DC/DC Converter QUINT4-PS/24DC/12DC/8/PT, 1pcs/pck, PhoenixInput data
Input voltage range
|
18 V DC ... 32 V DC
|
Electric strength, max.
|
35 V DC (60 s)
|
Typical current consumption
|
5.5 A (24 V DC)
|
Mains buffering
|
typ. 17 ms (24 V DC)
|
Switch-on time
|
< 1 s
|
Typical response time
|
300 ms (from SLEEP MODE)
|
Inrush current limitation typical
|
1 A
|
Inrush current integral (I2t)
|
< 0.02 A2s
|
Input fuse
|
15 A (slow-blow, internal)
|
Insulation electric strength
Insulation voltage input/output
|
4 kV DC (type test)
|
|
2 kV DC (routine test)
|
Type test (IEC/EN 60950-1) A
|
2 kV DC
|
Type test (IEC/EN 60950-1) B
|
4 kV DC
|
Type test (IEC/EN 60950-1) C
|
0.5 kV DC
|
Type test (IEC/EN 60950-1) D
|
0.5 kV DC
|
Production test A
|
2 kV DC
|
Production test B
|
2 kV DC
|
Production test C
|
0.5 kV DC
|
Production test D
|
0.5 kV DC
|
Input connection data
Connection method
|
Push-in connection
|
Stripping length
|
10 mm
|
Conductor cross section solid
|
0.2 mm² ... 6 mm²
|
Conductor cross section flexible
|
0.2 mm² ... 6 mm²
|
Flexible conductor cross section (ferrule with plastic sleeve)
|
0.2 mm² ... 4 mm²
|
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve)
|
0.2 mm² ... 4 mm²
|
Conductor cross section AWG
|
24 ... 10
|
Output data
Nominal output voltage (UN)
|
12 V DC
|
Setting range of the output voltage (USet)
|
12 V DC ... 15 V DC (> 12 V DC, constant capacity)
|
Nominal output current (IN)
|
8 A
|
Static Boost (IStat.Boost)
|
10 A
|
Dynamic Boost (IDyn.Boost)
|
16 A (5 s)
|
Selective Fuse Breaking (ISFB)
|
48 A (15 ms)
|
Magnetic circuit breaker tripping
|
A1 ... A6 / B2 ... B6 / Z1 ... Z6
|
System deviation, static
|
< 1 % (change in load, static 10 % ... 90 %)
|
System deviation, dynamic
|
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
|
System deviation, input voltage change
|
< 0.1 % (change in input voltage ±10 %)
|
Short-circuit-proof
|
yes
|
No-load proof
|
yes
|
Residual ripple
|
< 13 mVPP
|
Connection in parallel
|
yes, for redundancy and increased capacity
|
Connection in series
|
yes
|
Feedback voltage resistance
|
≤ 25 V DC
|
Protection against overvoltage at the output (OVP)
|
≤ 18 V DC
|
Rise time
|
< 1 s (UOUT (10 % ... 90 %))
|
Output connection data
Connection method
|
Push-in connection
|
Stripping length
|
10 mm
|
Conductor cross section solid
|
0.2 mm² ... 6 mm²
|
Conductor cross section flexible
|
0.2 mm² ... 6 mm²
|
Flexible conductor cross section (ferrule with plastic sleeve)
|
0.2 mm² ... 4 mm²
|
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve)
|
0.2 mm² ... 4 mm²
|
Conductor cross section AWG
|
24 ... 10
|
LED signaling
Types of signaling
|
LED
|
|
Floating signal contact
|
|
Active signal output Out1 (digital, configurable)
|
|
Active signal output Out2 (analog, configurable)
|
|
Remote contact
|
|
Signal ground SGnd
|
POut
|
> 100 % (LED lights up yellow, output power > 96 W)
|
|
> 75 % (LED lights up green, output power > 72 W)
|
|
> 50 % (LED lights up green, output power > 48 W)
|
UOut
|
> 0.9 x USet (LED lights up green)
|
|
< 0.9 x USet (LED flashes green)
|
UIn
|
