Sitop PSU8200, Stabilized Power Supply, input 120-230VAC/ 110-220VDC, output 20A 24VDC Code:
6EP1336-3BA10
Cena (indicative)
Manufacturer
:
Availability:
28 days
|
Weight:
1.26 kg/pc
|
Volume:
0.0023 m3/pc
|
|
|
|
|
Stabilized Power Supply Sitop PSU100M, input: 120-230VAC/110-220VDC, output: 24V/ 20ADC, Siemens
SITOP PSU8200 20A STABILIZED POWER SUPPLY INPUT: 120-230 V AC 110-220 V DC OUTPUT: 24 V/20 A DC
|
|
|
Input:
|
Input: |
1-phase AC or DC |
Supply voltage
at DC: |
110 ... 220 V |
Rated voltage value Vin rated: |
120 ... 230 V |
Voltage range AC
Note: |
85 ... 275 V
Derating of temperature necessary down to 50 °C at Vin < 100 V
AC or DC |
Input voltage at DC: |
88 ... 350 V |
Wide-range input: |
Yes |
Mains buffering at Iout rated, min.: |
20 ms; at Vin = 93/187 V |
Rated line frequency: |
50 ... 60 Hz |
Rated line range: |
47 ... 63 Hz |
Input current
at rated input voltage 120 V
at rated input voltage 230 V: |
4.6 A
2.5 A |
Switch-on current limiting (+25 °C), max.: |
20 A |
I2t, max.: |
5 A2·s |
Built-in incoming fuse: |
Yes |
Protection in the mains power input (IEC 898): |
Recommended miniature circuit breaker at 1-phase operation: 10 A characteristic C; required at 2-phase operation: circuit breaker2-pole connected or circuit breaker 3RV2711-1HD10 (UL 489) at 120 V or 3RV2711-1ED10 (UL 489) at 230 V |
Output:
|
Output: |
Controlled, isolated DC voltage |
Rated voltage Vout DC: |
24 V |
Total tolerance, static ±: |
3 % |
Static mains compensation, approx.: |
0.1 % |
Static load balancing, approx.: |
0.3 % |
Residual ripple peak-peak, max.: |
100 mV |
Residual ripple peak-peak, typ.: |
80 mV |
Spikes peak-peak, typ. (bandwidth: 20 MHz): |
200 mV |
Spikes peak-peak, typ. (bandwidth: 20 MHz): |
100 mV |
Adjustment range: |
24 ... 28.8 V |
Product function Output voltage adjustable: |
Yes |
Output voltage setting: |
via potentiometer |
Status display: |
Green LED for 24 V OK |
Signalling: |
Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK" |
On/off behavior: |
No overshoot of Vout (soft start) |