one Ethernet port for communication, allowing for remote configuration and diagnostics. The PLX30 gateways also come with an SD Card slot (SD card optional) for storing configuration files. In the event of a failure the SD card can be transferred to another gateway reducing downtime. These gateways also come with a wide input power range (10 - 36 VDC), and an extended temperature range (-25 To 70 DEG C ). The PLX30 gateways include all the necessary cables required for communication
- Multiple I/O Connections
- Status data
- Node Health
- 4000 Word database
- Data prioritization, multiple I/O connections allow you to set RPIs for status and/or control data, optimizing Ethernet bandwidth
- Standards: C/UL listed, CE marked, CB safety standard, KC marked
DOCUMENTS
-
|
File description
|
File type
|
Download link
|
|
|
|
"
Spec Sheet
|
.pdf
|
Download link
|
|
|
|
|
|
|
|