> 0.8 x UInNom (LED off)
|
|
< 0.8 x UInNom (LED lights up yellow)
|
Signal contacts – signal output Out 1 (configurable)
Connection labeling
|
3.5 +
|
Digital
|
0 V DC
|
|
24 V DC
|
|
20 mA
|
Default
|
UIN input voltage OK
|
Signal option
|
Output voltage
|
|
Output current
|
|
Output power
|
|
Operating hours
|
|
Early warning of high temperatures
|
|
OVP voltage limitation active
|
Signal contacts – signal output Out 2 (configurable)
Connection labeling
|
3.6 +
|
Digital
|
0 V DC
|
|
24 V DC
|
|
20 mA
|
Default
|
Output power
|
Signal option
|
Output voltage
|
|
Output current
|
|
Operating hours
|
|
Early warning of high temperatures
|
|
OVP voltage limitation active
|
Analog
|
4 mA ... 20 mA ±5 % (Load ≤400 Ω)
|
Signal option
|
Output voltage
|
|
Output current
|
|
Output power
|
Signal contacts – signal output relay 13/14 (configurable)
Connection labeling
|
3.1, 3.2
|
Switch contact
|
floating
|
Maximum contact load
|
24 V DC
|
|
1 A
|
|
30 V AC
|
|
0.5 A
|
Default
|
Output voltage
|
Signal option
|
Output current
|
|
Output power
|
|
Operating hours
|
|
Early warning of high temperatures
|
|
OVP voltage limitation active
|
|
UIN input voltage OK
|
Signal contacts – remote signal input (configurable)
Connection labeling
|
3.3 +
|
Function
|
Output power ON/OFF (remote)
|
Default
|
Output power ON (>40 kΩ/24 V DC/open bridge between REM and SGnd)
|
Signal contacts – signal ground SGnd
Connection labeling
|
3.4 +
|
Function
|
Signal ground
|
Reference potential
|
to OUT1, OUT2, REM
|
Signal connection data
Connection method
|
Push-in connection
|
Conductor cross section solid
|
0.2 mm² ... 1 mm²
|
Conductor cross section flexible
|
0.2 mm² ... 1.5 mm²
|
Flexible conductor cross section (ferrule with plastic sleeve)
|
0.2 mm² ... 0.75 mm²
|
Flexible conductor cross section flexible (ferrule, w/o plastic sleeve)
|
0.2 mm² ... 1.5 mm²
|
Conductor cross section AWG
|
24 ... 16
|
Stripping length
|
8 mm
|
Reliability
MTBF (IEC 61709, SN 29500)
|
> (25 °C)
|
|
> 970000 h (40 °C)
|
|
> (60 °C)
|
Life expectancy (electrolytic capacitors)
Output current
|
4 A
|
Temperature
|
40 °C
|
Time
|
452000 h
|
Voltage
|
12 V DC
|
Output current
|
8 A
|
Temperature
|
40 °C
|
Time
|
211000 h
|
Voltage
|
12 V DC
|
Output current
|
8 A
|
Temperature
|
30 °C
|
Time
|
422000 h
|
Voltage
|
12 V DC
|
Switching frequency
Auxiliary converter stage
|
190 kHz ... 220 kHz (Auxiliary converter stage)
|
Main converter stage
|
50 kHz ... 350 kHz (Main converter stage)
|
General data
Degree of protection
|
IP20
|
Protection class
|
Special with SELV input and output
|
Inflammability class in acc. with UL 94 (housing / terminal blocks)
|
V0
|
Side element version
|
Aluminum
|
Hood version
|
Stainless steel X6Cr17
|
Width
|
36 mm
|
Height
|
130 mm
|
Depth
|
125 mm
|
Width with alternative assembly
|
122 mm
|
Height with alternative assembly
|
130 mm
|
Depth with alternative assembly
|
39 mm
|
Weight
|
0.6 kg
|
Efficiency
|
typ. 91 % (24 V DC)
|
Power dissipation
Maximum power dissipation in no-load condition
|
< 2 W
|
Power dissipation SLEEP MODE
|
< 1 W
|
Power loss nominal load max.
