Image is illustrative
|
Digital DC Output Module ControlLogix, 16-ch., 5VDC, 210mA 5.1V drawn, Allen-Bradley Code:
1756-OG16
Cena (indicative)
Manufacturer
:
Availability:
21 days
|
Weight:
0.361 kg/pc
|
Volume:
0.002 m3/pc
|
|
|
|
|
Digital DC Output Module ControlLogix, 16-ch., 5VDC, 210mA 5.1V drawn, Allen-Bradley
DESCRIPTIONS
-
ControlLogix® Digital DC Output Module, Number Of Channels: 16 (8 Points/Group), Output: Operating Voltage: 4.5 - 5.5 VDC, 50 MV P-P Ripple (Maximum), Off-State Leakage Current Per Point: 0.1 MA Per Point (Maximum), On-State Voltage Drop: 0.4 VDC (Maximum), Voltage Rating: 5 VDC, Current Rating: Drawn: 210 MA At 5.1 V, 2 MA At 24 V, Continuous Current: 24 MA (Maximum), Load Current Per Point: 24 MA (Maximum), Load Current Per Module: 384 MA (Maximum), Load Current: 0.15 MA, Isolation: 250 V (Continuous), Basic Insulation Type, Outputs-To-Backplane, And Output Group-To-Group, No Isolation Between Individual Group Outputs, Routine Tested At 1350 VAC For 2 SEC, Power Rating: Backplane: 1.12 W, Enclosure: Open Type, Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2000 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 900 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 1890 MHZ, 3 V/M With 1 KHZ Sine-Wave 80% AM From 2000 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ, Display: Output, Module Health And Communication Status, Mounting: Chassis, Temperature Rating: 32 - 140 DEG F, Environmental Conditions: Relative Humidity: 5 - 95% Non-Condensing, Vibration: 2 G, Shock: 30 G (Operating), 50 G (Non-Operating), Response Time: Delay (Off To On): 45 MIC-SEC Nominal/450 MIC-SEC Maximum, Delay (On To Off): 145 MIC-SEC Nominal/700 MIC-SEC Maximum, Power Dissipation: 1.5 W At 60 DEG C, Output Type: Current Sourcing, Slot Width: 1, Standard/Approvals: C/US UL listed, CSA certified, CE marked, C-Tick certified, KC certified
SPECIFICATIONS
-
-
Item Name: Digital DC Output Module
-
Sub Brand: ControlLogix®
-
Number Of Channels: 16 (8 Points/Group)
-
Output: Operating Voltage: 4.5 - 5.5 VDC, 50 MV P-P Ripple (Maximum), Off-State Leakage Current Per Point: 0.1 MA Per Point (Maximum), On-State Voltage Drop: 0.4 VDC (Maximum)
-
Voltage Rating: 5 VDC
-
Current Rating: Drawn: 210 MA At 5.1 V, 2 MA At 24 V, Continuous Current: 24 MA (Maximum), Load Current Per Point: 24 MA (Maximum), Load Current Per Module: 384 MA (Maximum), Load Current: 0.15 MA
-
Isolation: 250 V (Continuous), Basic Insulation Type, Outputs-To-Backplane, And Output Group-To-Group, No Isolation Between Individual Group Outputs, Routine Tested At 1350 VAC For 2 SEC
-
Power Rating: Backplane: 1.12 W
-
Enclosure: Open Type
-
Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2000 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 900 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 1890 MHZ, 3 V/M With 1 KHZ Sine-Wave 80% AM From 2000 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ
-
Display: Output, Module Health And Communication Status
-
Mounting: Chassis
-
Temperature Rating: 32 - 140 DEG F
-
Environmental Conditions: Relative Humidity: 5 - 95% Non-Condensing, Vibration: 2 G, Shock: 30 G (Operating), 50 G (Non-Operating)
-
Response Time: Delay (Off To On): 45 MIC-SEC Nominal/450 MIC-SEC Maximum, Delay (On To Off): 145 MIC-SEC Nominal/700 MIC-SEC Maximum
-
Power Dissipation: 1.5 W At 60 DEG C
-
Output Type: Current Sourcing
-
Slot Width: 1
FEATURES
-
- Variety of voltage interface capabilities
- Point-level output fault states
- Field-side diagnostics on select modules
- Standards: C/US UL listed, CSA certified, CE marked, C-Tick certified, KC certified
|
|
|
|