Image is illustrative
|
Power Supply Unit QUINT-PS/1AC/24DC/40, Phoenix Code:
2866789
Cena
Manufacturer
:
Availability:
21 days
|
Weight:
3.9887 kg/pc
|
Volume:
0.0031 m3/pc
|
|
|
|
|
Power Supply Unit QUINT-PS/1AC/24DC/40, PhoenixDimensions
Width
|
180 mm
|
Height
|
130 mm
|
Depth
|
125 mm
|
Width with alternative assembly
|
122 mm
|
Height with alternative assembly
|
130 mm
|
Depth with alternative assembly
|
183 mm
|
Installation distance right/left
|
5 mm / 5 mm
|
Installation distance top/bottom
|
50 mm / 50 mm
|
Ambient conditions
Degree of protection
|
IP20
|
Ambient temperature (operation)
|
-25 °C ... 70 °C (> 60 °C Derating: 2.5 %/K)
|
Ambient temperature (start-up type tested)
|
-40 °C
|
Ambient temperature (storage/transport)
|
-40 °C ... 85 °C
|
Max. permissible relative humidity (operation)
|
≤ 95 % (at 25 °C, non-condensing)
|
Climatic class
|
3K3 (in acc. with EN 60721)
|
Degree of pollution
|
2
|
Installation height
|
4000 m
|
Input data
Nominal input voltage range
|
100 V AC ... 240 V AC
|
|
120 V DC ... 300 V DC (UL 508: ≤ 250 V DC)
|
Input voltage range
|
85 V AC ... 264 V AC
|
|
90 V DC ... 300 V DC (UL 508: ≤ 250 V DC)
|
Dielectric strength maximum
|
300 V AC
|
AC frequency range
|
45 Hz ... 65 Hz
|
Frequency range DC
|
0 Hz
|
Discharge current to PE
|
< 3.5 mA
|
Current consumption
|
8.8 A (120 V AC)
|
|
4.6 A (230 V AC)
|
|
9.5 A (110 V DC)
|
|
4.7 A (220 V DC)
|
Nominal power consumption
|
1157 VA
|
Inrush current
|
< 15 A (typical)
|
Mains buffering time
|
> 35 ms (120 V AC)
|
|
> 35 ms (230 V AC)
|
Input fuse
|
20 A (slow-blow, internal)
|
Recommended breaker for input protection
|
16 A ... 20 A (AC: Characteristics B, C, D, K)
|
Power factor (cos phi)
|
0.88
|
Type of protection
|
Transient surge protection
|
Protective circuit/component
|
Varistor, gas-filled surge arrester
|
Output data
Nominal output voltage
|
24 V DC ±1 %
|
Setting range of the output voltage (USet)
|
18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
|
Nominal output current (IN)
|
40 A (-25 °C ... 60 °C, UOUT = 24 V DC)
|
POWER BOOST (IBoost)
|
45 A (-25 °C ... 40 °C permanent, UOUT = 24 V DC )
|
Selective Fuse Breaking (ISFB)
|
215 A (12 ms)
|
Derating
|
60 °C ... 70 °C (2.5%/K)
|
Connection in parallel
|
yes, for redundancy and increased capacity
|
Connection in series
|
yes
|
Feedback voltage resistance
|
max. 35 V DC
|
Protection against overvoltage at the output (OVP)
|
< 35 V DC
|
Residual ripple
|
< 30 mVPP (with nominal values)
|
Output power
|
960 W
|
Typical response time
|
< 0.7 s
|
Maximum power dissipation in no-load condition
|
14 W
|
Power loss nominal load max.
|
80 W
|
General
Net weight
|
3.3 kg
|
Efficiency
|
> 92 % (for 230 V AC and nominal values)
|
MTBF (IEC 61709, SN 29500)
|
> 900000 h (25 °C)
|
|
> 530000 h (40 °C)
|
|
> 240000 h (60 °C)
|
Insulation voltage input/output
|
4 kV AC (type test)
|
|
2 kV AC (routine test)
|
Insulation voltage input / PE
|
3.5 kV AC (type test)
|
|
2 kV AC (routine test)
|
Insulation voltage output / PE
|
500 V DC (routine test)
|
Degree of protection
|
IP20
|
Protection class
|
I
|
Mounting position
|
horizontal DIN rail NS 35, EN 60715
|
Assembly instructions
|
alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
|
Connection data, input
Connection method
|
Screw connection
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
6 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
4 mm²
|
Conductor cross section AWG min.
|
14
|
Conductor cross section AWG max.
|
10
|
Stripping length
|
7 mm
|
Screw thread
|
M3
|
Connection data, output
Connection method
|
Screw connection
|
Conductor cross section solid min.
|
0.5 mm²
|
Conductor cross section solid max.
|
16 mm²
|
Conductor cross section flexible min.
|
0.5 mm²
|
Conductor cross section flexible max.
|
16 mm²
|
Conductor cross section AWG min.
|
8
|
Conductor cross section AWG max.
|
6
|
Stripping length
|
10 mm
|
Screw thread
|
M4
|
Connection data for signaling
Connection method
|
Screw connection
|
Conductor cross section solid min.
