Elit logo e-Elit - leading
electronic and automation component
online distributor
Elit shopping basket
Items: Total:
0
0,00 €
    search
Log in
Username/Email Address:

Password:
Show all products categ.
Need assistance?
Featured Products!
Bulkhead housing HDC IP68 24B AS, Size 8, screw plug, standard, IP68, Weidmüller
Bulkhead housing HDC IP68 24B AS, Size 8, screw plug, standard, IP68, Weidmüller



Simatic S7-1500, Analog IO Module, 4AI U/I/R/RTD/TC ST, 4-ch. in groups of 4, diagnostics, 2AQ U/I ST, 2-ch. in groups of 2, diagnostics, common-mode 10V, 16bit res., acc. 0.3%, incl. front con., infeed element, shield bracket, terminal
Image is illustrative
Simatic S7-1500, Analog IO Module, 4AI U/I/R/RTD/TC ST, 4-ch. in groups of 4, diagnostics, 2AQ U/I ST, 2-ch. in groups of 2, diagnostics, common-mode 10V, 16bit res., acc. 0.3%, incl. front con., infeed element, shield bracket, terminal
Code: 6ES7534-7QE00-0AB0
Cena (indicative)
786,90 €  /pc
Manufacturer :
Availability:
ask for dd
Weight:
0.4389 kg/pc
Volume:
0.0014 m3/pc
Quantity:
Plus sign Minus sign
 

 

Simatic S7-1500, Analog IO Module, 4AI U/I/R/RTD/TC ST, 4-ch. in groups of 4, diagnostics, 2AQ U/I ST, 2-ch. in groups of 2, diagnostics, common mode 10V, 16bit res., acc. 0.3%, incl. front con. ^infeed element ^shield bracket ^terminal, Siemens

