| General information |
| Product type designation |
AI 4xU/I/RTD/TC /AQ 2xU/I ST |
| HW functional status |
FS01 |
| Firmware version |
V1.0.0 |
| ● FW update possible |
Yes |
| Product function |
| ● I&M data |
Yes; I&M0 to I&M3 |
| ● Measuring range scalable |
No |
| ● Scalable measured values |
No |
| ● Adjustment of measuring range |
No |
| ● Output range scalable |
No |
| Engineering with |
| ● STEP 7 TIA Portal configurable/integrated as of version |
V13 / V13.0.2 |
| ● STEP 7 configurable/integrated as of version |
V5.5 SP3 / - |
| ● PROFIBUS as of GSD version/GSD revision |
V1.0 / V5.1 |
| ● PROFINET as of GSD version/GSD revision |
V2.3 / - |
| Operating mode |
| ● Oversampling |
No |
| ● MSI |
Yes |
| ● MSO |
Yes |
| CiR – Configuration in RUN |
| Reparameterization possible in RUN |
Yes |
| Calibration possible in RUN |
Yes |
| Supply voltage |
| Type of supply voltage |
DC |
| Rated value (DC) |
24 V |
| permissible range, lower limit (DC) |
20.4 V |
| permissible range, upper limit (DC) |
28.8 V |
| Reverse polarity protection |
Yes |
| Input current |
| Current consumption, max. |
200 mA; with 24 V DC supply |
| Encoder supply |
| 24 V encoder supply |
| ● Short-circuit protection |
Yes |
| ● Output current, max. |
20 mA; Max. 47 mA per channel for a duration < 10 s |
| Power |
| Power available from the backplane bus |
0.7 W |
| Power loss |
| Power loss, typ. |
3.3 W |
| Analog inputs |
| Number of analog inputs |
4 |
| ● For current measurement |
4 |
| ● For voltage measurement |
4 |
| ● For resistance/resistance thermometer measurement |
2 |
| ● For thermocouple measurement |
4 |
| permissible input voltage for voltage input (destruction limit), max. |
28.8 V |
| permissible input current for current input (destruction limit), max. |
40 mA |
| Constant measurement current for resistance-type transmitter, typ. |
150 Ohm, 300 Ohm, 600 Ohm, Pt100, Pt200, Ni100: 1.25 mA; 6 000 Ohm, Pt500, Pt1000, Ni1000, LG-Ni1000: 0.625 mA; PTC: 0.472 mA |
| Technical unit for temperature measurement adjustable |
Yes; °C/°F/K |
| Analog input with oversampling |
No |
| Standardization of measured values |
No |
| Input ranges (rated values), voltages |
| ● 0 to +5 V |
No |
| ● 0 to +10 V |
No |
| ● 1 V to 5 V |
Yes |
| ● Input resistance (1 V to 5 V) |
100 kΩ |
| ● -1 V to +1 V |
Yes |
| ● Input resistance (-1 V to +1 V) |
10 MΩ |
| ● -10 V to +10 V |
Yes |
| ● Input resistance (-10 V to +10 V) |
100 kΩ |
| ● -2.5 V to +2.5 V |
Yes |
| ● Input resistance (-2.5 V to +2.5 V) |
10 MΩ |
| ● -25 mV to +25 mV |
No |
| ● -250 mV to +250 mV |
Yes |
| ● Input resistance (-250 mV to +250 mV) |
10 MΩ |
| ● -5 V to +5 V |
Yes |
| ● Input resistance (-5 V to +5 V) |
100 kΩ |
| ● -50 mV to +50 mV |
Yes |
| ● Input resistance (-50 mV to +50 mV) |
10 MΩ |
| ● -500 mV to +500 mV |
Yes |
| ● Input resistance (-500 mV to +500 mV) |
10 MΩ |
| ● -80 mV to +80 mV |
Yes |
| ● Input resistance (-80 mV to +80 mV) |
10 MΩ |
| Input ranges (rated values), currents |
| ● 0 to 20 mA |
Yes |
| ● Input resistance (0 to 20 mA) |
25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC |
| ● -20 mA to +20 mA |
Yes |
| ● Input resistance (-20 mA to +20 mA) |
25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC |
| ● 4 mA to 20 mA |
Yes |
| ● Input resistance (4 mA to 20 mA) |
25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC |
| Input ranges (rated values), thermocouples |
| ● Type B |
Yes |
