Coding Profile PC, 50pcs/pck, Phoenix
Coding Profile PC, 50pcs/pck, Phoenix



Simatic ET 200SP, Analog Input Module, 4AI U/I 2wire, fits to BU-type A0, A1, color code CC03, module diagnosis, 16bit, acc. ±0.3%, Siemens
Image is illustrative
Simatic ET 200SP, Analog Input Module, 4AI U/I 2wire, fits to BU-type A0, A1, color code CC03, module diagnosis, 16bit, acc. ±0.3%, Siemens
Code: 6ES7134-6HD01-0BA1
Cena (indicative)
213,40 €  /pc
Manufacturer :
Availability:
ask for dd
Weight:
0.042 kg/pc
Volume:
0.0001 m3/pc
Quantity:
Plus sign Minus sign
 

 

Simatic ET 200SP, Analog Input Module, 4AI U/I 2wire, fits to BU-type A0, A1, color code CC03, module diagnosis, 16bit, acc. ±0.3%, Siemens

SIMATIC ET 200SP, ANALOG INPUT MODULE, AI 4XU/I 2-WIRE STANDARD, PACKING UNIT: 1 PIECE, FITS TO BU-TYPE A0, A1, COLOR CODE CC03, MODULE DIAGNOSIS, 16BIT, +/-0,3%
General information
Product type designation AI 4x U/I 2-wire
HW functional status From FS02
Firmware version V2.0
● FW update possible Yes
usable BaseUnits BU type A0, A1
Color code for module-specific color identification plate CC03
Product function
● I&M data Yes; I&M0 to I&M3
● Measuring range scalable No
Engineering with
● STEP 7 TIA Portal configurable/integrated as of version V14 / -
● STEP 7 configurable/integrated as of version V5.6 and higher
● PCS 7 configurable/integrated as of version V8.1 SP1
● PROFIBUS as of GSD version/GSD revision One GSD file each, Revision 3 and 5 and higher
● PROFINET as of GSD version/GSD revision GSDML V2.3
Operating mode
● Oversampling No
● MSI No
CiR – Configuration in RUN
Reparameterization possible in RUN Yes
Calibration possible in RUN No
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 37 mA; without sensor supply
Encoder supply
24 V encoder supply
● 24 V Yes
● Short-circuit protection Yes
● Output current, max. 20 mA; max. 50 mA per channel for a duration < 10 s
Power loss
Power loss, typ. 0.85 W; Without encoder supply voltage
Address area
Address space per module
● Address space per module, max. 8 byte; + 1 byte for QI information
Hardware configuration
Automatic encoding
● Mechanical coding element Yes
Selection of BaseUnit for connection variants
● 2-wire connection BU type A0, A1
Analog inputs
Number of analog inputs 4; Differential inputs
permissible input voltage for voltage input (destruction limit), max. 30 V
permissible input current for current input (destruction limit), max. 50 mA
Cycle time (all channels), min. Sum of the basic conversion times and additional processing times (depending on the parameterization of the active channels)
Input ranges (rated values), voltages
● 0 to +10 V Yes; 15 bit
● Input resistance (0 to 10 V) 120 kΩ
● 1 V to 5 V Yes; 15 bit
● Input resistance (1 V to 5 V) 120 kΩ
● -10 V to +10 V Yes; 16 bit incl. sign
● Input resistance (-10 V to +10 V) 120 kΩ
● -5 V to +5 V Yes; 16 bit incl. sign
● Input resistance (-5 V to +5 V) 120 kΩ
Input ranges (rated values), currents
● 0 to 20 mA Yes; 15 bit
● Input resistance (0 to 20 mA) 100 Ω; + approx. 0.7 V diode forward voltage
● 4 mA to 20 mA Yes; 15 bit
● Input resistance (4 mA to 20 mA) 100 Ω; + approx. 0.7 V diode forward voltage
Cable length
● shielded, max. 1 000 m; 200 m for voltage measurement
Analog value generation for the inputs
Measurement principle integrating (Sigma-Delta)
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Integration time, parameterizable Yes
● Interference voltage suppression for interference frequency f1 in Hz 16.6 / 50 / 60 Hz
● Conversion time (per channel) 180 / 60 / 50 ms
Smoothing of measured values
● Number of smoothing levels 4; None; 4/8/16 times
● parameterizable Yes
Encoder
Connection of signal encoders
● for voltage measurement Yes
● for current measurement as 2-wire transducer Yes
— Burden of 2-wire transmitter, max. 650 Ω
● for current measurement as 4-wire transducer No
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %
Temperature error (relative to input range), (+/-) 0.005 %/K
Crosstalk between the inputs, min. 50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.05 %
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 0.5 %
● Current, relative to input range, (+/-) 0.5 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.3 %
● Current, relative to input range, (+/-) 0.3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 70 dB
● Common mode voltage, max. 10 V
● Common mode interference, min. 90 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal) No
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
● Limit value alarm No
Diagnostic messages
● Monitoring the supply voltage Yes
● Wire-break Yes; at 4 to 20 mA
● Short-circuit Yes; with 1 to 5 V or 2-wire mode: Short-circuit of the encoder supply to ground or of an input to the encoder supply
● Group error Yes
● Overflow/underflow Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; Green LED
● Channel status display Yes; Green LED
● for channel diagnostics No
● for module diagnostics Yes; Green/red LED
Potential separation
Potential separation channels
● between the channels Yes; channel group-specific between 2-wire current input group and voltage input group
● between the channels and backplane bus Yes
● between the channels and the power supply of the electronics Yes; only for voltage inputs
Permissible potential difference
between the inputs (UCM) 10 V DC
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Suitable for applications according to AMS 2750 Yes; Declaration of Conformity, see online support entry 109757262
Suitable for applications according to CQI-9 Yes
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -30 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -30 °C
● vertical installation, max. 50 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 2 000 m; On request: Installation altitudes greater than 2 000 m
Dimensions