Image is illustrative
|
Digital DC Output Module ControlLogix, 16-ch., 350mA 5.1V drawn, 12..24VDC, Allen-Bradley Code:
1756-OB16I
Cena (indicative)
Manufacturer
:
Availability:
21 days
|
Weight:
0.354 kg/pc
|
Volume:
0.002 m3/pc
|
|
|
|
|
Digital DC Output Module ControlLogix, 16-ch., 350mA 5.1V drawn, 12..24VDC, Allen-Bradley
ControlLogix® Digital DC Output Module, Number Of Channels: 16 (Isolated), Output: Operating Voltage: 10 - 30 VDC, On-State Voltage Drop: 1.2 VDC At 2 A, Voltage Rating: 12/24 VDC, Current Rating: Drawn: 350 MA At 5.1 V, 2.5 MA At 24 V, Off-State Leakage Current Per Point: 0.5 MA Per Point, Current Per Point: 2 A At 30 DEG C, 1 A At 60 DEG C, Current Per Module: 8 A At 30 DEG C, 4 A At 60 DEG C, Load Current: 1 MA Per Point, Isolation: 250 V (Continuous), Basic Insulation Type, Outputs-To-Backplane, 125 V (Continuous), Basic Insulation Type, Output-To-Output, 1350 VAC For 2 SEC Routine Test, Power Rating: Backplane: 1.8 W, Enclosure: Open Type, Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2000 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 900 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 1890 MHZ, 3 V/M With 1 KHZ Sine-Wave 80% AM From 2000 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ, Display: Output, Module Health And Communication Status, Interface: Removable Terminal Block, Mounting: Chassis, Width: 1-23/64 IN, Height: 5-11/16 IN, Temperature Rating: 32 - 140 DEG F, Environmental Conditions: Relative Humidity: 5 - 95% Non-Condensing, Vibration: 2 G, Shock: 30 G(Operating), 50 G (Non-Operating), Response Time: Delay (Off To On): 1 MS Maximum, Delay (On To Off): 2 MS Maximum, Power Dissipation: 3.6 W At 60 DEG C, Output Type: Current Sinking/Source, Slot Width: 1, Surge Transient Immunity: Plus/Minus 1 KV Line-Line (DM) And Plus/Minus 2 KV Line-Earth (CM) On Signal Ports, Surge Current: 4 A For 10 MS/Point, Repeatable Every 2 SEC, Standard/Approvals: C/US UL listed, CSA certified, CE-ATEX, CE-EMC, CE-LVD, C-TICK, FM-US_HAZ, GOST_R, KCC certified, MARINE-ABS, MARINE-BVS, MARINE-DNV, MARINE-GL, MARINE-LR, ROSTECHNADZOR, TUV-FS
|
|
Specifications
- Item Name: Digital DC Output Module
- Sub Brand: ControlLogix®
- Number Of Channels: 16 (Isolated)
- Output: Operating Voltage: 10 - 30 VDC, On-State Voltage Drop: 1.2 VDC At 2 A
- Voltage Rating: 12/24 VDC
- Current Rating: Drawn: 350 MA At 5.1 V, 2.5 MA At 24 V, Off-State Leakage Current Per Point: 0.5 MA Per Point, Current Per Point: 2 A At 30 DEG C, 1 A At 60 DEG C, Current Per Module: 8 A At 30 DEG C, 4 A At 60 DEG C, Load Current: 1 MA Per Point
- Isolation: 250 V (Continuous), Basic Insulation Type, Outputs-To-Backplane, 125 V (Continuous), Basic Insulation Type, Output-To-Output, 1350 VAC For 2 SEC Routine Test
- Power Rating: Backplane: 1.8 W
- Enclosure: Open Type
- Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2000 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 900 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 1890 MHZ, 3 V/M With 1 KHZ Sine-Wave 80% AM From 2000 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ
- Display: Output, Module Health And Communication Status
- Interface: Removable Terminal Block
- Mounting: Chassis
- Width: 1-23/64 IN
- Height: 5-11/16 IN
- Temperature Rating: 32 - 140 DEG F
- Environmental Conditions: Relative Humidity: 5 - 95% Non-Condensing, Vibration: 2 G, Shock: 30 G(Operating), 50 G (Non-Operating)
- Response Time: Delay (Off To On): 1 MS Maximum, Delay (On To Off): 2 MS Maximum
- Power Dissipation: 3.6 W At 60 DEG C
- Output Type: Current Sinking/Source
- Surge Transient Immunity: Plus/Minus 1 KV Line-Line (DM) And Plus/Minus 2 KV Line-Earth (CM) On Signal Ports
- Surge Current: 4 A For 10 MS/Point, Repeatable Every 2 SEC
- Slot Width: 1
Features
Variety of voltage interface capabilities
Isolated and nonisolated module types
Point-level output fault states
Direct-connect or rack-optimized communication
Field-side diagnostics on select modules
These modules have individually isolated inputs or outputs
Standards: C/US UL listed, CSA certified, CE-ATEX, CE-EMC, CE-LVD, C-TICK, FM-US_HAZ, GOST_R, KCC certified, MARINE-ABS, MARINE-BVS, MARINE-DNV, MARINE-GL, MARINE-LR, ROSTECHNADZOR, TUV-FS
|
|
|
|