| ● Input resistance (Type B) |
10 MΩ |
| ● Type C |
No |
| ● Type E |
Yes |
| ● Input resistance (Type E) |
10 MΩ |
| ● Type J |
Yes |
| ● Input resistance (type J) |
10 MΩ |
| ● Type K |
Yes |
| ● Input resistance (Type K) |
10 MΩ |
| ● Type L |
No |
| ● Type N |
Yes |
| ● Input resistance (Type N) |
10 MΩ |
| ● Type R |
Yes |
| ● Input resistance (Type R) |
10 MΩ |
| ● Type S |
Yes |
| ● Input resistance (Type S) |
10 MΩ |
| ● Type T |
Yes |
| ● Input resistance (Type T) |
10 MΩ |
| ● Type U |
No |
| ● Type TXK/TXK(L) to GOST |
No |
| Input ranges (rated values), resistance thermometer |
| ● Cu 10 |
No |
| ● Cu 10 according to GOST |
No |
| ● Cu 50 |
No |
| ● Cu 50 according to GOST |
No |
| ● Cu 100 |
No |
| ● Cu 100 according to GOST |
No |
| ● Ni 10 |
No |
| ● Ni 10 according to GOST |
No |
| ● Ni 100 |
Yes; Standard/climate |
| ● Input resistance (Ni 100) |
10 MΩ |
| ● Ni 100 according to GOST |
No |
| ● Ni 1000 |
Yes; Standard/climate |
| ● Input resistance (Ni 1000) |
10 MΩ |
| ● Ni 1000 according to GOST |
No |
| ● LG-Ni 1000 |
Yes; Standard/climate |
| ● Input resistance (LG-Ni 1000) |
10 MΩ |
| ● Ni 120 |
No |
| ● Ni 120 according to GOST |
No |
| ● Ni 200 |
No |
| ● Ni 200 according to GOST |
No |
| ● Ni 500 |
No |
| ● Ni 500 according to GOST |
No |
| ● Pt 10 |
No |
| ● Pt 10 according to GOST |
No |
| ● Pt 50 |
No |
| ● Pt 50 according to GOST |
No |
| ● Pt 100 |
Yes; Standard/climate |
| ● Input resistance (Pt 100) |
10 MΩ |
| ● Pt 100 according to GOST |
No |
| ● Pt 1000 |
Yes; Standard/climate |
| ● Input resistance (Pt 1000) |
10 MΩ |
| ● Pt 1000 according to GOST |
No |
| ● Pt 200 |
Yes; Standard/climate |
| ● Input resistance (Pt 200) |
10 MΩ |
| ● Pt 200 according to GOST |
No |
| ● Pt 500 |
Yes; Standard/climate |
| ● Input resistance (Pt 500) |
10 MΩ |
| ● Pt 500 according to GOST |
No |
| Input ranges (rated values), resistors |
| ● 0 to 150 ohms |
Yes |
| ● Input resistance (0 to 150 ohms) |
10 MΩ |
| ● 0 to 300 ohms |
Yes |
| ● Input resistance (0 to 300 ohms) |
10 MΩ |
| ● 0 to 600 ohms |
Yes |
| ● Input resistance (0 to 600 ohms) |
10 MΩ |
| ● 0 to 3000 ohms |
No |
| ● 0 to 6000 ohms |
Yes |
| ● Input resistance (0 to 6000 ohms) |
10 MΩ |
| ● PTC |
Yes |
| ● Input resistance (PTC) |
10 MΩ |
| Thermocouple (TC) |
| Temperature compensation |
| — parameterizable |
Yes |
| — internal temperature compensation |
Yes |
| — external temperature compensation via RTD |
Yes |
| — Compensation for 0 °C reference point temperature |
Yes; fixed value can be set |
| — Reference channel of the module |
No |
| Cable length |
| ● shielded, max. |
800 m; for U/I, 200 m for R/RTD, 50 m for TC |
| Analog outputs |
| Number of analog outputs |
2 |
| Voltage output, short-circuit protection |
Yes |
| Voltage output, short-circuit current, max. |
24 mA |
| Current output, no-load voltage, max. |
22 V |
| Cycle time (all channels), min. |
3.2 ms; ±0.5 ms, regardless of the number of activated channels |
| Output ranges, voltage |
| ● 0 to 10 V |
Yes |
| ● 1 V to 5 V |
Yes |
| ● -5 V to +5 V |
No |
| ● -10 V to +10 V |
Yes |
| Output ranges, current |
| ● 0 to 20 mA |
Yes |
| ● -20 mA to +20 mA |
Yes |
| ● 4 mA to 20 mA |
Yes |
| Connection of actuators |
| ● for voltage output two-wire connection |
Yes |
| ● for voltage output four-wire connection |
Yes |
| ● for current output two-wire connection |
Yes |
| Load impedance (in rated range of output) |
| ● with voltage outputs, min. |