|
< 9 W
|
Ambient conditions
Ambient temperature (operation)
|
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
|
Ambient temperature (start-up type tested)
|
-40 °C
|
Ambient temperature (storage/transport)
|
-40 °C ... 85 °C
|
Max. permissible relative humidity (operation)
|
≤ 95 % (at 25 °C, non-condensing)
|
Maximum altitude
|
≤ 5000 m (> 2000 m, observe derating)
|
Vibration (operation)
|
5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C)
|
Shock
|
18 ms, 30g, in each space direction (according to IEC 60068-2-27)
|
Degree of pollution
|
2
|
Climatic class
|
3K3 (EN 60721)
|
Standards
EMC requirements for noise immunity
|
EN 61000-6-1
|
|
EN 61000-6-2
|
EMC requirements for noise emission
|
EN 61000-6-3
|
|
EN 61000-6-4
|
EMC requirements, power plant
|
IEC 61850-3
|
|
EN 61000-6-5
|
Standard designation
|
Electrical safety (of control and regulation devices)
|
Standards/regulations
|
IEC 61010-1
|
Standard designation
|
Protective extra-low voltage
|
Standards/regulations
|
EN 61010-1 (SELV)
|
|
IEC 61010-2-201 (PELV)
|
Standard designation
|
Explosive atmospheres
|
Standards/regulations
|
IEC 60079-0
|
|
IEC 60079-7
|
|
IEC 60079-11
|
|
IEC 60079-15
|
Standard designation
|
Mains variation/undervoltage
|
Standards/regulations
|
EN 61000-4-29
|
Overvoltage category EN 61010-1
|
II
|
Overvoltage category EN 62477-1
|
III
|
Conformance/approvals
Designation
|
UL
|
Identification
|
UL Listed UL 61010-1
|
Designation
|
UL
|
Identification
|
UL Listed UL 61010-2-201
|
Designation
|
UL
|
Identification
|
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
|
Designation
|
CSA
|
Identification
|
CAN/CSA-C22.2 No. 61010-1-12
|
Designation
|
CSA
|
Identification
|
CAN/CSA-IEC 61010-2-201:14
|
Designation
|
SIQ
|
Identification
|
Type tested (type approved)
|
Designation
|
SIQ
|
Identification
|
CB scheme (IEC 61010-1, IEC 61010-2-201)
|
Designation
|
Shipbuilding
|
Identification
|
DNV GL
|
Designation
|
Shipbuilding
|
Identification
|
ABS
|
EMC data
Electromagnetic compatibility
|
Conformance with EMC Directive 2014/30/EU
|
Low Voltage Directive
|
Conformance with Low Voltage Directive 2014/35/EC
|
Conducted noise emission
|
EN 55016
|
|
EN 61000-6-3 (Class B)
|
Noise emission
|
EN 55016
|
|
EN 61000-6-3 (Class B)
|
DNV GL conducted interference
|
Class B
|
Additional text
|
Bridge and deck area
|
DNV GL noise radiation
|
Class B
|
Additional text
|
Bridge and deck area
|
Electrostatic discharge
|
EN 61000-4-2
|
Contact discharge
|
8 kV (Test Level 4)
|
Discharge in air
|
15 kV (Test Level 4)
|
Electromagnetic HF field
|
EN 61000-4-3
|
Frequency range
|
80 MHz ... 1 GHz
|
Test field strength
|
20 V/m (Test Level 3)
|
Frequency range
|
1 GHz ... 6 GHz
|
Test field strength
|
10 V/m (Test Level 3)
|
Frequency range
|
1 GHz ... 6 GHz
|
Test field strength
|
10 V/m (Test Level 3)
|
Comments
|
Criterion A
|
Fast transients (burst)
|
EN 61000-4-4
|
Input
|
2 kV (Test Level 3 - asymmetrical)
|
Output
|
2 kV (Test Level 3 - asymmetrical)
|
Signal
|
2 kV (Test Level 4 - asymmetrical)
|
Comments
|
Criterion A
|
Surge voltage load (surge)
