Featured Products!
Cable Gland Progress EMC easyConnect, M12x1.5, ø5..6.5mm| 2piece sealing insert, thread 5mm, ss 1.4310 contact spring, -60..100°C, nickel-plated brass, TPE, NBR, incl. O-ring, CE/IEC/VDE/UL/EAC, IP68/69, Agro
Cable Gland Progress EMC easyConnect, M12x1.5, ø5..6.5mm| 2piece sealing insert, thread 5mm, ss 1.4310 contact spring, -60..100°C, nickel-plated brass, TPE, NBR, incl. O-ring, CE/IEC/VDE/UL/EAC, IP68/69, Agro



Simatic S7-1200, CPU 1212C, compact CPU, DC/DC/DC, onboard I/O: 8DI 24VDC, 6DO 24VDC, 2AI 0..10VDC, sv 20.4..28.8VDC, progr./data memory 75kB, Siemens
Image is illustrative
Simatic S7-1200, CPU 1212C, compact CPU, DC/DC/DC, onboard I/O: 8DI 24VDC, 6DO 24VDC, 2AI 0..10VDC, sv 20.4..28.8VDC, progr./data memory 75kB, Siemens
Code: 6ES7212-1AE40-0XB0
Cena (indicative)
267,70 €  /pc
Manufacturer :
Availability:
21 days
Weight:
0.357 kg/pc
Volume:
0.001 m3/pc
Quantity:
Plus sign Minus sign
 

 

Simatic S7-1200, CPU 1212C, compact CPU, DC/DC/DC, onboard I/O: 8DI 24VDC/ 6DO 24VDC/ 2AI 0..10VDC, 20.4..28.8VDC, program/data memory 75kB, Siemens

