DESCRIPTIONS
-
Flex™ I/O Analog Combination I/O Module, Number Of Channels: 4 (2 Isolated Input, 2 Output), Input: Voltage: 0.156 MV/CNT Unipolar, 0.313 MV/CNT Bipolar, Current: 0.320 MICRO-A/CNT Unipolar, 0.640 MICRO-A/CNT Bipolar, Input Voltage Terminal: Plus/Minus 10 V (User Configurable), 0 - 10 V (User Configurable), Plus/Minus 5 V (User Configurable), 0 - 5 V (User Configurable), Input Current Terminal: 4 - 20 MA (User Configurable), 0 - 20 MA (User Configurable), Plus/Minus 20 MA (User Configurable), Output: Voltage: 0.320 MV/CNT, Current: 0.656 MICRO-A/CNT, Output Current Terminal: 0 MA Output Until Module Is Configured, 4 - 20 MA (User Configurable), 0 - 20 MA (User Configurable), Output Voltage Terminal: 0 V Output Until Module Is Configured, Plus/Minus 10 V (User Configurable), 0 - 10 V (User Configurable), Plus/Minus 5 V (User Configurable), 0 - 5 V (User Configurable), Current Load On Voltage Output: 3 MA, Voltage Rating: 19.2 - 31.2 VDC (Includes 5% AC Ripple), Current Rating: External DC Power Supply Current: 150 MA At 24 VDC, Isolation: 120 V (Continuous), Basic Insulation Type, Channel To Channel, Channel To User, Channel To System And User Power To System When Used With 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3T, or 1794-TB3TS, 250 V (Continuous), Basic Insulation Type, Channel To Channel, Channel To User, Channel To System, And User Power To System When Used With 1794-TBN, Type Tested At 1000 VAC For 60 SEC, Enclosure: Open Type, Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2000 MHZ, 10 V/M With 200 Hz 50% Pulse 100% AM At 900 MHZ, 10 V/M With 200 Hz 50% Pulse 100% AM At 1890 MHZ, 3 V/M With 1 KHZ Sine-Wave 80% AM From 2000 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ, Mounting: DIN Rail, Panel, Length: 3.7 IN, Width: 2.6 IN, Height: 3.7 IN, Temperature Rating: -4 To 131 DEG F, Environmental Conditions: Relative Humidity: 5 - 95% (Non-Condensing), Vibration Operating: 5 G At 10 - 500 HZ, Shock - Operating: 30 G, Non-Operating: 50 G, Response Time: Input Update Rate: 2.5/5/7.5 MS All Channels, Output Update Rate: 2.5/5 MS All Channels, Accuracy: Input Absolute Accuracy - Voltage Terminal: 0.1% Full Scale At 25 DEG C, Current Terminal: 0.1% Full Scale At 25 DEG C, Input Accuracy Drift With Temperature - Voltage Terminal: 0.0028% Full Scale/DEG C, Current Terminal: 0.0038% Full Scale/DEG C, Output Absolute Accuracy - Voltage Terminal: 0.1% Full Scale At 25 DEG C, Current Terminal: 0.1% Full Scale At 25 DEG C, Output Accuracy Drift With Temperature - Voltage Terminal: 0.0028% Full Scale/DEG C, Current Terminal: 0.0038% Full Scale/DEG C, Power Dissipation: 3.3 W At 31.2 VDC, Keyswitch Position: 5, Bus Rating: Flexbus Voltage: 5 VDC, Flexbus Current: 50 MA, Indicator: 1 Red/Green Power/Status Indicator, Resistance: Input Resistance - Voltage Terminal: More Than 10 MOHM, Current Terminal: Less Than 100 OHM, Resistive Load On Voltage Output: 0 -750 OHM, Resolution: Input: 16 Bits - Unipolar, 15 Bits Plus Sign - Bipolar, Output: 15 Bits Plus Sign
SPECIFICATIONS
-
-
Item Name: Analog Combination I/O Module
-
Sub Brand: Flex™ I/O
-
Number Of Channels: 4 (2 Isolated Input, 2 Output)
-
Input: Voltage: 0.156 MV/CNT Unipolar, 0.313 MV/CNT Bipolar, Current: 0.320 MICRO-A/CNT Unipolar, 0.640 MICRO-A/CNT Bipolar, Input Voltage Terminal: Plus/Minus 10 V (User Configurable), 0 - 10 V (User Configurable), Plus/Minus 5 V (User Configurable), 0 - 5 V (User Configurable), Input Current Terminal: 4 - 20 MA (User Configurable), 0 - 20 MA (User Configurable), Plus/Minus 20 MA (User Configurable)
-
Output: Voltage: 0.320 MV/CNT, Current: 0.656 MICRO-A/CNT, Output Current Terminal: 0 MA Output Until Module Is Configured, 4 - 20 MA (User Configurable), 0 - 20 MA (User Configurable), Output Voltage Terminal: 0 V Output Until Module Is Configured, Plus/Minus 10 V (User Configurable), 0 - 10 V (User Configurable), Plus/Minus 5 V (User Configurable), 0 - 5 V (User Configurable), Current Load On Voltage Output: 3 MA
-
Voltage Rating: 19.2 - 31.2 VDC (Includes 5% AC Ripple)
-
Current Rating: External DC Power Supply Current: 150 MA At 24 VDC
-