|
EN 61000-4-5
|
Input
|
1 kV (Test Level 3 - symmetrical)
|
|
2 kV (Test Level 3 - asymmetrical)
|
Output
|
1 kV (Test Level 3 - symmetrical)
|
|
2 kV (Test Level 3 - asymmetrical)
|
Signal
|
2 kV (Test Level 3 - asymmetrical)
|
Comments
|
Criterion A
|
Conducted interference
|
EN 61000-4-6
|
I/O/S
|
asymmetrical
|
Frequency range
|
0.15 MHz ... 80 MHz
|
Voltage
|
10 V (Test Level 3)
|
Comments
|
Criterion A
|
Power frequency magnetic field
|
EN 61000-4-8
|
Frequency
|
16.7 Hz
|
|
50 Hz
|
|
60 Hz
|
Test field strength
|
100 A/m
|
Additional text
|
60 s
|
Comments
|
Criterion A
|
Frequency
|
50 Hz
|
|
60 Hz
|
Frequency range
|
50 Hz ... 60 Hz
|
Test field strength
|
1 kA/m
|
Additional text
|
3 s
|
Comments
|
Criterion A
|
Frequency
|
0 Hz
|
Test field strength
|
300 A/m
|
Additional text
|
DC, 60 s
|
Comments
|
Criterion A
|
Voltage dips
|
EN 61000-4-29
|
Voltage
|
24 V DC
|
Voltage dip
|
70 %
|
Additional text
|
Test Level 2
|
Comments
|
Criterion A
|
Voltage dip
|
40 %
|
Additional text
|
Test Level 2
|
Comments
|
Criterion A
|
Voltage dip
|
0 %
|
Additional text
|
Test Level 2
|
Comments
|
Criterion B
|
Pulse-shape magnetic field
|
EN 61000-4-9
|
Test field strength
|
1000 A/m
|
Comments
|
Criterion A
|
Damped oscillating magnetic field
|
EN 61000-4-10
|
Test field strength
|
100 A/m
|
Test level 1
|
100 kHz
|
Test field strength
|
100 A/m
|
Test level 2
|
1 MHz
|
Comments
|
Criterion A
|
Asymmetrical conducted disturbance variables
|
EN 61000-4-16
|
Test level 1
|
15 Hz 150 Hz (Test Level 3)
|
Voltage
|
10 V 1 V
|
Test level 2
|
150 Hz 1.5 kHz (Test Level 3)
|
Voltage
|
1 V
|
Test level 3
|
1.5 kHz 15 kHz (Test Level 3)
|
Voltage
|
1 V 10 V
|
Test level 4
|
15 kHz 150 kHz (Test Level 3)
|
Voltage
|
10 V
|
Test level 5
|
16.7 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3)
|
Voltage
|
10 V (Permanent)
|
Test level 6
|
0 Hz 16.7 Hz 50 Hz 60 Hz (Test Level 3)
|
Voltage
|
100 V (1 s)
|
Comments
|
Criterion A
|
Alternating component of DC voltage
|
EN 61000-4-17
|
Attenuated oscillating wave
|
EN 61000-4-18
|
Input, output (test level 1)
|
100 kHz 1 MHz (Test Level 3 - symmetrical)
|
Voltage
|
1 kV
|
Input, output (test level 2)
|
100 kHz 1 MHz (Test Level 2 - asymmetrical)
|
Voltage
|
1 kV
|
Input, output (test level 3)
|
10 MHz (Test Level 2 - asymmetrical)
|
Voltage
|
0.5 kV
|
Signals (test level 1)
|
100 kHz 1 MHz (Test Level 2 - symmetrical)
|
Voltage
|
0.5 kV
|
Signals (test level 2)
|
100 kHz 1 MHz (Test Level 2 - asymmetrical)
|
Voltage
|
1 kV
|
Comments
|
Criterion A
|
Criterion A
|
Normal operating behavior within the specified limits.
|
Criterion B
|
Temporary impairment to operational behavior that is corrected by the device itself.
|
Criterion C
|
Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
|
ECLASS
ECLASS 10.0.1 |
27210901
|
ECLASS 11.0 |
27210901
|
ECLASS 9.0 |
27210901
|
ETIM
ETIM 6.0 |
EC002046
|
ETIM 7.0 |
EC002046
|
UNSPSC
UNSPSC 18.0 |
39121041
|
UNSPSC 19.0 |
39121041
|
UNSPSC 20.0 |
39121041
|
UNSPSC 21.0 |
39121041
|
|
File description
|
File type
|
Download link
|
|
|
|
|
|
|
|
|