Digital DC Input Module Diagnostic Flex, 16-ch., 10..31.2VDC, Allen-Bradley
DESCRIPTIONS
-
Flex™ Digital DC Input Module, Type: Diagnostic, Number Of Channels: 16 (Isolated), Input: On-State Voltage: 10 VDC (Minimum), 24 VDC Nominal, 31.2 VDC (Maximum), On-State Current: 2 MA (Minimum) At 10 VDC, 8.2 MA Nominal At 24 VDC, 12.1 MA (Maximum) At 31.2 VDC, Off-State Voltage: 5 VDC (Maximum), Off-State Current: 1.5 MA Min, Voltage Rating: 10 - 31.2 VDC, Isolation: 2121 VDC For 1 SEC Between User And System, Enclosure: Open Type, Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2000 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 900 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 1890 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ, Connection Cables: 12 AWG Stranded Copper Wire, Communication: EtherNet/IP, ControlNet, DeviceNet And Profibus DP, Mounting: DIN Rail, Panel, Length: 3.7 IN, Width: 2.1 IN, Height: 1.8 IN, Temperature Rating: 32 - 131 DEG F, Environmental Conditions: Relative Humidity: 5 - 95% Non-Condensing, Vibration: 5 G, Shock: 50 G (Non-Operating), Response Time: Off To On/On To Off: 0.25, 0.5, 1, 2, 4, 8, 16, 32 MS, Default: 0.25 MS, Power Dissipation: 8.5 W At 31.2 VDC, Output Type: Current Sinking, Impedance: Input: 3.1 KOHM, Indicator: 16 Yellow ON/OFF Status (Field Side), 16 Red Diagnostic Status (Each Channel, Field Side), 1 Red Module Fault (Field Side), Surge Transient Immunity: Plus/Minus 1 KV Line-Line(DM) And Plus/Minus 2 KV Line-Earth(CM) On Signal/Power Ports, Keyswitch Position: 2, Bus Rating: 30 MA, Standard/Approvals: UL listed, CSA certified, CE-EMC marked, C-TICK certified, GOST_R certified, KCC certified, MARINE-ABS certified, MARINE-BVS certified, MARINE-DNV certified, MARINE-GL certified, MARINE-LR certified, ROSTECHNADZOR, Application: For in-cabinets
SPECIFICATIONS
-
-
Item Name: Digital DC Input Module
-
Type: Diagnostic
-
Sub Brand: Flex™
-
Number Of Channels: 16 (Isolated)
-
Input: On-State Voltage: 10 VDC (Minimum), 24 VDC Nominal, 31.2 VDC (Maximum), On-State Current: 2 MA (Minimum) At 10 VDC, 8.2 MA Nominal At 24 VDC, 12.1 MA (Maximum) At 31.2 VDC, Off-State Voltage: 5 VDC (Maximum), Off-State Current: 1.5 MA Min
-
Voltage Rating: 10 - 31.2 VDC
-
Isolation: 2121 VDC For 1 SEC Between User And System
-
Enclosure: Open Type
-
Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2000 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 900 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 1890 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ
-
Connection Cables: 12 AWG Stranded Copper Wire
-
Communication: EtherNet/IP, ControlNet, DeviceNet And Profibus DP
-
Mounting: DIN Rail, Panel
-
Length: 3.7 IN
-
Width: 2.1 IN
-
Height: 1.8 IN
-
Temperature Rating: 32 - 131 DEG F
-
Environmental Conditions: Relative Humidity: 5 - 95% Non-Condensing, Vibration: 5 G, Shock: 50 G (Non-Operating)
-
Response Time: Off To On/On To Off: 0.25, 0.5, 1, 2, 4, 8, 16, 32 MS, Default: 0.25 MS
-
Power Dissipation: 8.5 W At 31.2 VDC
-
Output Type: Current Sinking
-
Indicator: 16 Yellow ON/OFF Status (Field Side), 16 Red Diagnostic Status (Each Channel, Field Side), 1 Red Module Fault (Field Side)
-
Surge Transient Immunity: Plus/Minus 1 KV Line-Line(DM) And Plus/Minus 2 KV Line-Earth(CM) On Signal/Power Ports
-
Impedance: Input: 3.1 KOHM
-
Keyswitch Position: 2
-
Bus Rating: 30 MA
FEATURES
-
The FLEX I/O module plugs into the terminal base, connecting to the I/O bus and field devices. Since there is no direct wiring to the I/O module, modules can be removed and inserted under power, enabling to change modules without disturbing field wiring, other I/O modules, or system power. This eliminates costly downtime and the inefficiencies of restarting a system. - LED for each channel indicating status of: corresponding input device, output signal
- Diagnostic (D) modules detect, indicate, and report the following faults: open input or output field devices or wiring, shorted output field devices, shorted input or output wiring, reverse polarity of user supply wiring
- Standards: UL listed, CSA certified, CE-EMC marked, C-TICK certified, GOST_R certified, KCC certified, MARINE-ABS certified, MARINE-BVS certified, MARINE-DNV certified, MARINE-GL certified, MARINE-LR certified, ROSTECHNADZOR
- Applications: For in-cabinets
|