General

Note The current is determined by the fuse used, the voltage by the light indicator.
Number of rows 1
Number of connections 2
Nominal cross section 4 mm²
Color black
Insulating material PA
Flammability rating according to UL 94 V0
Area of application Railway industry
Machine building
Plant engineering
Rated surge voltage 6 kV
Rated operating voltage 250 V
Degree of pollution 3
Overvoltage category III
Insulating material group I
Maximum power dissipation max. 1.6 W (with single arrangement of the fuse terminal block in the event of overload)
max. 1.6 W (With interconnected arrangement of several fuse terminal blocks in the event of overload)
max. 4 W (with single arrangement of the fuse terminal block in the event of a short-circuit)
max. 2.5 W (With interconnected arrangement of several fuse terminal blocks in the event of a short-circuit)
Connection in acc. with standard IEC 60947-7-3
Maximum load current 6.3 A (with 6 mm² conductor cross section, rigid)
Nominal current IN 6.3 A (the current is determined by the fuse used)
Nominal voltage UN 400 V
Fuse G / 5 x 20
Fuse type Glass / ceramics / ...
Open side panel Yes
Number of positions 1
Shock protection test specification DIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protection guaranteed
Finger protection guaranteed
Note Swing the locking lever to its final position before replacing the fuse.
Inscriptions Test passed
Result of surge voltage test Test passed
Surge voltage test setpoint 4.8 kV
Result of power-frequency withstand voltage test Test passed
Power frequency withstand voltage setpoint 1.5 kV
Result of tight fit on support Test passed
Contact resistance Test passed
Compatibitity between modular fuse terminal block and fuse insert Test passed
Actuatiing forces on plug in or lever in fuse insert carriers Test passed
Result of the test for mechanical stability of terminal points (5 x conductor connection) Test passed
Result of flexion and pull-out test Test passed
Bending test rotation speed 10 rpm
Bending test turns 135
Bending test conductor cross section/weight 0.2 mm² / 0.2 kg
4 mm² / 0.9 kg
6 mm² / 1.4 kg
Conductor cross section tensile test 0.2 mm²
Tractive force setpoint 10 N
Conductor cross section tensile test 4 mm²
Tractive force setpoint 60 N
Conductor cross section tensile test 6 mm²
Tractive force setpoint 80 N
Testing the rated value of the power dissipation (overload and short circuit Protection) Test passed
Testing the rated value of the power dissipation (exclusively short circuit protection) Test passed
Result service life test Test passed
Result of temperature-rise test Test passed
Result of aging test Test passed
Temperature cycles 192
Result of thermal test Test passed
Oscillation, broadband noise test result Test passed
Test specification, oscillation, broadband noise DIN EN 50155 (VDE 0115-200):2018-05
Test spectrum Service life test category 2, bogie-mounted
Test frequency f1 = 5 Hz to f2 = 250 Hz
ASD level 6.12 (m/s²)²/Hz
Acceleration 3.12g
Test duration per axis 5 h
Test directions X-, Y- and Z-axis
Shock test result Test passed
Test specification, shock test DIN EN 50155 (VDE 0115-200):2018-05
Shock form Half-sine
Acceleration 30g
Shock duration 18 ms
Number of shocks per direction 3
Test directions X-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B) 130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) 130 °C
Static insulating material application in cold -60 °C
Surface flammability NFPA 130 (ASTM E 162) passed
Specific optical density of smoke NFPA 130 (ASTM E 662) passed
Smoke gas toxicity NFPA 130 (SMP 800C) passed
Calorimetric heat release NFPA 130 (ASTM E 1354) 28 MJ/kg
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 - HL 3

Dimensions

Width 6.2 mm
End cover width 2.2 mm
Length 56 mm
Height 57.3 mm
Height NS 35/7,5 64.8 mm
Height NS 35/15 72.3 mm

Ambient conditions

Operating temperature -60 °C ... 105 °C (max. short-term operating temperature 130°C)
Ambient temperature (storage/transport) -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport) 30 % ... 70 %
Ambient temperature (assembly) -5 °C ... 70 °C
Ambient temperature (actuation) -5 °C ... 70 °C

Connection data

Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 6 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 4 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 10
Conductor cross section flexible, with ferrule without plastic sleeve min. 0.25 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max. 4 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min. 0.25 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max. 4 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum 0.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum 1 mm²
Connection method Push-in connection
Stripping length 10 mm ... 12 mm
Internal cylindrical gage A4

Standards and Regulations

Connection in acc. with standard CSA
IEC 60947-7-3
Flammability rating according to UL 94 V0

Environmental Product Compliance

China RoHS Environmentally friendly use period: unlimited = EFUP-e
No hazardous substances above threshold values

ECLASS

ECLASS 10.0.1 27141116
ECLASS 11.0 27141116
ECLASS 4.0 27141100
ECLASS 4.1 27141100
ECLASS 5.0 27141100
ECLASS 5.1 27141100
ECLASS 6.0 27141100
ECLASS 7.0 27141116
ECLASS 9.0 27141116

ETIM

ETIM 2.0 EC000897
ETIM 3.0 EC000899
ETIM 4.0 EC000899
ETIM 6.0 EC000899
ETIM 7.0 EC000899

UNSPSC

UNSPSC 6.01 30211811
UNSPSC 7.0901 39121410
UNSPSC 11 39121410
UNSPSC 12.01 39121410
UNSPSC 13.2 39121410
UNSPSC 18.0 39121410
UNSPSC 19.0 39121410
UNSPSC 20.0 39121410
UNSPSC 21.0 39121410
 
 
Elit OÜ | e-post: elit@elit.ee | +372 622 9119 | 2016 ©


 
X
 
X