Isolation: 120 V (Continuous), Basic Insulation Type, Channel To Channel, Channel To User, Channel To System And User Power To System When Used With 1794-TB2, 1794-TB3, 1794-TB3S, 1794-TB3T, or 1794-TB3TS, 250 V (Continuous), Basic Insulation Type, Channel To Channel, Channel To User, Channel To System, And User Power To System When Used With 1794-TBN, Type Tested At 1000 VAC For 60 SEC
-
Enclosure: Open Type
-
Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2000 MHZ, 10 V/M With 200 Hz 50% Pulse 100% AM At 900 MHZ, 10 V/M With 200 Hz 50% Pulse 100% AM At 1890 MHZ, 3 V/M With 1 KHZ Sine-Wave 80% AM From 2000 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ
-
Mounting: DIN Rail, Panel
-
Length: 3.7 IN
-
Width: 2.6 IN
-
Height: 3.7 IN
-
Temperature Rating: -4 To 131 DEG F
-
Environmental Conditions: Relative Humidity: 5 - 95% (Non-Condensing), Vibration Operating: 5 G At 10 - 500 HZ, Shock - Operating: 30 G, Non-Operating: 50 G
-
Response Time: Input Update Rate: 2.5/5/7.5 MS All Channels, Output Update Rate: 2.5/5 MS All Channels
-
Accuracy: Input Absolute Accuracy - Voltage Terminal: 0.1% Full Scale At 25 DEG C, Current Terminal: 0.1% Full Scale At 25 DEG C, Input Accuracy Drift With Temperature - Voltage Terminal: 0.0028% Full Scale/DEG C, Current Terminal: 0.0038% Full Scale/DEG C, Output Absolute Accuracy - Voltage Terminal: 0.1% Full Scale At 25 DEG C, Current Terminal: 0.1% Full Scale At 25 DEG C, Output Accuracy Drift With Temperature - Voltage Terminal: 0.0028% Full Scale/DEG C, Current Terminal: 0.0038% Full Scale/DEG C
-
Power Dissipation: 3.3 W At 31.2 VDC
-
Indicator: 1 Red/Green Power/Status Indicator
-
Surge Transient Immunity: Plus/Minus 1 KV Line-Line(DM) And Plus/Minus 2 KV Line-Earth(CM) On Power Ports, Plus/Minus 2 KV Line-Earth(CM) On Shielded Signal Ports
-
Resolution: Input: 16 Bits - Unipolar, 15 Bits Plus Sign - Bipolar, Output: 15 Bits Plus Sign
-
Keyswitch Position: 5
-
Bus Rating: Flexbus Voltage: 5 VDC, Flexbus Current: 50 MA
-
Resistance: Input Resistance - Voltage Terminal: More Than 10 MOHM, Current Terminal: Less Than 100 OHM, Resistive Load On Voltage Output: 0 -750 OHM
-
Input Step Response: Input Step Response To 63% - Voltage Or Current Terminal: 1200 HZ Conversion Rate: 0.6 MS, 600 HZ Conversion Rate: 6.7 MS, 300 HZ Conversion Rate: 13.4 MS, 150 HZ Conversion Rate: 26.7 MS, Output Step Response To 63% Of Full Scale: Less Than 25 MIC-SEC
-
Rejection Ratio: Input Normal Mode Rejection Ratio - Voltage Or Current Terminal: -3 DB At 12 HZ (300 HZ Conversion Rate), -80 DB At 50 HZ (300 HZ Conversion Rate), -3 DB At 6 HZ (150 HZ Conversion Rate), -80 DB At 60 HZ (150 HZ Conversion Rate), Input Common Mode Rejection Ratio: -120 DB At 50/60 HZ
FEATURES
-
FLEX I/O offers all the functions of larger rack-based I/O without the space requirements. Its cost effectiveness, flexibility, modularity, and reliability have made it the most popular distributed I/O platform with over 4 million modules sold. FLEX I/O helps eliminate multiple long wiring runs, reduces terminations per point, decreases engineering and installation costs and time, and substantially reduces downtime. It complements all processor platforms from Rockwell Automation for a distributed I/O solution. Conformally coated, extreme environment FLEX I/O products help to reduce panel costs and the need for additional heating/cooling equipment, resulting in lower installation and maintenance costs. - Reduced space - wire direct from sensor to terminal base and eliminate terminal strip
- Functionality: 4- through 32-point modules offer functions of larger rack-based I/O
- Increased productivity: easy configuration and setup of I/O modules using wizards speeds engineering and installation
- Reduced downtime: removal and insertion under power (RIUP) and diagnostics
- Operation in harsh environments: conformal coated and extreme environment rated modules
- Network flexibility: communicates on EtherNet/IP, ControlNet, DeviceNet, and PROFIBUS DP
- Improved plant operations: HART analog modules pass through HART data to asset management software or controller for improved plant operations
- 2's complement percent, binary, offset binary
- Standards: C/US UL listed, CE-ATEX, CE-EMC, CSA certified, CSA_HAZ, C-tick, GOST_R, KCC certified, marine-ABS, marine-DNV, marine-KRS, ROSTECHNADZOR, RUS_PAT_APPR, TUV-FS
- Applications: For in-cabinets
|
|
|
|