Cable Tie GT-UV, 300/3.6 SW, 18.2kg, Polyamide 6.6, -40..85°C, UV resistant, UL94 V2, 100pcs/pck, UL E75050, Lloyd’s, GL 59425-08HH, Mil-23190D, black
Cable Tie GT-UV, 300/3.6 SW, 18.2kg, Polyamide 6.6, -40..85°C, UV resistant, UL94 V2, 100pcs/pck, UL E75050, Lloyd’s, GL 59425-08HH, Mil-23190D, black



Frequency Converter w. Trip Values KFD2-UFC-Ex1.D, 1-ch., input NAMUR/dry contacts w. 1mHz..5kHz, output 0/4..20mA/relay, transistor, start-up override, LFD, SIL2, 24VDC PR, Pepperl+Fuchs
Image is illustrative
Frequency Converter w. Trip Values KFD2-UFC-Ex1.D, 1-ch., input NAMUR/dry contacts w. 1mHz..5kHz, output 0/4..20mA/relay, transistor, start-up override, LFD, SIL2, 24VDC PR, Pepperl+Fuchs
Code: 231194
Cena (indicative)
413,90 €  /pc
Manufacturer :
Availability:
21 days
Weight:
0.321 kg/pc
Volume:
0.0006 m3/pc
Quantity:
Plus sign Minus sign
 

 

Frequency Converter w. Trip Values KFD2-UFC-Ex1.D, 1-ch., input NAMUR/dry contacts w. 1mHz..5kHz, output 0/4..20mA/relay ?transistor, start-up override, LFD, SIL2, 24VDC PR, Pepperl+Fuchs

Frequency Converter with Trip Values KFD2-UFC-Ex1.D
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Input for NAMUR sensors or dry contacts
  • Input frequency 1 mHz ... 5 kHz
  • Current output 0/4 mA ... 20 mA
  • Relay and transistor output
  • Start-up override
  • Line fault detection (LFD)
  • Up to SIL 2 acc. to IEC 61508/IEC 61511

Datasheet excerpt: Technical data of KFD2-UFC-Ex1.D

Product Description
24 V DC
General specifications
Signal typeDigital Input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
Connectionterminals 23+, 24- or power feed module/Power Rail
Rated voltage20 ... 30 V DC
Rated currentapprox. 100 mA
Power dissipation/power consumption≤ 2 W / 2.2 W
Interface
Programming interfaceprogramming socket
Input
Connection sidefield side
ConnectionInput I: intrinsically safe: terminals 1+, 3-
Input II: non-intrinsically safe: terminals 13+, 14-
Input Isensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Pulse duration> 50 µs
Input frequency0.001 ... 5000 Hz
Line fault detectionbreakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Input IIstartup override: 1 ... 1000 s, adjustable in steps of 1 s
Active/PassiveI > 4 mA (for min. 100 ms) / I < 1.5 mA
Open circuit voltage/short-circuit current18 V / 5 mA
Output
Connection sidecontrol side
Connectionoutput I: terminals 10, 11, 12
output II: terminals 16, 17, 18
outout III: terminasl 19+, 20-
output IV: terminals 8+, 7-
Output I, IIsignal, relay
Contact loading250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
Mechanical life5 x 107 switching cycles
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Output IIIelectronic output, passive
Contact loading40 V DC
Signal level1-signal: (L+) - 2.5 V (50 mA, short-circuit/overload proof)
0-signal: switched off (off-state current ≤ 10 µA)
Output IVanalog
Current range0 ... 20 mA or 4 ... 20 mA
Open loop voltagemax. 24 V DC
Loadmax. 650 Ω
Fault signaldownscale I ≤ 3.6 mA , upscale ≥ 21.5 mA (acc. NAMUR NE43)
Collective error messagePower Rail
Transfer characteristics
Output IV
Resolution< 10 µA
Accuracy< 20 µA
Influence of ambient temperature0.005 %/K (50 ppm)
Indicators/settings
Display elementsLEDs , display
Control elementsControl panel
Configurationvia operating buttons
via PACTware
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Mass300 g
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-Type Examination CertificateTÜV 99 ATEX 1471
Marking II (1)G [Ex ia Ga] IIC
II (1)D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I
CertificateTÜV 02 ATEX 1885 X
Marking II 3G Ex nA nC IIC T4 Gc
Output I, II
Contact loading50 V AC/2 A/cos φ > 0.7; 40 V DC/1 A resistive load
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing16-538FM-12
UL approvalE223772
IECEx approvalIECEx TUN 04.0007
Approved for[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
 
 