Elit logo e-Elit - leading
electronic and automation component
online distributor
Elit shopping basket
Items: Total:
0
0,00 €
    search
Log in
Username/Email Address:

Password:
Show all products categ.
Need assistance?
Featured Products!
Cartridge Fuse HRC, 10x38, 1A 500VAC, gG, MaxGE
Cartridge Fuse HRC, 10x38, 1A 500VAC, gG, MaxGE



Disconnect Terminal Block UT 2.5-TG-P/P, 50pcs/pck, Phoenix
Image is illustrative
Disconnect Terminal Block UT 2.5-TG-P/P, 50pcs/pck, Phoenix
Code: 3046391
Cena
80,00 €  /pk
Package 50pc, unit price 1.6EUR/pc
Manufacturer :
Availability:
28 days
Weight:
0.01 kg/pc
Volume:
0 m3/pc
Quantity:
Plus sign Minus sign
 

 

Disconnect Terminal Block UT 2.5-TG-P/P, 50pcs/pck, Phoenix

General

Note Current and voltage are determined by the plug used.
Number of rows 1
Number of connections 2
Potentials 1
Nominal cross section 2.5 mm²
Color gray
Insulating material PA
Flammability rating according to UL 94 V0
Area of application Railway industry
Machine building
Plant engineering
Mounting type NS 35/7,5
Rated surge voltage 6 kV
Degree of pollution 3
Overvoltage category III
Insulating material group I
Maximum load current 20 A (with 4 mm² conductor cross section)
Nominal current IN 20 A (with 4 mm² conductor cross section)
Nominal voltage UN 400 V (Current and voltage are determined by the plug used.)
Open side panel Yes
Shock protection test specification DIN EN 50274 (VDE 0660-514):2002-11
Back of the hand protection guaranteed
Finger protection guaranteed
Result of surge voltage test Test passed
Surge voltage test setpoint 7.2 kV
Result of power-frequency withstand voltage test Test passed
Power frequency withstand voltage setpoint 1.89 kV
Result of the test for mechanical stability of terminal points (5 x conductor connection) Test passed
Result of flexion and pull-out test Test passed
Bending test rotation speed 10 (+/- 2) rpm
Bending test turns 135
Bending test conductor cross section/weight 0.14 mm² / 0.2 kg
2.5 mm² / 0.7 kg
Tensile test result Test passed
Conductor cross section tensile test 0.14 mm²
Tractive force setpoint 10 N
Conductor cross section tensile test 2.5 mm²
Tractive force setpoint 50 N
Conductor cross section tensile test 4 mm²
Tractive force setpoint 60 N
Result of voltage-drop test Test passed
Requirements, voltage drop U1 ≤ 6,4 mV (1,6 mV x number of conductor
clamping units or disconnect unit contact
points)
U2 ≤ 1,5 x U1
Result of temperature-rise test Test passed
Requirement temperature-rise test Increase in temperature ≤ 45 K
Short circuit stability result Test passed
Conductor cross section short circuit testing 2.5 mm²
Short-time current 0.3 kA
Result of thermal test Test passed
Proof of thermal characteristics (needle flame) effective duration 30 s
Oscillation, broadband noise test result Test passed
Test specification, oscillation, broadband noise DIN EN 50155 (VDE 0115-200):2018-05
Test spectrum Service life test category 2, bogie-mounted
Test frequency f1 = 5 Hz to f2 = 250 Hz
ASD level 6.12 (m/s²)²/Hz
Acceleration 3.12g
Test duration per axis 5 h
Test directions X-, Y- and Z-axis
Shock form Half-sine
Acceleration 5g
Shock duration 30 ms
Number of shocks per direction 3
Test directions X-, Y- and Z-axis (pos. and neg.)
Relative insulation material temperature index (Elec., UL 746 B) 130 °C
Temperature index of insulation material (DIN EN 60216-1 (VDE 0304-21)) 125 °C
Static insulating material application in cold -60 °C
Surface flammability NFPA 130 (ASTM E 162) passed
Specific optical density of smoke NFPA 130 (ASTM E 662) passed
Calorimetric heat release NFPA 130 (ASTM E 1354) 27,5 MJ/kg
Smoke gas toxicity NFPA 130 (SMP 800C) passed
Fire protection for rail vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
Fire protection for rail vehicles (DIN EN 45545-2) R26 HL 1 - HL 3

Dimensions

Width 5.2 mm
End cover width 2.2 mm
Length 57.8 mm
Height NS 35/7,5 47.5 mm
Height NS 35/15 55 mm

Connection data

Connection method Screw connection
Screw thread M3
Stripping length 9 mm
Tightening torque, min 0.5 Nm
Tightening torque max 0.6 Nm
Connection in acc. with standard IEC 60947-7-1
Conductor cross section solid min. 0.14 mm²
Conductor cross section solid max. 4 mm²
Conductor cross section AWG min. 26
Conductor cross section AWG max. 12
Conductor cross section flexible min. 0.14 mm²
Conductor cross section flexible max. 4 mm²
Min. AWG conductor cross section, flexible 26
Max. AWG conductor cross section, flexible 12
Conductor cross section flexible, with ferrule without plastic sleeve min. 0.14 mm²
Conductor cross section flexible, with ferrule without plastic sleeve max. 2.5 mm²
Conductor cross section flexible, with ferrule with plastic sleeve min. 0.14 mm²
Conductor cross section flexible, with ferrule with plastic sleeve max. 2.5 mm²
2 conductors with same cross section, solid min. 0.14 mm²
2 conductors with same cross section, solid max. 1.5 mm²
2 conductors with same cross section, stranded min. 0.14 mm²
2 conductors with same cross section, stranded max. 1.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, minimum 0.5 mm²
Two conductors with the same cross section, flexible, with TWIN ferrules, with plastic sleeve, maximum 1.5 mm²
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, minimum 0.14 mm²
Two conductors with the same cross section stranded, with ferrule and without plastic sleeve, maximum 1.5 mm²
Internal cylindrical gage A3

Ambient conditions

Operating temperature -60 °C ... 105 °C (max. short-term operating temperature 130°C)
Ambient temperature (storage/transport) -25 °C ... 60 °C (for a short time, not exceeding 24 h, -60 °C to +70 °C)
Permissible humidity (storage/transport) 30 % ... 70 %
Ambient temperature (assembly) -5 °C ... 70 °C
Ambient temperature (actuation) -5 °C ... 70 °C

Standards and Regulations

Connection in acc. with standard CSA
IEC 60947-7-1
Flammability rating according to UL 94 V0

Environmental Product Compliance

China RoHS Environmentally Friendly Use Period = 50 years
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”

ECLASS

ECLASS 10.0.1 27141126
ECLASS 11.0 27141126
ECLASS 4.0 27141100
ECLASS 4.1 27141100
ECLASS 5.0 27141100
ECLASS 5.1 27141100
ECLASS 6.0 27141100
ECLASS 7.0 27141126
ECLASS 9.0 27141126

ETIM

ETIM 2.0 EC000902
ETIM 3.0 EC000902
ETIM 4.0 EC000902
ETIM 6.0 EC000902
ETIM 7.0 EC000902

UNSPSC

UNSPSC 6.01 30211811
UNSPSC 7.0901 39121410
UNSPSC 11 39121410
UNSPSC 12.01 39121410
UNSPSC 13.2 39121410
UNSPSC 18.0 39121410
UNSPSC 19.0 39121410
UNSPSC 20.0 39121410
UNSPSC 21.0 39121410
 
 
Elit OÜ | e-post: elit@elit.ee | +372 622 9119 | 2016 ©


 