Image is illustrative
|
Simatic DP, Electronic Module ET 200S, 2DO relay 5A 24VDC/230VAC, W15mm, substitute value output w. LED SF (group fault), 5pcs/pck, Siemens Code:
6ES7132-4HB01-0AB0
Cena (indicative)
1 123,00 €
/pk
Package 5pc, unit price
224.6EUR/pc
Manufacturer
:
Availability:
21 days
|
Weight:
0.2079 kg/pc
|
Volume:
0.0005 m3/pc
|
|
|
|
|
Simatic DP, Electronic Module ET 200S, 2DO relay 5A 24VDC/230VAC, W15mm, substitute value output w. LED SF (group fault), 5pcs/pck, Siemens
Supply voltage |
Load voltage L+ |
● Rated value (DC) |
24 V; From power module |
● Reverse polarity protection |
Yes |
Input current |
from load voltage L+ (without load), max. |
30 mA |
from backplane bus 3.3 V DC, max. |
10 mA |
Power loss |
Power loss, typ. |
0.6 W |
Address area |
Address space per module |
● with packing |
2 bit |
● without packing |
1 byte |
Digital outputs |
Number of digital outputs |
2 |
Short-circuit protection |
No |
Limitation of inductive shutdown voltage to |
No |
Controlling a digital input |
Yes |
Output current |
● for signal "1" rated value |
5 A |
● for signal "1" minimum load current |
8 mA |
Switching frequency |
● with resistive load, max. |
2 Hz |
● with inductive load, max. |
0.5 Hz |
● on lamp load, max. |
2 Hz |
Relay outputs |
Switching capacity of contacts |
— Thermal continuous current, max. |
5 A |
Cable length |
● shielded, max. |
1 000 m |
● unshielded, max. |
600 m |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) |
No |
Interrupts/diagnostics/status information |
Diagnostic functions |
No |
Substitute values connectable |
Yes; 0/1 |
Diagnostics indication LED |
● Status indicator digital output (green) |
Yes |
Parameter |
Response to CPU/master STOP |
Substitute a value/keep last value |
Potential separation |
Potential separation digital outputs |
● between the channels |
Yes |
● between the channels and backplane bus |
Yes |
● Between the channels and load voltage L+ |
Yes |
Isolation |
tested with |
● Channels against backplane bus and load voltage L+ |
1500 V AC |
● Load voltage L+ against backplane bus |
500 V DC |
Ambient conditions |
Altitude during operation relating to sea level |
● Ambient air temperature-barometric pressure-altitude |
Tmin ... Tmax at 1 080 hPa ... 795 hPa (-1 000 m ... +2 000 m) // Tmin ... (Tmax - 10 K) at 795 hPa ... 658 hPa (+2 000 m ... +3 500 m) // Tmin ... (Tmax - 20 K) at 658 hPa ... 540 hPa (+3 500 m ... +5 000 m) |
Dimensions |
Width |
15 mm |
Height |
81 mm |
Depth |
52 mm |
Weights |
Weight, approx. |
50 g |
last modified: |
07/03/2018 |
|
File description
|
File type
|
Download link
|
|
|
|
|
|
|
|
|