SIMATIC S7-1500, Analog input/output module AI 4x U/I/R/RTD/TC ST; 4 channels in groups of 4; hardware interrupts; Diagnostics AQ 2x U/I ST; 2 channels in groups of 2; substitute value; Diagnostics COMMON mode voltage approx. 10 V 16 bit; accuracy 0.3% incl. push-in front connector, infeed element, shield bracket, shield terminal
General information
Product type designation AI 4xU/I/RTD/TC /AQ 2xU/I ST
HW functional status FS01
Firmware version V1.0.0
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Measuring range scalable No
● Scalable measured values No
● Adjustment of measuring range No
● Output range scalable No
Engineering with
● STEP 7 TIA Portal configurable/integrated as of version V13 / V13.0.2
● STEP 7 configurable/integrated as of version V5.5 SP3 / -
● PROFIBUS as of GSD version/GSD revision V1.0 / V5.1
● PROFINET as of GSD version/GSD revision V2.3 / -
Operating mode
● Oversampling No
● MSI Yes
● MSO Yes
CiR – Configuration in RUN
Reparameterization possible in RUN Yes
Calibration possible in RUN Yes
Supply voltage
Type of supply voltage DC
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 200 mA; with 24 V DC supply
Encoder supply
24 V encoder supply
● Short-circuit protection Yes
● Output current, max. 20 mA; Max. 47 mA per channel for a duration < 10 s
Power
Power available from the backplane bus 0.7 W
Power loss
Power loss, typ. 3.3 W
Analog inputs
Number of analog inputs 4
● For current measurement 4
● For voltage measurement 4
● For resistance/resistance thermometer measurement 2
● For thermocouple measurement 4
permissible input voltage for voltage input (destruction limit), max. 28.8 V
permissible input current for current input (destruction limit), max. 40 mA
Constant measurement current for resistance-type transmitter, typ. 150 Ohm, 300 Ohm, 600 Ohm, Pt100, Pt200, Ni100: 1.25 mA; 6 000 Ohm, Pt500, Pt1000, Ni1000, LG-Ni1000: 0.625 mA; PTC: 0.472 mA
Technical unit for temperature measurement adjustable Yes; °C/°F/K
Analog input with oversampling No
Standardization of measured values No
Input ranges (rated values), voltages
● 0 to +5 V No
● 0 to +10 V No
● 1 V to 5 V Yes
● Input resistance (1 V to 5 V) 100 kΩ
● -1 V to +1 V Yes
● Input resistance (-1 V to +1 V) 10 MΩ
● -10 V to +10 V Yes
● Input resistance (-10 V to +10 V) 100 kΩ
● -2.5 V to +2.5 V Yes
● Input resistance (-2.5 V to +2.5 V) 10 MΩ
● -25 mV to +25 mV No
● -250 mV to +250 mV Yes
● Input resistance (-250 mV to +250 mV) 10 MΩ
● -5 V to +5 V Yes
● Input resistance (-5 V to +5 V) 100 kΩ
● -50 mV to +50 mV Yes
● Input resistance (-50 mV to +50 mV) 10 MΩ
● -500 mV to +500 mV Yes
● Input resistance (-500 mV to +500 mV) 10 MΩ
● -80 mV to +80 mV Yes
● Input resistance (-80 mV to +80 mV) 10 MΩ
Input ranges (rated values), currents
● 0 to 20 mA Yes
● Input resistance (0 to 20 mA) 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
● -20 mA to +20 mA Yes
● Input resistance (-20 mA to +20 mA) 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
● 4 mA to 20 mA Yes
● Input resistance (4 mA to 20 mA) 25 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
Input ranges (rated values), thermocouples
● Type B Yes
● Input resistance (Type B) 10 MΩ
● Type C No
● Type E Yes
● Input resistance (Type E) 10 MΩ
● Type J Yes
● Input resistance (type J) 10 MΩ
● Type K Yes
● Input resistance (Type K) 10 MΩ
● Type L No
● Type N Yes
● Input resistance (Type N) 10 MΩ
● Type R Yes
● Input resistance (Type R) 10 MΩ
● Type S Yes
● Input resistance (Type S) 10 MΩ
● Type T Yes
● Input resistance (Type T) 10 MΩ
● Type U No
● Type TXK/TXK(L) to GOST No
Input ranges (rated values), resistance thermometer
● Cu 10 No
● Cu 10 according to GOST No
● Cu 50 No
● Cu 50 according to GOST No
● Cu 100 No
● Cu 100 according to GOST No
● Ni 10 No
● Ni 10 according to GOST No
● Ni 100 Yes; Standard/climate
● Input resistance (Ni 100) 10 MΩ
● Ni 100 according to GOST No
● Ni 1000 Yes; Standard/climate
● Input resistance (Ni 1000) 10 MΩ
● Ni 1000 according to GOST No
● LG-Ni 1000 Yes; Standard/climate
● Input resistance (LG-Ni 1000) 10 MΩ
● Ni 120 No
● Ni 120 according to GOST No
● Ni 200 No
● Ni 200 according to GOST No
● Ni 500 No
● Ni 500 according to GOST No
● Pt 10 No
● Pt 10 according to GOST No
● Pt 50 No
● Pt 50 according to GOST No
● Pt 100 Yes; Standard/climate
● Input resistance (Pt 100) 10 MΩ
● Pt 100 according to GOST No
● Pt 1000 Yes; Standard/climate
● Input resistance (Pt 1000) 10 MΩ
● Pt 1000 according to GOST No
● Pt 200 Yes; Standard/climate
● Input resistance (Pt 200) 10 MΩ
● Pt 200 according to GOST No
● Pt 500 Yes; Standard/climate
● Input resistance (Pt 500) 10 MΩ
● Pt 500 according to GOST No
Input ranges (rated values), resistors
● 0 to 150 ohms Yes
● Input resistance (0 to 150 ohms) 10 MΩ
● 0 to 300 ohms Yes
● Input resistance (0 to 300 ohms) 10 MΩ
● 0 to 600 ohms Yes
● Input resistance (0 to 600 ohms) 10 MΩ
● 0 to 3000 ohms No
● 0 to 6000 ohms Yes
● Input resistance (0 to 6000 ohms) 10 MΩ
● PTC Yes
● Input resistance (PTC) 10 MΩ
Thermocouple (TC)
Temperature compensation
— parameterizable Yes
— internal temperature compensation Yes
— external temperature compensation via RTD Yes
— Compensation for 0 °C reference point temperature Yes; fixed value can be set
— Reference channel of the module No
Cable length
● shielded, max. 800 m; for U/I, 200 m for R/RTD, 50 m for TC
Analog outputs
Number of analog outputs 2
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 24 mA
Current output, no-load voltage, max. 22 V
Cycle time (all channels), min. 3.2 ms; ±0.5 ms, regardless of the number of activated channels
Output ranges, voltage
● 0 to 10 V Yes
● 1 V to 5 V Yes
● -5 V to +5 V No
● -10 V to +10 V Yes
Output ranges, current
● 0 to 20 mA Yes
● -20 mA to +20 mA Yes
● 4 mA to 20 mA Yes
Connection of actuators
● for voltage output two-wire connection Yes
