DESCRIPTIONS
-
Flex™ Digital DC Output Module, Number Of Channels: 16 (Non-Isolated), Output: On-State Voltage Range: 10 VDC Min, 24 VDC Nominal, 31.2 VDC Max, Off-State Voltage: 31.2 VDC Max, On-State Current: 1 MA Min Per Channel, 500 MA Maximum Per Channel, Output Current Rating: 8 A (16 Outputs At 0.5 A), Off-State Leakage: 0.5 MA Max, On-State Voltage Drop: 0.5 VDC Max, Voltage Rating: 10 - 31.2 VDC (Includes 5% AC Ripple), Current Rating: Supply: 60 MA At 24 VDC, Isolation: 2121 VDC For 1 SEC Between User And System, Enclosure: Open Type, Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 30 - 1000 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 30 MHZ, Connection Cables: 12 AWG Stranded Copper Wire, Communication: EtherNet/IP, ControlNet, DeviceNet And Profibus DP, Mounting: DIN Rail, Panel, Length: 3.7 IN, Width: 2.7 IN, Height: 3.7 IN, Temperature Rating: 32 - 131 DEG F, Environmental Conditions: Relative Humidity: 5 - 95% Non-Condensing, Vibration: 5 G, Shock: 30 G (Operating), 50 G (Non-Operating), Response Time: Delay (Off To On/On To Off): 0.5 MS/1 MS, Power Dissipation: 5 W At 31.2 VDC, Output Type: Current Sourcing, Surge Current: 1.5 A For 50 MS, Repeatable Every 2 SEC, Surge Transient Immunity: Plus/Minus 1 KV Line-Line(DM) And Plus/Minus 2 KV Line-Earth(CM) On Signal Ports, Indicator: 16 Yellow Status, Keyswitch Position: 2, Bus Rating: 60 MA, Standard/Approvals: C/US UL listed, CSA certified, CE-ATEX, CE-EMC, C-TICK, GOST_R, KCC certified, MARINE-ABS, MARINE-BVS, MARINE-DNV, MARINE-GL, MARINE-KRS, MARINE-LR, ROSTECHNADZOR, TUV-FS, Application: For in-cabinets
SPECIFICATIONS
-
-
Item Name: Digital DC Output Module
-
Sub Brand: Flex™
-
Number Of Channels: 16 (Non-Isolated)
-
Output: On-State Voltage Range: 10 VDC Min, 24 VDC Nominal, 31.2 VDC Max, Off-State Voltage: 31.2 VDC Max, On-State Current: 1 MA Min Per Channel, 500 MA Maximum Per Channel, Output Current Rating: 8 A (16 Outputs At 0.5 A), Off-State Leakage: 0.5 MA Max, On-State Voltage Drop: 0.5 VDC Max
-
Voltage Rating: 10 - 31.2 VDC (Includes 5% AC Ripple)
-
Current Rating: Supply: 60 MA At 24 VDC
-
Isolation: 2121 VDC For 1 SEC Between User And System
-
Enclosure: Open Type
-
Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 30 - 1000 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 30 MHZ
-
Connection Cables: 12 AWG Stranded Copper Wire
-
Communication: EtherNet/IP, ControlNet, DeviceNet And Profibus DP
-
Mounting: DIN Rail, Panel
-
Length: 3.7 IN
-
Width: 2.7 IN
-
Height: 3.7 IN
-
Temperature Rating: 32 - 131 DEG F
-
Environmental Conditions: Relative Humidity: 5 - 95% Non-Condensing, Vibration: 5 G, Shock: 30 G (Operating), 50 G (Non-Operating)
-
Response Time: Delay (Off To On/On To Off): 0.5 MS/1 MS
-
Power Dissipation: 5 W At 31.2 VDC
-
Output Type: Current Sourcing
-
Indicator: 16 Yellow Status
-
Surge Transient Immunity: Plus/Minus 1 KV Line-Line(DM) And Plus/Minus 2 KV Line-Earth(CM) On Signal Ports
-
Surge Current: 1.5 A For 50 MS, Repeatable Every 2 SEC
-
Keyswitch Position: 2
-
Bus Rating: 60 MA
FEATURES
-
The FLEX I/O module plugs into the terminal base, connecting to the I/O bus and field devices. Since there is no direct wiring to the I/O module, modules can be removed and inserted under power, enabling to change modules without disturbing field wiring, other I/O modules, or system power. This eliminates costly downtime and the inefficiencies of restarting a system. - LED for each channel indicating status of: corresponding input device, output signal
- Protected (P) outputs have electronic protection, which acts to shut the module down in reaction to a short circuit, overload, or over-temperature condition, recovery from shutdown is automatic upon removal of the output fault, no fault status is provided to the processor
- Standards: C/US UL listed, CSA certified, CE-ATEX, CE-EMC, C-TICK, GOST_R, KCC certified, MARINE-ABS, MARINE-BVS, MARINE-DNV, MARINE-GL, MARINE-KRS, MARINE-LR, ROSTECHNADZOR, TUV-FS
- Applications: For in-cabinets
|
|
|
|