Simatic DP, Electronics Module ET 200S: 2AI RTD HF, W15mm, 15bit+sign acc. ±0.1%, for 2/3/4wire sensors, w. internal compensation of the line resistance, w. SF LED (group fault), Siemens
Image is illustrative
Simatic DP, Electronics Module ET 200S: 2AI RTD HF, W15mm, 15bit+sign acc. ±0.1%, for 2/3/4wire sensors, w. internal compensation of the line resistance, w. SF LED (group fault), Siemens
Code: 6ES7134-4NB51-0AB0
Cena (indicative)
333,20 €  /pc
Manufacturer :
Availability:
ask for dd
Weight:
0.0452 kg/pc
Volume:
0.0001 m3/pc
Quantity:
Plus sign Minus sign
 

 

Simatic DP, Electronics Module ET 200S: 2AI RTD HF, W15mm, 15bit+sign acc. ±0.1%, for 2/3/4wire sensors, w. internal compensation of the line resistance, w. SF LED (group fault), Siemens

SIMATIC DP, Electronics module ET 200S: 2AI RTD High Feature, 15 mm width, 15 bit+sign accuracy +/-0.1%, for 2-/3-/4-wire sensors, with internal compensation of the line resistance, with SF LED (group fault)
Supply voltage
Load voltage L+
● Rated value (DC) 24 V; From power module
● Reverse polarity protection Yes
Input current
from load voltage L+ (without load), max. 30 mA
from backplane bus 3.3 V DC, max. 10 mA
Power loss
Power loss, typ. 0.6 W
Address area
Address space per module
● Address space per module, max. 4 byte
Analog inputs
Number of analog inputs 2
permissible input voltage for voltage input (destruction limit), max. 9 V
Constant measurement current for resistance-type transmitter, typ. 1.25 mA
Cycle time (all channels) max. Number of active channels per module x basic conversion time
Technical unit for temperature measurement adjustable Yes
Input ranges
● Voltage No
● Current No
● Thermocouple No
● Resistance thermometer Yes
● Resistance Yes
Input ranges (rated values), resistance thermometer
● Cu 10 Yes
● Input resistance (Cu 10) 10 MΩ
● Ni 100 Yes
● Input resistance (Ni 100) 10 MΩ
● Ni 1000 Yes
● Input resistance (Ni 1000) 10 MΩ
● Ni 120 Yes
● Input resistance (Ni 120) 10 MΩ
● Ni 200 Yes
● Input resistance (Ni 200) 10 MΩ
● Ni 500 Yes
● Input resistance (Ni 500) 10 MΩ
● Pt 100 Yes
● Input resistance (Pt 100) 10 MΩ
● Pt 1000 Yes
● Input resistance (Pt 1000) 10 MΩ
● Pt 200 Yes
● Input resistance (Pt 200) 10 MΩ
● Pt 500 Yes
● Input resistance (Pt 500) 10 MΩ
Input ranges (rated values), resistors
● 0 to 150 ohms Yes
● Input resistance (0 to 150 ohms) 10 MΩ
● 0 to 300 ohms Yes
● Input resistance (0 to 300 ohms) 10 MΩ
● 0 to 600 ohms Yes
● Input resistance (0 to 600 ohms) 10 MΩ
● 0 to 3000 ohms Yes
● Input resistance (0 to 3000 ohms) 10 MΩ
Thermocouple (TC)
Temperature compensation
— internal temperature compensation Yes
Characteristic linearization
● parameterizable Yes; for Ptxxx, Nixxx
— for resistance thermometer Ptxxx, Nixxx
Cable length
● shielded, max. 200 m
Analog value generation for the inputs
Measurement principle integrating (Sigma-Delta)
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit; for Pt100, Ni100, Ni120, Pt200, Ni200, Pt500, Ni500, Pt1000, Ni1000, Cu10: 15 bit + sign; for 150, 300, 600, 3000 ohms: 15 bit; for PTC: 1 bit
● Integration time (ms) 16,7 / 20 ms
● Interference voltage suppression for interference frequency f1 in Hz 50 / 60 Hz
● Conversion time (per channel) Basic conversion time incl. integration time: 50 / 60 ms; additional conversion time for diagnostics of wire break test: 5 / 5 ms; additional conversion time for line compensation with 3-wire connection: 50 / 60 ms
Smoothing of measured values
● parameterizable Yes; In four stages by means of digital filtering
● Step: None Yes; 1x cycle time
● Step: low Yes; 4x cycle time
● Step: Medium Yes; 32x cycle time
● Step: High Yes; 64x cycle time
Encoder
Connection of signal encoders
● for resistance measurement with two-wire connection Yes
● for resistance measurement with three-wire connection Yes; internal compensation of the line resistances
● for resistance measurement with four-wire connection Yes
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %
Temperature error (relative to input range), (+/-) 0.0009 %/K
Crosstalk between the inputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to input range), (+/-) 0.05 %
Operational error limit in overall temperature range
● Resistance thermometer, relative to input range, (+/-) Resistance-type transmitter: ±0.1 %; Pt100, Pt200, Pt500, Pt1000 standard: ±1.0 K; Pt100, Pt200, Pt500, Pt1000 climate: ±0.25 K; Ni100, Ni120, Ni200, Ni500, Ni1000 standard and climate: ±0.4 K; Cu10 ±1.5 K
Basic error limit (operational limit at 25 °C)
● Resistance thermometer, relative to input range, (+/-) Resistance-type transmitter: ±0.05 %; Pt100, Pt200, Pt500, Pt1000 standard: ±0.6 K; Pt100, Pt200, Pt500, Pt1000 climate: ±0.13 K; Ni100, Ni120, Ni200, Ni500, Ni1000 standard and climate: ±0.2 K; Cu10 ±1 K
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 70 dB
● Common mode interference (USS < 2.5 V) , min. 90 dB
Isochronous mode
Isochronous operation (application synchronized up to terminal) No
Interrupts/diagnostics/status information
Diagnostic messages
● Wire-break Yes
● Group error Yes
● Overflow/underflow Yes
Diagnostics indication LED
● Group error SF (red) Yes
Parameter
Remark 7 byte
Diagnostics wire break Disable / enable
Measurement type/range Deactivated/ 150 Ohm / 300 Ohm / 600 Ohm /Pt100/Pt200/Pt500/Pt1000 each standard or climate range / Ni100/Ni120/Ni200/Ni500/Ni1000 each standard or climate range / Cu10 each standard or climate range / PTC
Group diagnostics Disable / enable
Overflow/underflow Disable / enable
Potential separation
Potential separation analog inputs
● between the channels No
● between the channels and backplane bus Yes
● Between the channels and load voltage L+ Yes
Permissible potential difference
between MANA and M internally (UISO) 75 V DC/60 V AC
Isolation
Isolation tested with 500 V DC
Dimensions
Width 15 mm
Height 81 mm
Depth 52 mm
Weights
Weight, approx. 40 g
last modified: 11/10/2018
 
 