1 kΩ; 0.5 kOhm at 1 to 5 V |
| ● with voltage outputs, capacitive load, max. |
1 µF |
| ● with current outputs, max. |
750 Ω |
| ● with current outputs, inductive load, max. |
10 mH |
| Cable length |
| ● shielded, max. |
800 m; for current, 200 m for voltage |
| Analog value generation for the inputs |
| Integration and conversion time/resolution per channel |
| ● Resolution with overrange (bit including sign), max. |
16 bit |
| ● Integration time, parameterizable |
Yes |
| ● Integration time (ms) |
2,5 / 16,67 / 20 / 100 ms |
| ● Basic conversion time, including integration time (ms) |
9 / 23 / 27 / 107 ms |
| — additional conversion time for wire-break monitoring |
9 ms |
| — additional conversion time for resistance measurement |
150 ohm, 300 ohm, 600 ohm, Pt100, Pt200, Ni100: 2 ms, 6000 ohm, Pt500, Pt1000, Ni1000, LG-Ni1000, PTC: 4 ms |
| ● Interference voltage suppression for interference frequency f1 in Hz |
400 / 60 / 50 / 10 |
| ● Time for offset calibration (per module) |
Basic conversion time of the slowest channel |
| Smoothing of measured values |
| ● parameterizable |
Yes |
| ● Step: None |
Yes |
| ● Step: low |
Yes |
| ● Step: Medium |
Yes |
| ● Step: High |
Yes |
| Analog value generation for the outputs |
| Integration and conversion time/resolution per channel |
| ● Resolution with overrange (bit including sign), max. |
16 bit |
| ● Conversion time (per channel) |
0.5 ms |
| Settling time |
| ● for resistive load |
1.5 ms |
| ● for capacitive load |
2.5 ms |
| ● for inductive load |
2.5 ms |
| Encoder |
| Connection of signal encoders |
| ● for voltage measurement |
Yes |
| ● for current measurement as 2-wire transducer |
Yes |
| — Burden of 2-wire transmitter, max. |
820 Ω |
| ● for current measurement as 4-wire transducer |
Yes |
| ● for resistance measurement with two-wire connection |
Yes; Only for PTC |
| ● for resistance measurement with three-wire connection |
Yes; All measuring ranges except PTC; internal compensation of the cable resistances |
| ● for resistance measurement with four-wire connection |
Yes; All measuring ranges except PTC |
| Errors/accuracies |
| Linearity error (relative to input range), (+/-) |
0.02 % |
| Temperature error (relative to input range), (+/-) |
0.005 %/K; With TC type T 0.02 ± % / K |
| Crosstalk between the inputs, max. |
-80 dB |
| Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) |
0.02 % |
| Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) |
0.02 % |
| Linearity error (relative to output range), (+/-) |
0.15 % |
| Temperature error (relative to output range), (+/-) |
0.002 %/K |
| Crosstalk between the outputs, max. |
-100 dB |
| Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) |
0.05 % |
| Temperature error of internal compensation |
±6 °C |
| Operational error limit in overall temperature range |
| ● Voltage, relative to input range, (+/-) |
0.3 % |
| ● Current, relative to input range, (+/-) |
0.3 % |
| ● Resistance, relative to input range, (+/-) |
0.3 % |
| ● Resistance thermometer, relative to input range, (+/-) |
0.3 %; Ptxxx standard: ±1.5 K, Ptxxx climate: ±0.5 K, Nixxx standard: ±0.5 K, Nixxx climate: ±0.3 K |
| ● Thermocouple, relative to input range, (+/-) |
0.3 %; Type B: > 600 °C ±4.6 K, type E: > -200 °C ±1.5 K, type J: > -210 °C ±1.9 K, type K: > -200 °C ±2.4 K, type N: > -200 °C ±2.9 K, type R: > 0 °C ±4.7 K, type S: > 0 °C ±4.6 K, type T: > -200 °C ±2.4 K |
| ● Voltage, relative to output range, (+/-) |
