Simatic S7-1200, Analog Output, SM 1232, 2AO, ±10V, 14bit res., 0/4..20mA, 13bit res., Siemens
Image is illustrative
Simatic S7-1200, Analog Output, SM 1232, 2AO, ±10V, 14bit res., 0/4..20mA, 13bit res., Siemens
Code: 6ES7232-4HB32-0XB0
Cena (indicative)
269,80 €  /pc
Manufacturer :
Availability:
ask for dd
Weight:
0.1775 kg/pc
Volume:
0.0005 m3/pc
Quantity:
Plus sign Minus sign
 

 

Simatic S7-1200, Analog Output, SM 1232, 2AO, ±10V, 14bit res., 0/4..20mA, 13bit res., Siemens

SIMATIC S7-1200, Analog output, SM 1232, 2 AO, +/-10 V, 14-bit resolution, or 0-20 mA/4-20 mA, 13-bit resolution
General information
Product type designation SM 1232, AQ 2x14 bit
Supply voltage
Rated value (DC)
● 24 V DC Yes
Input current
Current consumption, typ. 45 mA
from backplane bus 5 V DC, typ. 80 mA
Power loss
Power loss, typ. 1.5 W
Analog outputs
Number of analog outputs 2; Current or voltage
Output ranges, voltage
● -10 V to +10 V Yes
Output ranges, current
● 0 to 20 mA Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 1 000 Ω
● with current outputs, max. 600 Ω
Cable length
● shielded, max. 100 m; shielded, twisted pair
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution (incl. overrange) Voltage: 14 bit; Current : 13 bit
Errors/accuracies
Temperature error (relative to output range), (+/-) 25 °C ±0.3%, to 55 °C ±0.6% total measurement range
Basic error limit (operational limit at 25 °C)
● Voltage, relative to output range, (+/-) 0.3 %
● Current, relative to output range, (+/-) 0.3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Common mode voltage, max. 12 V
Interrupts/diagnostics/status information
Alarms Yes
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
Diagnostic messages
● Monitoring the supply voltage Yes
● Wire-break Yes
● Short-circuit Yes
Diagnostics indication LED
● for status of the outputs Yes
● for maintenance Yes
Degree and class of protection
Degree of protection acc. to EN 60529
● IP20 Yes
Standards, approvals, certificates
CE mark Yes
CSA approval Yes
FM approval Yes
RCM (formerly C-TICK) Yes
Ambient conditions
Free fall
● Fall height, max. 0.3 m; five times, in product package
Ambient temperature during operation
● min. -20 °C
● max. 60 °C
● horizontal installation, min. -20 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -20 °C
● vertical installation, max. 50 °C
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Air pressure acc. to IEC 60068-2-13
● Operation, min. 795 hPa
● Operation, max. 1 080 hPa
● Storage/transport, min. 660 hPa
● Storage/transport, max. 1 080 hPa
Relative humidity
● Operation at 25 ℃ without condensation, max. 95 %
Pollutant concentrations
● SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
Connection method
required front connector Yes
Mechanics/material
Enclosure material (front)
● Plastic Yes
Dimensions
Width 45 mm
Height 100 mm
Depth 75 mm
Weights
Weight, approx. 180 g
last modified: 11/10/2018
 
 