Image is illustrative
|
Electronic Circuit Breaker CBM E8 24DC/0.5-10A NO-R, 1pcs/pck, Phoenix Code:
2905744
Cena
Manufacturer
:
Availability:
21 days
|
Weight:
0.319 kg/pc
|
Volume:
0.0012 m3/pc
|
|
|
|
|
Electronic Circuit Breaker CBM E8 24DC/0.5-10A NO-R, 1pcs/pck, PhoenixDimensions
Height
|
130 mm
|
Width
|
41 mm
|
Depth
|
121 mm (incl. DIN rail 7.5 mm)
|
Ambient conditions
Ambient temperature (operation)
|
-25 °C ... 70 °C (Startup at -40 C type-tested)
|
|
-25 °C ... 65 °C (for UL 2367)
|
Ambient temperature (storage/transport)
|
-40 °C ... 80 °C
|
Humidity test
|
240 h, 95 % RH, 40 °C
|
Altitude
|
≤ 6000 m (amsl (above mean sea level))
|
Shock (operation)
|
30g (IEC 60068-2-27, Test Ea)
|
Vibration (operation)
|
5 Hz ... 24.9 Hz (Amplitude ±1.6 mm; in accordance with IEC 60068-2-6, Test Fc)
|
|
24.9 Hz … 150 Hz (Acceleration 4g; in accordance with IEC 60068-2-6, Test Fc with additional resonance frequency testing in accordance with DNV GL)
|
Degree of protection
|
IP20
|
General
Flammability rating according to UL 94
|
V-0
|
Mounting type
|
DIN rail: 35 mm
|
Color
|
light grey RAL 7035
|
Number of positions
|
1
|
Protection class
|
III
|
Degree of pollution
|
2
|
Type
|
DIN rail module, one-piece
|
Electrical data
Fuse type
|
electronic
|
Rated surge voltage
|
0.5 kV
|
Operating voltage
|
18 V DC ... 30 V DC
|
Rated voltage
|
24 V DC
|
Rated current IN
|
max. 80 A DC (for double supply IN+ with at least 2 x 6 mm²)
|
|
max. 70 A DC (for UL 2367)
|
|
0.5 / 1 / 2 / 4 / 6 / 10 A DC (adjustable per output channel)
|
Rated current (pre-adjusted)
|
0.5 A
|
Measuring tolerance I
|
typ. 40 % (0.5 A ... 1 A)
|
|
typ. 10 % (2 - 10 A)
|
Feedback resistance
|
max. 35 V DC
|
Fail-safe element
|
15 A DC (per output channel)
|
Active current limitation
|
typ. 2.0 x IN (0.5 - 1 A)
|
|
typ. 1.5 x IN (2 - 10 A)
|
Efficiency
|
> 99 %
|
Closed circuit current I0
|
typ. 50 mA
|
Power dissipation
|
1.2 W (No-load operation)
|
|
17.2 W (Nominal operation)
|
Module initialization time
|
3.3 s
|
Waiting time after switch off of a channel
|
10 s (at overload / short circuit)
|
Temperature derating
|
40 A DC (at 70°C (65°C for UL 2367))
|
|
50 A DC (at 60 °C)
|
|
60 A DC (at 50 °C)
|
|
70 A DC (at 40 °C)
|
|
80 A DC (at 40 °C)
|
|
70 A DC (at 40°C for UL 2367)
|
Tripping method
|
E (electronic)
|
Required backup fuse
|
Only required if Imax of the power supply > the short-circuit switching capacity. Integrated failsafe element.
|
Short-circuit switching capacity
|
300 A
|
Dielectric strength
|
max. 30 V DC (Load circuit)
|
MTBF (IEC 61709, SN 29500)
|
1304293 h (at 25 °C)
|
|
858501 h (at 40 °C)
|
|
440048 h (at 60 °C)
|
Shutdown time load circuit
|
0.02 s (> 1.3 x IN)
|
|
30 s (1.1 ... 1.3 x IN)
|
Undervoltage switch-off load circuit
|
≤ 17.8 V DC (active)
|
|
≥ 19 V DC (inactive)
|
Overvoltage switch-off shutdown load circuit
|
≥ 30.5 V DC (active)
|
|
≤ 29.5 V DC (inactive)
|
Max. capacitive load load circuit
|
75000 µF
|
Output voltage status output
|
24 V DC
|
Output current status output
|
max. 20 mA (when I > 80% at at least one channel)
|
Input voltage reset input
|
7 V DC ... 30 V DC (Reset with falling edge)
|
Current consumption reset input
|
typ. 0.4 mA (at 24 V DC)
|
Pulse length reset input
|
≥ 50 ms (High signal)
|
|
≥ 50 ms (Low signal)
|
Voltage reset input
|
< 5 V DC (Low signal)
|
|
> 8 V DC (High signal)
|
Remote indication contact
Connection name
|
Remote indication circuit
|
Switching function
|
N/O contact
|
Stripping length
|
10 mm
|
Conductor cross section solid
|
0.2 mm² ... 2.5 mm²
|
Conductor cross section AWG
|
24 ... 12
|
Conductor cross section, flexible, with ferrule, with plastic sleeve
|
1.5 mm² ... 0.25 mm²
|
Conductor cross section flexible, with ferrule without plastic sleeve
|
0.25 mm² ... 2.5 mm²
|
DC operating voltage
|
0 V DC ... 30 V DC
|
DC operating current
|
1 mA DC ... 100 mA DC
|
Signaling
Channel LED off
|
off (Channel switched off)
|
Channel LED green
|
lit (Channel switched on)
|
|