0.3 % |
| ● Current, relative to output range, (+/-) |
0.3 % |
| Basic error limit (operational limit at 25 °C) |
| ● Voltage, relative to input range, (+/-) |
0.1 % |
| ● Current, relative to input range, (+/-) |
0.1 % |
| ● Resistance, relative to input range, (+/-) |
0.1 % |
| ● Resistance thermometer, relative to input range, (+/-) |
0.1 %; Ptxxx standard: ±0.7 K, Ptxxx climate: ±0.2 K, Nixxx standard: ±0.3 K, Nixxx climate: ±0.15 K |
| ● Thermocouple, relative to input range, (+/-) |
0.1 %; Type B: > 600 °C ±1.7 K, type E: > -200 °C ±0.7 K, type J: > -210 °C ±0.8 K, type K: > -200 °C ±1.2 K, type N: > -200 °C ±1.2 K, type R: > 0 °C ±1.9 K, type S: > 0 °C ±1.9 K, type T: > -200 °C ±0.8 K |
| ● Voltage, relative to output range, (+/-) |
0.2 % |
| ● Current, relative to output range, (+/-) |
0.2 % |
| Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency |
| ● Series mode interference (peak value of interference < rated value of input range), min. |
40 dB |
| ● Common mode voltage, max. |
10 V |
| ● Common mode interference, min. |
60 dB |
| Isochronous mode |
| Isochronous operation (application synchronized up to terminal) |
No |
| Interrupts/diagnostics/status information |
| Diagnostics function |
Yes |
| Substitute values connectable |
Yes |
| Alarms |
| ● Diagnostic alarm |
Yes |
| ● Limit value alarm |
Yes; two upper and two lower limit values in each case |
| Diagnostic messages |
| ● Monitoring the supply voltage |
Yes |
| ● Wire-break |
Yes; only for input type 1 ... 5 V, 4 ... 20 mA, TC, R, RTD and output type current |
| ● Short-circuit |
Yes; Only for output type "voltage" |
| ● Overflow/underflow |
Yes |
| Diagnostics indication LED |
| ● RUN LED |
Yes; Green LED |
| ● ERROR LED |
Yes; Red LED |
| ● Monitoring of the supply voltage (PWR-LED) |
Yes; Green LED |
| ● Channel status display |
Yes; Green LED |
| ● for channel diagnostics |
Yes; Red LED |
| ● for module diagnostics |
Yes; Red LED |
| Potential separation |
| Potential separation analog inputs |
| ● between the channels |
No |
| ● between the channels, in groups of |
4 |
| ● between the channels and backplane bus |
Yes |
| ● Between the channels and load voltage L+ |
Yes |
| Potential separation analog outputs |
| ● between the channels |
No |
| ● between the channels, in groups of |
2 |
| ● between the channels and backplane bus |
Yes |
| ● Between the channels and load voltage L+ |
Yes |
| Permissible potential difference |
| between the inputs (UCM) |
20 V DC |
| Between the inputs and MANA (UCM) |
10 V DC |
| between S- and MANA (UCM) |
8 V DC |
| Isolation |
| Isolation tested with |
707 V DC (type test) |
| Ambient conditions |
| Ambient temperature during operation |
| ● horizontal installation, min. |
0 °C |
| ● horizontal installation, max. |
60 °C |
| ● vertical installation, min. |
0 °C |
| ● vertical installation, max. |
40 °C |
| Decentralized operation |
| Prioritized startup |
No |
| Dimensions |
| Width |
25 mm |
| Height |
147 mm |
| Depth |
129 mm |
| Weights |
| Weight, approx. |
250 g |
| Other |
| Note: |
Supplied incl. 40-pole push-in front connectors. Additional basic error and noise for integration time = 2.5 ms: Voltage: ±250 mV (±0.02%), ±80 mV (±0.05%), ±50 mV (±0.05%); resistance: 150 Ohms (±0.02%); resistance thermometer: Pt100 climate: ±0.08 K, Ni100 climate: ±0.08 K; thermoelement: Type B, R, S: ±3 K, type E, J, K, N, T: ±1 K |
| last modified: |
03/13/2019 |