Show all products categ.
Need assistance?
Featured Products!
Compact Cylinder ADNGF-40-40-P-A, 554254, Festo
Compact Cylinder ADNGF-40-40-P-A, 554254, Festo



Sitop PSU8200, Stabilized Power Supply, input 3x400..500VAC, output 40A 24VDC, Siemens
Image is illustrative
Sitop PSU8200, Stabilized Power Supply, input 3x400..500VAC, output 40A 24VDC, Siemens
Code: 6EP1437-3BA10
Cena (indicative)
820,90 €  /pc
Manufacturer :
Availability:
21 days
Weight:
3.57 kg/pc
Volume:
0.0051 m3/pc
Quantity:
Plus sign Minus sign
 

 

Sitop PSU8200 24V 40A Stabilized Power Supply, input 3x400..500VAC, output 40A 24VDC, Siemens

SITOP PSU8200 24 V/40 A
SITOP PSU8200 24 V/40 A Stabilized power supply Input: 400-500 V 3 AC Output: 24 V DC/40 A !!! Phased-out product !!! Successor: 6EP3437-8SB00-0AY0
Input
Input 3-phase AC
Rated voltage value Vin rated 400 ... 500 V
Voltage range AC 320 ... 575 V
Wide-range input Yes
Mains buffering at Iout rated, min. 15 ms; at Vin = 400 V
Rated line frequency 1 50 Hz
Rated line frequency 2 60 Hz
Rated line range 47 ... 63 Hz
Input current
● at rated input voltage 400 V 2.6 A
● at rated input voltage 500 V 2.1 A
Switch-on current limiting (+25 °C), max. 56 A
I²t, max. 2.24 A²·s
Built-in incoming fuse none
Protection in the mains power input (IEC 898) Required: 3-pole connected miniature circuit breaker 10 ... 16 A characteristic C or circuit breaker 3RV2011-1DA10 (setting 3 A) or 3RV2711-1DD10 (UL 489)
Output
Output Controlled, isolated DC voltage
Rated voltage Vout DC 24 V
Total tolerance, static ± 3 %
Static mains compensation, approx. 0.1 %
Static load balancing, approx. 0.2 %
Residual ripple peak-peak, max. 100 mV
Spikes peak-peak, max. (bandwidth: 20 MHz) 200 mV
Adjustment range 24 ... 28.8 V
Product function Output voltage adjustable Yes
Output voltage setting via potentiometer; max. 960 W
Status display Green LED for 24 V OK
Signaling Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
On/off behavior No overshoot of Vout (soft start)
Startup delay, max. 2.5 s
Voltage increase time of the output voltage maximum 500 ms
Rated current value Iout rated 40 A
Current range 0 ... 40 A
● Note +60 ... +70 °C: Derating 3.75%/K
Supplied active power typical 960 W
Short-term overload current
● at short-circuit during operation typical 120 A
Duration of overloading capability for excess current
● at short-circuit during operation 25 ms
Constant overload current
● on short-circuiting during the start-up typical 44 A
Parallel switching for enhanced performance Yes; switchable characteristic
Numbers of parallel switchable units for enhanced performance 2
Efficiency
Efficiency at Vout rated, Iout rated, approx. 92 %
Power loss at Vout rated, Iout rated, approx. 83 W
Closed-loop control
Dynamic mains compensation (Vin rated ±15 %), max. 1 %
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. 3 %
Setting time maximum 10 ms
Protection and monitoring
Output overvoltage protection < 35 V
Current limitation, typ. 44 A
Property of the output Short-circuit proof Yes
Short-circuit protection Alternatively, constant current characteristic approx. 44 A or latching shutdown
Enduring short circuit current RMS value
● typical 44 A
Overcurrent overload capability in normal operation overload capability 150 % Iout rated up to 5 s/min
Overload/short-circuit indicator LED yellow for "overload", LED red for "latching shutdown"
Safety
Primary/secondary isolation Yes
Galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
Protection class Class I
Leakage current
● maximum 3.5 mA
CE mark Yes
UL/cUL (CSA) approval cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus (CSA C22.2 No. 60950-1, UL 60950-1)
Explosion protection IECEx Ex nA nC IIC T4 Gc; ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cCSAus (CSA C22.2 No. 213, ANSI/ISA-12.12.01) Class I, Div. 2, Group ABCD, T4
FM approval -
CB approval Yes
Marine approval ABS, DNV GL
Degree of protection (EN 60529) IP20
EMC
Emitted interference EN 55022 Class B
Supply harmonics limitation EN 61000-3-2
Noise immunity EN 61000-6-2
Operating data
Ambient temperature
● during operation -25 ... +70 °C
— Note With natural convection; startup tested starting from -40 °C nominal voltage
● during transport -40 ... +85 °C
● during storage -40 ... +85 °C
Humidity class according to EN 60721 Climate class 3K3, no condensation
Mechanics
Connection technology screw-type terminals
Connections
● Supply input L1, L2, L3, PE: 1 screw terminal each for 0.2 ... 4 mm² single-core/finely stranded
● Output +, -: 2 screw terminals each for 0.33 ... 10 mm²
● Auxiliary 13, 14 (alarm signal): 1 screw terminal each for 0.14 ... 1.5 mm²
Width of the enclosure 150 mm
Height of the enclosure 125 mm
Depth of the enclosure 150 mm
Required spacing
● top 50 mm
● bottom 50 mm
● left 0 mm
● right 0 mm
Weight, approx. 3.4 kg
Product feature of the enclosure housing for side-by-side mounting Yes
Installation Snaps onto DIN rail EN 60715 35x15
Electrical accessories Buffer module
Mechanical accessories Device identification label 20 mm × 7 mm, TI-grey 3RT2900-1SB20
MTBF at 40 °C 885 739 h
Other information Specifications at rated input voltage and ambient temperature +25 °C (unless otherwise specified)
 
 