DESCRIPTIONS
-
Flex™ Digital AC Output Module, Number Of Channels: 8 (Non-Isolated), Output: Output Voltage: 85 VAC (Minimum), 120 VAC (Nominal), 132 VAC (Maximum), Output Current Rating: 4 A (8 Outputs At 500 MA), On-State Current: 5 MA Per Output (Minimum), 500 MA Per Output Maximum At 55 DEG C, 750 MA Per Output Maximum At 35 DEG C, 1 A On 4 Nonadjacent Outputs, 500 MA On The Remaining 4 Outputs At 30 DEG C, Voltage Drop On-State: 1 V At 0.5 A, Leakage Current Off-State: 2.25 MA, Isolation: 120 V (Continuous), Basic Insulation Type, Field Side To Backplane, No Isolation Between Individual Channels, Type Tested At 1250 VAC For 60 SEC, Enclosure: Open Type, Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 30 - 2000 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 900 MHZ, 1 V/M With 1 KHZ Sine-Wave 80% AM From 2000 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 30 MHZ, Mounting: DIN Rail, Panel, Length: 3.7 IN, Width: 2.7 IN, Height: 3.7 IN, Temperature Rating: 32 - 131 DEG F, Environmental Conditions: Relative Humidity: 5 - 95% Non-Condensing, Vibration: 2 G, Shock: 30 G (Operating), 50 G (Non-Operating), Response Time: Delay (Off To On/On To Off): 1/2 Cycle, Power Dissipation: 4.1 W At 0.5 A, 6.3 W At 0.75 A, 6.3 W At 1.0 A, Keyswitch Position: 8, Surge Current: 7 A For 40 MS, Repeatable Every 8 SEC, Bus Rating: 80 MA At 5 VDC, Surge Transient Immunity: Plus/Minus 1 KV Line-Line(DM) And Plus/Minus 2 KV Line-Earth(CM) On Signal Ports, Indicator: 8 Yellow Status, Standard/Approvals: UL listed, file number E65584, CSA certified, file number LR69960C, CE-ATEX marked, CE-EMC marked, CE-LVD marked, C-TICK certified, GOST_R certified, KCC certified, ROSTECHNADZOR, Application: For in-cabinets
SPECIFICATIONS
-
-
Item Name: Digital AC Output Module
-
Sub Brand: Flex™
-
Number Of Channels: 8 (Non-Isolated)
-
Output: Output Voltage: 85 VAC (Minimum), 120 VAC (Nominal), 132 VAC (Maximum), Output Current Rating: 4 A (8 Outputs At 500 MA), On-State Current: 5 MA Per Output (Minimum), 500 MA Per Output Maximum At 55 DEG C, 750 MA Per Output Maximum At 35 DEG C, 1 A On 4 Nonadjacent Outputs, 500 MA On The Remaining 4 Outputs At 30 DEG C, Voltage Drop On-State: 1 V At 0.5 A, Leakage Current Off-State: 2.25 MA
-
Isolation: 120 V (Continuous), Basic Insulation Type, Field Side To Backplane, No Isolation Between Individual Channels, Type Tested At 1250 VAC For 60 SEC
-
Enclosure: Open Type
-
Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 30 - 2000 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 900 MHZ, 1 V/M With 1 KHZ Sine-Wave 80% AM From 2000 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 30 MHZ
-
Mounting: DIN Rail, Panel
-
Length: 3.7 IN
-
Width: 2.7 IN
-
Height: 3.7 IN
-
Temperature Rating: 32 - 131 DEG F
-
Environmental Conditions: Relative Humidity: 5 - 95% Non-Condensing, Vibration: 2 G, Shock: 30 G (Operating), 50 G (Non-Operating)
-
Response Time: Delay (Off To On/On To Off): 1/2 Cycle
-
Power Dissipation: 4.1 W At 0.5 A, 6.3 W At 0.75 A, 6.3 W At 1.0 A
-
Indicator: 8 Yellow Status
-
Surge Transient Immunity: Plus/Minus 1 KV Line-Line(DM) And Plus/Minus 2 KV Line-Earth(CM) On Signal Ports
-
Surge Current: 7 A For 40 MS, Repeatable Every 8 SEC
-
Keyswitch Position: 8
-
Bus Rating: 80 MA At 5 VDC
FEATURES
-
The FLEX I/O module plugs into the terminal base, connecting to the I/O bus and field devices. Since there is no direct wiring to the I/O module, you can remove and insert modules under power, enabling you to change modules without disturbing field wiring, other I/O modules, or system power. This eliminates costly downtime and the inefficiencies of restarting a system. - Modules are available in densities ranging from 8 to 32 points
- Isolated inputs and outputs can be used in applications such as motor control centers, where individual control transformers are used
- Selectable input filter times from <1 - 60 MS
- LED for each channel indicating status of: corresponding input device, output signal
- Standards: UL listed, file number E65584, CSA certified, file number LR69960C, CE-ATEX marked, CE-EMC marked, CE-LVD marked, C-TICK certified, GOST_R certified, KCC certified, ROSTECHNADZOR