|
0.2 mm²
|
Conductor cross section solid max.
|
6 mm²
|
Conductor cross section flexible min.
|
0.2 mm²
|
Conductor cross section flexible max.
|
4 mm²
|
Conductor cross section AWG min.
|
24
|
Conductor cross section AWG max.
|
10
|
Screw thread
|
M3
|
Standards
EMC requirements for noise immunity
|
EN 61000-6-1
|
|
EN 61000-6-2
|
EMC requirements for noise emission
|
EN 61000-6-3
|
|
EN 61000-6-4
|
Standard - Electrical safety
|
IEC 61010-2-201 (SELV)
|
Standard - safety for equipment for measurement, control, and laboratory use
|
IEC 61010-1
|
Standard – Safety extra-low voltage
|
IEC 61010-1 (SELV)
|
|
IEC 61010-2-201 (PELV)
|
Standard - Safe isolation
|
IEC 61010-2-201
|
Standard – Protection against shock currents, basic requirements for protective separation in electrical equipment
|
EN 50178
|
Standard – Limitation of mains harmonic currents
|
EN 61000-3-2
|
Standard - Equipment safety
|
BG (design tested)
|
Rail applications
|
EN 50121-4
|
|
EN 50121-3-2
|
Overvoltage category EN 62477-1
|
III
|
Conformance/approvals
UL approvals
|
UL Listed UL 508
|
|
UL/C-UL Recognized UL 60950-1
|
|
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
|
CSA
|
CSA-C22.2 No. 107.1-01
|
Shipbuilding approval
|
DNV GL (EMC A), ABS, LR, RINA, NK, BV
|
EMC data
Electromagnetic compatibility
|
Conformance with EMC Directive 2014/30/EU
|
Low Voltage Directive
|
Conformance with Low Voltage Directive 2014/35/EC
|
Electrostatic discharge
|
EN 61000-4-2
|
Contact discharge
|
8 kV (Test Level 4)
|
Discharge in air
|
15 kV (Test Level 4)
|
Electromagnetic HF field
|
EN 61000-4-3
|
Frequency range
|
80 MHz ... 1 GHz
|
Test field strength
|
20 V/m (Test Level 3)
|
Frequency range
|
1 GHz ... 2 GHz
|
Test field strength
|
10 V/m (Test Level 3)
|
Frequency range
|
2 GHz ... 3 GHz
|
Test field strength
|
10 V/m (Test Level 3)
|
Comments
|
Criterion A
|
Fast transients (burst)
|
EN 61000-4-4
|
Input
|
4 kV (Test Level 4 - asymmetrical)
|
Output
|
2 kV (Test Level 3 - asymmetrical)
|
Signal
|
2 kV (Test Level 4 - asymmetrical)
|
Comments
|
Criterion A
|
Surge voltage load (surge)
|
EN 61000-4-5
|
Input
|
2 kV (Test Level 3 - symmetrical)
|
|
4 kV (Test Level 4 - asymmetrical)
|
Output
|
1 kV (Test Level 2 - symmetrical)
|
|
2 kV (Test Level 3 - asymmetrical)
|
Signal
|
1 kV (Test Level 2 - asymmetrical)
|
Comments
|
Criterion A
|
Conducted interference
|
EN 61000-4-6
|
I/O/S
|
asymmetrical
|
Frequency range
|
0.15 MHz ... 80 MHz
|
Voltage
|
10 V (Test Level 3)
|
Comments
|
Criterion A
|
Wireless telephone simulation
|
ENV 50204
|
Frequency
|
900 MHz
|
|
1800 MHz
|
Field intensity
|
20 V/m
|
Criterion A
|
Normal operating behavior within the specified limits.
|
Criterion B
|
Temporary impairment to operational behavior that is corrected by the device itself.
|
Environmental Product Compliance
REACh SVHC
|
Lead 7439-92-1
|
China RoHS
|
Environmentally Friendly Use Period = 25;
|
|
For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
|
ECLASS
ECLASS 10.0.1 |
27040701
|
ECLASS 11.0 |
27040701
|
ECLASS 4.0 |
27040700
|
ECLASS 4.1 |
27040700
|
ECLASS 5.0 |
27049000
|
ECLASS 5.1 |
27049000
|
ECLASS 6.0 |
27049000
|
ECLASS 7.0 |
27049002
|
ECLASS 9.0 |
27040701
|
ETIM
ETIM 2.0 |
EC001039
|
ETIM 3.0 |
EC001039
|
ETIM 4.0 |
EC000599
|
ETIM 6.0 |
EC002540
|
ETIM 7.0 |
EC002540
|
UNSPSC
UNSPSC 6.01 |
30211502
|
UNSPSC 7.0901 |
39121004
|
UNSPSC 11 |
39121004
|
UNSPSC 12.01 |
39121004
|
UNSPSC 13.2 |
39121004
|
UNSPSC 18.0 |
39121004
|
UNSPSC 19.0 |
39121004
|
UNSPSC 20.0 |
39121004
|
UNSPSC 21.0 |
39121004
|
|
File description
|
File type
|
Download link
|
|
|
|
|
|
|
|
|
|