Image is illustrative
|
Simatic S7-300, analog output SM332, optically isolated, 2AO, U/I, 11/12bits resol., 20pin, remove/insert w. active backplane bus Code:
6ES7332-5HB01-0AB0
Cena (indicative)
Manufacturer
:
|
Availability:
21 days
|
Weight:
0.2646 kg/pc
|
Volume:
0.001 m3/pc
|
|
|
|
|
Simatic S7-300, analog output SM332, optically isolated, 2AO, U/I, 11/12bits resol., 20pin, remove/insert w. active backplane bus, Siemens
| Supply voltage |
| Load voltage L+ |
| ● Rated value (DC) |
24 V |
| ● Reverse polarity protection |
Yes |
| Input current |
| from load voltage L+ (without load), max. |
135 mA |
| from backplane bus 5 V DC, max. |
60 mA |
| Power loss |
| Power loss, typ. |
3 W |
| Analog outputs |
| Number of analog outputs |
2 |
| Voltage output, short-circuit protection |
Yes |
| Voltage output, short-circuit current, max. |
25 mA |
| Current output, no-load voltage, max. |
18 V |
| Output ranges, voltage |
| ● 0 to 10 V |
Yes |
| ● 1 V to 5 V |
Yes |
| ● -10 V to +10 V |
Yes |
| Output ranges, current |
| ● 0 to 20 mA |
Yes |
| ● -20 mA to +20 mA |
Yes |
| ● 4 mA to 20 mA |
Yes |
| Load impedance (in rated range of output) |
| ● with voltage outputs, min. |
1 kΩ |
| ● with voltage outputs, capacitive load, max. |
1 µF |
| ● with current outputs, max. |
500 Ω |
| ● with current outputs, inductive load, max. |
10 mH |
| Cable length |
| ● shielded, max. |
200 m |
| Analog value generation for the outputs |
| Integration and conversion time/resolution per channel |
| ● Resolution with overrange (bit including sign), max. |
12 bit; ±10 V, ±20 mA, 4 mA to 20 mA, 1 V to 5 V: 11 bit + sign; 0 V to 10 V, 0 mA to 20 mA: 12 bit |
| ● Conversion time (per channel) |
0.8 ms |
| Settling time |
| ● for resistive load |
0.2 ms |
| ● for capacitive load |
3.3 ms |
| ● for inductive load |
0.5 ms; 0.5 ms (1 mH); 3.3 ms (10 mH) |
| Errors/accuracies |
| Operational error limit in overall temperature range |
| ● Voltage, relative to output range, (+/-) |
0.5 % |
| ● Current, relative to output range, (+/-) |
0.6 % |
| Basic error limit (operational limit at 25 °C) |
| ● Voltage, relative to output range, (+/-) |
0.4 % |
| ● Current, relative to output range, (+/-) |
0.5 % |
| Interrupts/diagnostics/status information |
| Diagnostic functions |
Yes; Parameterizable |
| Substitute values connectable |
Yes; Parameterizable |
| Alarms |
| ● Diagnostic alarm |
Yes; Parameterizable |
| Diagnostic messages |
| ● Diagnostic information readable |
Yes |
| Diagnostics indication LED |
| ● Group error SF (red) |
Yes |
| Potential separation |
| Potential separation analog outputs |
| ● between the channels and backplane bus |
Yes |
| Isolation |
| Isolation tested with |
500 V DC |
| Connection method |
| required front connector |
20-pin |
| Dimensions |
| Width |
40 mm |
| Height |
125 mm |
| Depth |
117 mm |
| Weights |
| Weight |
220 g |
| last modified: |
11/21/2017 |
|
|
File description
|
File type
|
Download link
|
|
|
|
|
| "
6ES7332-5HB01-0AB0 datasheet
|
PDF
|
Download link
|
|
|
|
|
|
|
|
|