Image is illustrative
|
Simatic S7, Digital Output SM326, F-DO10x 24VDC/2A p.pole, failsafe digital outputs f. Simatic S7F systems, w. Diagnost. interrupt, LW, up to cat.4(EN9S4-1)/ SIL3(IEC61508)/ PLE (IS013849), 40pin Code:
6ES7326-2BF10-0AB0
Cena (indicative)
Manufacturer
:
|
Availability:
21 days
|
Weight:
0.36 kg/pc
|
Volume:
0.001 m3/pc
|
|
|
|
|
Simatic S7, Digital Output SM326, F-DO10x 24VDC/2A p.pole, failsafe digital outputs f. Simatic S7F systems, w. Diagnost. interrupt, LW, up to cat.4(EN9S4-1)/ SIL3(IEC61508)/ PLE (IS013849), 40pin, Siemens
| Supply voltage |
| Rated value (DC) |
24 V; 1L+ |
| Reverse polarity protection |
Yes |
| Load voltage L+ |
| ● Rated value (DC) |
24 V; 2L+, 3L+ |
| ● Reverse polarity protection |
No |
| Input current |
| from supply voltage 1L+, max. |
100 mA |
| from load voltage 2L+ (without load), max. |
100 mA |
| from load voltage 3L+ (without load), max. |
100 mA |
| from backplane bus 5 V DC, max. |
100 mA |
| Power loss |
| Power loss, typ. |
6 W |
| Digital outputs |
| Number of digital outputs |
10 |
| Short-circuit protection |
Yes |
| Switching capacity of the outputs |
| ● on lamp load, max. |
5 W |
| Output voltage |
| ● for signal "1", min. |
L+ (-1.0 V) |
| Output current |
| ● for signal "1" rated value |
2 A |
| ● for signal "1" permissible range for 0 to 40 °C, min. |
7 mA |
| ● for signal "1" permissible range for 0 to 40 °C, max. |
2.4 A |
| ● for signal "1" permissible range for 40 to 60 °C, min. |
7 mA |
| ● for signal "1" permissible range for 40 to 60 °C, max. |
2.4 A |
| ● for signal "0" residual current, max. |
0.5 mA |
| Switching frequency |
| ● with resistive load, max. |
25 Hz |
| ● with inductive load, max. |
25 Hz |
| ● on lamp load, max. |
10 Hz |
| Total current of the outputs (per group) |
| horizontal installation |
| — up to 40 °C, max. |
10 A |
| — up to 60 °C, max. |
6 A |
| vertical installation |
| — up to 40 °C, max. |
5 A |
| Cable length |
| ● shielded, max. |
1 000 m |
| ● unshielded, max. |
600 m |
| Interrupts/diagnostics/status information |
| Alarms |
| ● Diagnostic alarm |
Yes |
| Diagnostic messages |
| ● Diagnostic information readable |
Yes |
| Diagnostics indication LED |
| ● Fail-safe operation |
Yes |
| ● Group error SF (red) |
Yes |
| Potential separation |
| Potential separation digital outputs |
| ● between the channels |
Yes |
| ● between the channels, in groups of |
5 |
| ● between the channels and backplane bus |
Yes |
| ● between the channels and the power supply of the electronics |
Yes |
| Isolation |
| Isolation tested with |
370V for 1 min |
| Standards, approvals, certificates |
| Highest safety class achievable in safety mode |
| ● acc. to DIN VDE 0801 |
AK 5 and 6 |
| ● acc. to EN 954 |
Cat. 4 |
| ● SIL acc. to IEC 61508 |
SIL 3 |
| Connection method |
| required front connector |
40-pin |
| Dimensions |
| Width |
40 mm |
| Height |
125 mm |
| Depth |
120 mm |
| Weights |
| Weight |
330 g |
| last modified: |
11/21/2017 |
|
|
File description
|
File type
|
Download link
|
|
|
|
|
| "
6ES7326-2BF10-0AB0 datasheet
|
PDF
|
Download link
|
|
|
|
|
|
|
|
|
|