Image is illustrative
|
Digital Contact Output Module ControlLogix, 8NO/NC isolated relay outputs, 2points/group, 36pin, 10..265VAC/ 5..150VDC, Rockwell Automation Code:
1756-OX8I
Cena (indicative)
Manufacturer
:
Availability:
21 days
|
Weight:
0.48 kg/pc
|
Volume:
0.0021 m3/pc
|
|
|
|
|
Digital Contact Output Module ControlLogix, 8NO/NC isolated relay outputs, 2points/group, 36pin, 10..265VAC/ 5..150VDC, Rockwell Automation
ControlLogix® Contact Output Module, Number Of Channels: 8, Output: Operating Voltage: 5 - 125 VDC, 10 - 240 VAC, Contact Current Rating: 2 A At 5 - 30 VDC, 0.5 A At 48 VDC, 0.25 A At 125 VDC, 2 A At 125/240 VAC, Current Rating: Drawn: 100 MA At 5.1 V, 100 MA At 24 V, Load Current: 10 MA Per Point, Isolation: 250 V (Continuous), Basic Insulation Type, Outputs-To-Backplane, And Output-To-Output, 1350 VAC For 2 SEC Routine Test, Power Rating: Backplane: 2.9 W, Enclosure: Open Type, Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2000 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 900 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 1890 MHZ, 3 V/M With 1 KHZ Sine-Wave 80% AM From 2000 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ, Display: Output, Module Health And Communication Status, Interface: Removable Terminal Block, Mounting: Chassis, Width: 1-23/64 IN, Height: 5-11/16 IN, Temperature Rating: 32 - 140 DEG F, Environmental Conditions: Relative Humidity: 5 - 95% Non-Condensing, Vibration: 2 G, Shock: 30 G(Operating), 50 G (Non-Operating), Response Time: Delay (Off To On): 13 MS Maximum, Delay (On To Off): 13 MS Maximum, Power Dissipation: 3.1 W At 60 DEG C, Operating Cycles: Contacts Life: 300000 Operations Resistive, 100000 Operations Inductive, Slot Width: 1, Surge Transient Immunity: Plus/Minus 1 KV Line-Line (DM) And Plus/Minus 2 KV Line-Earth (CM) On Signal Ports, Contact Configuration: NO/NC, Standard/Approvals: C/US UL listed, CSA certified, CE-EMC marked, CE-LVD marked, C-TICK certified, FM-US_HAZ, GOST_R certified, MARINE-ABS certified, MARINE-BVS certified, MARINE-DNV certified, MARINE-GL certified, MARINE-LR certified, ROSTECHNADZOR, TUV-FS certified
|
|
Specifications
- Item Name: Contact Output Module
- Sub Brand: ControlLogix®
- Number Of Channels: 8
- Output: Operating Voltage: 5 - 125 VDC, 10 - 240 VAC, Contact Current Rating: 2 A At 5 - 30 VDC, 0.5 A At 48 VDC, 0.25 A At 125 VDC, 2 A At 125/240 VAC
- Current Rating: Drawn: 100 MA At 5.1 V, 100 MA At 24 V, Load Current: 10 MA Per Point
- Isolation: 250 V (Continuous), Basic Insulation Type, Outputs-To-Backplane, And Output-To-Output, 1350 VAC For 2 SEC Routine Test
- Power Rating: Backplane: 2.9 W
- Enclosure: Open Type
- Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2000 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 900 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 1890 MHZ, 3 V/M With 1 KHZ Sine-Wave 80% AM From 2000 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ
- Display: Output, Module Health And Communication Status
- Interface: Removable Terminal Block
- Mounting: Chassis
- Width: 1-23/64 IN
- Height: 5-11/16 IN
- Temperature Rating: 32 - 140 DEG F
- Environmental Conditions: Relative Humidity: 5 - 95% Non-Condensing, Vibration: 2 G, Shock: 30 G(Operating), 50 G (Non-Operating)
- Response Time: Delay (Off To On): 13 MS Maximum, Delay (On To Off): 13 MS Maximum
- Power Dissipation: 3.1 W At 60 DEG C
- Operating Cycles: Contacts Life: 300000 Operations Resistive, 100000 Operations Inductive
- Surge Transient Immunity: Plus/Minus 1 KV Line-Line (DM) And Plus/Minus 2 KV Line-Earth (CM) On Signal Ports
- Slot Width: 1
- Contact Configuration: NO/NC
Features
Variety of voltage interface capabilities
Isolated and nonisolated module types
Point-level output fault states
Direct-connect or rack-optimized communication
Field-side diagnostics on select modules
These modules have individually isolated inputs or outputs
Standards: C/US UL listed, CSA certified, CE-EMC marked, CE-LVD marked, C-TICK certified, FM-US_HAZ, GOST_R certified, MARINE-ABS certified, MARINE-BVS certified, MARINE-DNV certified, MARINE-GL certified, MARINE-LR certified, ROSTECHNADZOR, TUV-FS certified
|
|
|
|