General information
Product type designation CPU 1212C DC/DC/DC
Engineering with
● Programming package STEP 7 V13 SP1 or higher
Supply voltage
Rated value (DC)
● 24 V DC Yes
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 20.4 V
● permissible range, upper limit (DC) 28.8 V
Input current
Current consumption (rated value) 400 mA; Typical
Inrush current, max. 12 A; at 28.8 V DC
Output current
for backplane bus (5 V DC), max. 1 000 mA; Max. 5 V DC for SM and CM
Encoder supply
24 V encoder supply
● 24 V Permissible range: 20.4V to 28.8V
Power loss
Power loss, typ. 9 W
Memory
Work memory
● integrated 50 kbyte
● expandable No
Load memory
● integrated 1 Mbyte
● Plug-in (SIMATIC Memory Card), max. 2 Gbyte; with SIMATIC memory card
Backup
● present Yes; maintenance-free
● without battery Yes
CPU processing times
for bit operations, typ. 0.085 µs; / Operation
for word operations, typ. 1.7 µs; / Operation
for floating point arithmetic, typ. 2.3 µs; / Operation
CPU-blocks
Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of addressable blocks ranges from 1 to 65535. There is no restriction, the entire working memory can be used
OB
● Number, max. Limited only by RAM for code
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max. 10 kbyte
Flag
● Number, max. 4 kbyte; Size of bit memory address area
Address area
I/O address area
● Inputs 1 024 byte
● Outputs 1 024 byte
Process image
● Inputs, adjustable 1 kbyte
● Outputs, adjustable 1 kbyte
Hardware configuration
Number of modules per system, max. 3 comm. modules, 1 signal board, 2 signal modules
Time of day
Clock
● Hardware clock (real-time) Yes
● Backup time 480 h; Typical
● Deviation per day, max. ±60 s/month at 25 °C
Digital inputs
Number of digital inputs 8; Integrated
● of which inputs usable for technological functions 6; HSC (High Speed Counting)
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 8
Input voltage
● Rated value (DC) 24 V
● for signal "0" 5 V DC at 1 mA
● for signal "1" 15 V DC at 2.5 mA
Input current
● for signal "1", typ. 1 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 μs; 0.05 / 0.1 / 0.2 / 0.4 / 0.8 / 1.6 / 3.2 / 6.4 / 10.0 / 12.8 / 20.0 ms
— at "0" to "1", min. 0.1 µs
— at "0" to "1", max. 20 ms
for interrupt inputs
— parameterizable Yes
for counter/technological functions
— parameterizable Single phase: 3 @ 100 kHz & 1 @ 30 kHz, differential: 3 @ 80 kHz & 1 @ 30 kHz
Cable length
● shielded, max. 500 m; 50 m for technological functions
● unshielded, max. 300 m; For technological functions: No
Digital outputs
Number of digital outputs 6
● of which high-speed outputs 4; 100 kHz Pulse Train Output
Short-circuit protection No; to be provided externally
Limitation of inductive shutdown voltage to L+ (-48 V)
Switching capacity of the outputs
● with resistive load, max. 0.5 A
● on lamp load, max. 5 W
Output voltage
● for signal "0", max. 0.1 V; with 10 kOhm load
● for signal "1", min. 20 V
Output current
● for signal "1" rated value 0.5 A
● for signal "0" residual current, max. 0.1 mA
Output delay with resistive load
● "0" to "1", max. 1 µs
● "1" to "0", max. 3 µs
Cable length
● shielded, max. 500 m
● unshielded, max. 150 m
Analog inputs
Number of analog inputs 2
Input ranges
● Voltage Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
● Input resistance (0 to 10 V) ≥100k ohms
Cable length
● shielded, max. 100 m; twisted and shielded
Analog outputs
Number of analog outputs 0
Cable length
● shielded, max. 100 m; shielded, twisted pair
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 10 bit
● Integration time, parameterizable Yes
● Conversion time (per channel) 625 µs
Encoder
Connectable encoders
● 2-wire sensor Yes
1. Interface
Interface type PROFINET
Physics Ethernet
Isolated Yes
automatic detection of transmission rate Yes
Autonegotiation Yes
Autocrossing Yes
Functionality
● PROFINET IO Controller Yes
● PROFINET IO Device Yes
PROFINET IO Controller
Services
— Number of IO devices with prioritized startup, max. 16
Protocols
Supports protocol for PROFINET IO Yes
PROFIBUS Yes; CM 1243-5 required
AS-Interface Yes
Protocols (Ethernet)
● TCP/IP Yes
Open IE communication
● ISO-on-TCP (RFC1006) Yes
Further protocols
● MODBUS Yes
Communication functions
S7 communication
● supported Yes
● as server Yes
● as client Yes
Web server
● supported Yes
Test commissioning functions
Status/control
● Status/control variable Yes
Forcing
● Forcing Yes
Diagnostic buffer
● present Yes
Traces
● Number of configurable Traces 2; Up to 512 KB of data per trace are possible
Integrated Functions
Number of counters 6
Counting frequency (counter) max. 100 kHz
controlled positioning Yes
PID controller Yes
Number of alarm inputs 4
Number of pulse outputs 4
Limit frequency (pulse) 100 kHz
Potential separation
Potential separation digital inputs
● Potential separation digital inputs 500V AC for 1 minute
● between the channels, in groups of 1
Potential separation digital outputs
● Potential separation digital outputs 500V AC for 1 minute
● between the channels, in groups of 1
Permissible potential difference
between different circuits 500 V DC between 24 V DC and 5 V DC
EMC
Interference immunity against discharge of static electricity
● Interference immunity against discharge of static electricity acc. to IEC 61000-4-2 Yes
— Test voltage at air discharge 8 kV
— Test voltage at contact discharge 6 kV
Interference immunity to cable-borne interference
● Interference immunity on supply lines acc. to IEC 61000-4-4 Yes
● Interference immunity on signal cables acc. to IEC 61000-4-4 Yes
Interference immunity against voltage surge
● on the supply lines acc. to IEC 61000-4-5 Yes
Interference immunity against conducted variable disturbance induced by high-frequency fields
● Interference immunity against high-frequency radiation acc. to IEC 61000-4-6 Yes
Emission of radio interference acc. to EN 55 011
● Limit class A, for use in industrial areas Yes; Group 1
● Limit class B, for use in residential areas Yes; When appropriate measures are used to ensure compliance with the limits for Class B according to EN 55011
Degree and class of protection
Degree of protection acc. to EN 60529
● IP20 Yes
Standards, approvals, certificates
CE mark Yes
UL approval Yes
cULus Yes
FM approval Yes
RCM (formerly C-TICK) Yes
Marine approval Yes
Ambient conditions
Free fall
● Fall height, max. 0.3 m; five times, in product package
Ambient temperature during operation
● min. -20 °C
● max. 60 °C; Number of simultaneously activated inputs or outputs 4 or 3 (no adjacent points) at 60 °C horizontal or 50 °C vertical, 8 or 6 at 55 °C horizontal or 45 °C vertical
● horizontal installation, min. -20 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -20 °C
● vertical installation, max. 50 °C
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Air pressure acc. to IEC 60068-2-13
● Operation, min. 795 hPa
● Operation, max. 1 080 hPa
● Storage/transport, min. 660 hPa
● Storage/transport, max. 1 080 hPa
Relative humidity
● Operation, max. 95 %; no condensation
Vibrations
● Operation, tested according to IEC 60068-2-6 Yes
Pollutant concentrations
● SO2 at RH < 60% without condensation S02: < 0.5 ppm; H2S: < 0.1 ppm; RH < 60% condensation-free
Configuration
Programming
Programming language
— LAD Yes
— FBD Yes
— SCL Yes
Cycle time monitoring
● adjustable Yes
Dimensions
Width 90 mm
Height 100 mm
Depth 75 mm
last modified: 11/21/2017
 
 