flashing (Channel switched on, programming mode active)
|
Channel LED yellow
|
lit (Channel switched on, channel load > 80% )
|
Channel LED yellow-green
|
flashing (Channel switched on, nominal current assistant active)
|
Channel LED red
|
lit (Channel switched off, over- or undervoltage active)
|
|
ON temporarily (Channel switched off, 10 s cool-down phase, overload or short-circuit release)
|
|
flashing (Channel switched off, ready to be switched back on, overload or short-circuit release)
|
Channel LED red-yellow
|
flashing (Channel switched on, overload mode, capacity approximately 110 ... 130% , shutdown after 30 s)
|
Channel LED red-green
|
flashing (Channel switched off, programming mode active, current adjustment after overload or short-circuit release)
|
DC OK LED off
|
off (No supply voltage)
|
DC OK LED green
|
lit (Operating voltage in nominal range 18 ... 30 V)
|
DC OK LED yellow
|
lit (Undervoltage active, voltage ≤ 17.8 V, active channels switched off and channel LEDs are lit red)
|
|
flashing (Undervoltage switch-off inactive, device was in undervoltage switch-off)
|
DC OK LED red
|
lit (Overvoltage switch-off active, voltage ≥ 30.5 V, channels switched off and channel LEDs are lit red)
|
|
flashing (Overvoltage switch-off inactive, device was in overvoltage shutdown)
|
Connection data
Connection name
|
Main circuit IN+
|
Connection method
|
Push-in connection
|
Stripping length
|
18 mm
|
Conductor cross section solid
|
0.75 mm² ... 16 mm²
|
Conductor cross section AWG
|
20 ... 4
|
Conductor cross section, flexible, with ferrule, with plastic sleeve
|
0.75 mm² ... 10 mm²
|
Conductor cross section flexible, with ferrule without plastic sleeve
|
0.75 mm² ... 16 mm²
|
Connection name
|
Main circuit IN-
|
Connection method
|
Push-in connection
|
Stripping length
|
10 mm
|
Conductor cross section solid
|
0.2 mm² ... 2.5 mm²
|
Conductor cross section AWG
|
24 ... 12
|
Conductor cross section, flexible, with ferrule, with plastic sleeve
|
0.25 mm² ... 1.5 mm²
|
Conductor cross section flexible, with ferrule without plastic sleeve
|
0.25 mm² ... 2.5 mm²
|
Connection name
|
Main circuit OUT
|
Connection method
|
Push-in connection
|
Stripping length
|
10 mm
|
Conductor cross section solid
|
0.2 mm² ... 2.5 mm²
|
Conductor cross section AWG
|
24 ... 12
|
Conductor cross section, flexible, with ferrule, with plastic sleeve
|
0.25 mm² ... 1.5 mm²
|
Conductor cross section flexible, with ferrule without plastic sleeve
|
0.25 mm² ... 2.5 mm²
|
Standards and Regulations
Standards/specifications
|
EN 61000-6-2 EMC – Immunity for industrial areas
|
|
EN 61000-6-3 EMC – Emission for residential, business and commercial properties and small operations
|
|
EN 60068-2-6 Environmental influences – Vibrations (sinusoidal)
|
|
EN 60068-2-1 Environmental influences – Part 2-1: Tests – Test A: Cold
|
|
EN 60068-2-2 Environmental influences – Part 2-2: Tests – Test B: Dry heat
|
|
EN 60068-2-78 Environmental influences – Moisture and heat, constant
|
Conformance/approvals
Designation
|
UL approval
|
Identification
|
UL/C-UL Listed UL 508
|
|
UL Recognized UL 2367
|
|
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
|
Designation
|
Shipbuilding approval
|
Identification
|
DNV GL
|
Temperature
|
D
|
Humidity
|
B
|
Vibration
|
B
|
EMC
|
A
|
Enclosure
|
Required protection according to the Rules shall be provided upon installation on board
|
Environmental Product Compliance
REACh SVHC
|
Lead 7439-92-1
|
China RoHS
|
Environmentally friendly use period: unlimited = EFUP-e
|
|
No hazardous substances above threshold values
|
ECLASS
ECLASS 10.0.1 |
27140401
|
ECLASS 11.0 |
27140401
|
ECLASS 4.0 |
27141100
|
ECLASS 4.1 |
27141100
|
ECLASS 5.0 |
27141100
|
ECLASS 5.1 |
27141100
|
ECLASS 6.0 |
27141100
|
ECLASS 7.0 |
27141116
|
ECLASS 9.0 |
27141116
|
ETIMUNSPSC
UNSPSC 13.2 |
39121410
|
UNSPSC 18.0 |
39121410
|
UNSPSC 19.0 |
39121410
|
UNSPSC 20.0 |
39121410
|
UNSPSC 21.0 |
39121410
|
|
File description
|
File type
|
Download link
|
|
|
|
|
|
|
|