Simatic S7-1500, Digital IO Module, 16DI 24VDC BA, 16-ch. in groups of 16, input delay 3.2ms, input type 3 (IEC 61131), 16DQ 0.5A 24VDC BA, 16-ch. in groups of 8, 4A per group, incl. push-in front connector, Siemens
Image is illustrative
Simatic S7-1500, Digital IO Module, 16DI 24VDC BA, 16-ch. in groups of 16, input delay 3.2ms, input type 3 (IEC 61131), 16DQ 0.5A 24VDC BA, 16-ch. in groups of 8, 4A per group, incl. push-in front connector, Siemens
Code: 6ES7523-1BL00-0AA0
Cena (indicative)
543,30 €  /pc
Manufacturer :
Availability:
21 days
Weight:
0.378 kg/pc
Volume:
0.0011 m3/pc
Quantity:
Plus sign Minus sign
 

 

Simatic S7-1500, Digital IO Module, 16DI 24VDC BA, 16-ch. in groups of 16, input delay 3.2ms, input type 3 (IEC 61131), 16DQ 0.5A 24VDC BA, 16-ch. in groups of 8, 4A per group, incl. push-in front connector, Siemens

SIMATIC S7-1500 digital input/output module, DI16x 24 V DC BA, 16 channels in groups of 16, input delay typ. 3.2ms Input type 3 (IEC 61131), DQ16X24 V DC/0.5A BA; 16 channels in groups of 8; 4 A per group incl. push-in front connector
General information
Product type designation DI 16x24VDC / DQ16x24VDC/0.5A BA
HW functional status FS01
Firmware version V1.0.0
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
Engineering with
● STEP 7 TIA Portal configurable/integrated as of version V13 / V13
● STEP 7 configurable/integrated as of version V5.5 SP3 / -
● PROFIBUS as of GSD version/GSD revision V1.0 / V5.1
● PROFINET as of GSD version/GSD revision V2.3 / -
Operating mode
● DI Yes
● Counter No
● DQ Yes
● DQ with energy-saving function No
● PWM No
● Oversampling No
● MSI Yes
● MSO Yes
Supply voltage
Type of supply voltage DC
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes; through internal protection with 7 A per group
Input current
Current consumption, max. 30 mA
Output voltage
Rated value (DC) 24 V
Power
Power available from the backplane bus 1.1 W
Power loss
Power loss, typ. 3.45 W
Digital inputs
Number of digital inputs 16
Digital inputs, parameterizable No
Source/sink input P-reading
Input characteristic curve in accordance with IEC 61131, type 3 Yes
Input voltage
● Type of input voltage DC
● Rated value (DC) 24 V
● for signal "0" -30 to +5V
● for signal "1" +11 to +30V
Input current
● for signal "1", typ. 2.7 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable No
— at "0" to "1", min. 3 ms
— at "0" to "1", max. 4 ms
— at "1" to "0", min. 3 ms
— at "1" to "0", max. 4 ms
for interrupt inputs
— parameterizable No
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Digital outputs
Type of digital output Transistor
Number of digital outputs 16
Current-sourcing Yes
Short-circuit protection Yes
● Response threshold, typ. 1 A
Limitation of inductive shutdown voltage to L+ (-53 V)
Controlling a digital input Yes
Switching capacity of the outputs
● with resistive load, max. 0.5 A
● on lamp load, max. 5 W
Load resistance range
● lower limit 48 Ω
● upper limit 12 kΩ
Output voltage
● for signal "1", min. L+ (-0.8 V)
Output current
● for signal "1" rated value 0.5 A
● for signal "1" permissible range, max. 0.5 A
● for signal "0" residual current, max. 0.5 mA
Output delay with resistive load
● "0" to "1", max. 100 µs
● "1" to "0", max. 500 µs
Parallel switching of two outputs
● for logic links Yes
● for uprating No
● for redundant control of a load Yes
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 0.5 Hz
● on lamp load, max. 10 Hz
Total current of the outputs
● Current per channel, max. 0.5 A; see additional description in the manual
● Current per group, max. 4 A; see additional description in the manual
● Current per module, max. 8 A; see additional description in the manual
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Encoder
Connectable encoders
● 2-wire sensor Yes
— permissible quiescent current (2-wire sensor), max. 1.5 mA
Isochronous mode
Isochronous operation (application synchronized up to terminal) No
Interrupts/diagnostics/status information
Diagnostics function No
Substitute values connectable No
Alarms
● Diagnostic alarm No
● Maintenance interrupt No
● Hardware interrupt No
Diagnostic messages
● Monitoring the supply voltage No
● Wire-break No
● Short-circuit No
● Group error No
Diagnostics indication LED
● RUN LED Yes; Green LED
● ERROR LED Yes; Red LED
● Monitoring of the supply voltage (PWR-LED) Yes; Green LED
● Channel status display Yes; Green LED
● for channel diagnostics No
● for module diagnostics No
Potential separation
Potential separation channels
● between the channels No
● between the channels, in groups of 8
● between the channels and backplane bus Yes
Isolation
Isolation tested with 707 V DC (type test)
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. 0 °C
● horizontal installation, max. 60 °C
● vertical installation, min. 0 °C
● vertical installation, max. 40 °C
Decentralized operation
Prioritized startup Yes
Dimensions
Width 25 mm
Height 147 mm
Depth 129 mm
Weights
Weight, approx. 280 g
Other
Note: Supplied incl. 40-pole push-in front connectors