Image is illustrative
|
HART Multiplexer Slave KFD0-HMS-16 Code:
231291
Cena (indicative)
Manufacturer
:
|
Availability:
21 days
|
Weight:
0.1234 kg/pc
|
|
|
|
|
|
HART Multiplexer Slave KFD0-HMS-16, Pepperl+FuchsHART Multiplexer Slave KFD0-HMS-16
- 16-channel
- No external power required
- HART field device input (revision 5 to 7)
- Used with HART Multiplexer Master KFD2-HMM-16
- Up to SIL3 acc. to IEC 61508
Datasheet excerpt: Technical data of KFD0-HMS-16
| Functional safety related parameters |
| Safety Integrity Level (SIL) | SIL 3 |
| Supply |
| Connection | via 14-channel flat cable form master KFD2-HMM-16 |
| HART signal channels (non-intrinsically safe) |
| Conformity | HART field device input (revision 5 to 7) |
| Connection | 26-pin flat cable for analog connections 14-pin flat cable for master-slave connection between KFD2-HMM-16 and KFD0-HMS-16 |
| Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) |
| Terminating resistor | external 230 ... 500 Ω standard (up to 1000 Ω possible) |
| Output voltage | ≥ 400 mV ss (with the terminator resistance specified above) |
| Output resistance | 100 Ω or smaller, capacitive coupling |
| Input impedance | according to HART specification |
| Input voltage range | 0.08 ... 4 V ss ; typ. ± 5.2 V as local reference |
| Indicators/settings |
| Labeling | space for labeling at the front |
| Directive conformity |
| Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
| Conformity |
| Degree of protection | IEC 60529:2001 |
| Ambient conditions |
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
| Mechanical specifications |
| Degree of protection | IP20 |
| Mass | approx. 100 g |
| Dimensions | 20 x 93 x 115 mm (0.8 x 3.7 x 4.5 inch) , housing type B1 |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
| Data for application in connection with hazardous areas |
| Certificate | PF 07 CERT 1143 X |
| Marking | II 3G Ex nA IIC T4 Gc |
| Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
|
|
|
|
|