● for voltage output four-wire connection Yes
● for current output two-wire connection Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 1 kΩ; 0.5 kOhm at 1 to 5 V
● with voltage outputs, capacitive load, max. 1 µF
● with current outputs, max. 750 Ω
● with current outputs, inductive load, max. 10 mH
Cable length
● shielded, max. 800 m; for current, 200 m for voltage
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Integration time, parameterizable Yes
● Integration time (ms) 2,5 / 16,67 / 20 / 100 ms
● Basic conversion time, including integration time (ms) 9 / 23 / 27 / 107 ms
— additional conversion time for wire-break monitoring 9 ms
— additional conversion time for resistance measurement 150 ohm, 300 ohm, 600 ohm, Pt100, Pt200, Ni100: 2 ms, 6000 ohm, Pt500, Pt1000, Ni1000, LG-Ni1000, PTC: 4 ms
● Interference voltage suppression for interference frequency f1 in Hz 400 / 60 / 50 / 10
● Time for offset calibration (per module) Basic conversion time of the slowest channel
Smoothing of measured values
● parameterizable Yes
● Step: None Yes
● Step: low Yes
● Step: Medium Yes
● Step: High Yes
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Conversion time (per channel) 0.5 ms
Settling time
● for resistive load 1.5 ms
● for capacitive load 2.5 ms
● for inductive load 2.5 ms
Encoder
Connection of signal encoders
● for voltage measurement Yes
● for current measurement as 2-wire transducer Yes
— Burden of 2-wire transmitter, max. 820 Ω
● for current measurement as 4-wire transducer Yes
● for resistance measurement with two-wire connection Yes; Only for PTC
● for resistance measurement with three-wire connection Yes; All measuring ranges except PTC; internal compensation of the cable resistances
● for resistance measurement with four-wire connection Yes; All measuring ranges except PTC
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.02 %
Temperature error (relative to input range), (+/-) 0.005 %/K; With TC type T 0.02 ± % / K
Crosstalk between the inputs, max. -80 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.02 %
Output ripple (relative to output range, bandwidth 0 to 50 kHz), (+/-) 0.02 %
Linearity error (relative to output range), (+/-) 0.15 %
Temperature error (relative to output range), (+/-) 0.002 %/K
Crosstalk between the outputs, max. -100 dB
Repeat accuracy in steady state at 25 °C (relative to output range), (+/-) 0.05 %
Temperature error of internal compensation ±6 °C
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 0.3 %
● Current, relative to input range, (+/-) 0.3 %
● Resistance, relative to input range, (+/-) 0.3 %
● Resistance thermometer, relative to input range, (+/-) 0.3 %; Ptxxx standard: ±1.5 K, Ptxxx climate: ±0.5 K, Nixxx standard: ±0.5 K, Nixxx climate: ±0.3 K
● Thermocouple, relative to input range, (+/-) 0.3 %; Type B: > 600 °C ±4.6 K, type E: > -200 °C ±1.5 K, type J: > -210 °C ±1.9 K, type K: > -200 °C ±2.4 K, type N: > -200 °C ±2.9 K, type R: > 0 °C ±4.7 K, type S: > 0 °C ±4.6 K, type T: > -200 °C ±2.4 K
● Voltage, relative to output range, (+/-) 0.3 %
● Current, relative to output range, (+/-) 0.3 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.1 %
● Current, relative to input range, (+/-) 0.1 %
● Resistance, relative to input range, (+/-) 0.1 %
● Resistance thermometer, relative to input range, (+/-) 0.1 %; Ptxxx standard: ±0.7 K, Ptxxx climate: ±0.2 K, Nixxx standard: ±0.3 K, Nixxx climate: ±0.15 K
● Thermocouple, relative to input range, (+/-) 0.1 %; Type B: > 600 °C ±1.7 K, type E: > -200 °C ±0.7 K, type J: > -210 °C ±0.8 K, type K: > -200 °C ±1.2 K, type N: > -200 °C ±1.2 K, type R: > 0 °C ±1.9 K, type S: > 0 °C ±1.9 K, type T: > -200 °C ±0.8 K
● Voltage, relative to output range, (+/-) 0.2 %
● Current, relative to output range, (+/-) 0.2 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 40 dB
● Common mode voltage, max. 10 V
● Common mode interference, min. 60 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal) No
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm Yes
● Limit value alarm Yes; two upper and two lower limit values in each case
Diagnostic messages
● Monitoring the supply voltage Yes
● Wire-break Yes; only for input type 1 ... 5 V, 4 ... 20 mA, TC, R, RTD and output type current
● Short-circuit Yes; Only for output type "voltage"
● Overflow/underflow Yes
Diagnostics indication LED
● RUN LED Yes; Green LED
● ERROR LED Yes; Red LED
● Monitoring of the supply voltage (PWR-LED) Yes; Green LED
● Channel status display Yes; Green LED
● for channel diagnostics Yes; Red LED
● for module diagnostics Yes; Red LED
Potential separation
Potential separation analog inputs
● between the channels No
● between the channels, in groups of 4
● between the channels and backplane bus Yes
● Between the channels and load voltage L+ Yes
Potential separation analog outputs
● between the channels No
● between the channels, in groups of 2
● between the channels and backplane bus Yes
● Between the channels and load voltage L+ Yes
Permissible potential difference
between the inputs (UCM) 20 V DC
Between the inputs and MANA (UCM) 10 V DC
between S- and MANA (UCM) 8 V DC
Isolation
Isolation tested with 707 V DC (type test)
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. 0 °C
● horizontal installation, max. 60 °C
● vertical installation, min. 0 °C
● vertical installation, max. 40 °C
Decentralized operation
Prioritized startup No
Dimensions
Width 25 mm
Height 147 mm
Depth 129 mm
Weights
Weight, approx. 250 g
Other
Note: Supplied incl. 40-pole push-in front connectors. Additional basic error and noise for integration time = 2.5 ms: Voltage: ±250 mV (±0.02%), ±80 mV (±0.05%), ±50 mV (±0.05%); resistance: 150 Ohms (±0.02%); resistance thermometer: Pt100 climate: ±0.08 K, Ni100 climate: ±0.08 K; thermoelement: Type B, R, S: ±3 K, type E, J, K, N, T: ±1 K