|
|
Image is illustrative
|
Digital AC Output Module ControlLogix, 16-ch., 120/240VAC, 400mA 5.1V drawn, Allen-Bradley Code:
1756-OA16
Cena (indicative)
Manufacturer
:
Availability:
21 days
|
Weight:
0.383 kg/pc
|
Volume:
0.0023 m3/pc
|
|
|
|
|
Digital AC Output Module ControlLogix, 16-ch., 120/240VAC, 400mA 5.1V drawn, Allen-Bradley
DESCRIPTIONS
-
ControlLogix® Digital AC Output Module, Number Of Channels: 16 (Mechanically Fused/Group), Output: Operating Voltage: 74 - 265 VAC, On-State Voltage Drop: 1.5 V At 0.5 A, 5.7 V At Load Current Less Than 50 MA, Voltage Rating: 120/240 VAC, Commutating Voltage: 4 V/MICSEC For Loads Greater Than 50 MA, 0.2 V/MICSEC For Loads Less Than 50 MA, Current Rating: Drawn: 400 MA At 5.1 V, 2 MA At 24 V, Off-State Leakage Current: 3 MA Per Point, Current Per Point: 0.5 A At 60 DEG C, Current Per Group: 2 A At 60 DEG C, Current Per Module: 4 A At 60 DEG C, Load Current: 10 MA Per Point, Isolation: 250 V (Continuous), Basic Insulation Type, Outputs-To-Backplane, And Output Group-To-Group, No Isolation Between Individual Group Outputs, 1350 VAC For 2 SEC Routine Test, Power Rating: Backplane: 0.66 W, Enclosure: Open Type, Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2000 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 900 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 1890 MHZ, 3 V/M With 1 KHZ Sine-Wave 80% AM From 2000 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ, Display: Output, Module Health And Communication Status, Interface: Removable Terminal Block, Mounting: Chassis, Width: 1-23/64 IN, Height: 5-11/16 IN, Temperature Rating: 32 - 140 DEG F, Environmental Conditions: Relative Humidity: 5 - 95% Non-Condensing, Vibration: 2 G, Shock: 30 G(Operating), 50 G (Non-Operating), Response Time: Delay (Off To On): 9.3 MS At 60 HZ, 11 MS At 50 HZ, Delay (On To Off): 9.3 MS At 60 HZ, 11 MS At 50 HZ, Power Dissipation: 6.5 W At 60 DEG C, Surge Current: 5 A For 43 MS/Point, Repeatable Every 2 SEC At 60 DEG C/Point, 15 A For 43 MS/Point, Repeatable Every 2 SEC At 60 DEG C/Group, Slot Width: 1, Surge Transient Immunity: Plus/Minus 1 KV Line-Line (DM) And Plus/Minus 2 KV Line-Earth (CM) On Signal Ports, Standard/Approvals: C/US UL listed, CSA certified, CE-EMC, CE-LVD, C-TICK, FM-US_HAZ, GOST_R, KCC certified, MARINE-ABS, MARINE-BVS, MARINE-DNV, MARINE-GL, MARINE-KRS, MARINE-LR, ROSTECHNADZOR
SPECIFICATIONS
-
-
Item Name: Digital AC Output Module
-
Sub Brand: ControlLogix®
-
Number Of Channels: 16 (Mechanically Fused/Group)
-
Output: Operating Voltage: 74 - 265 VAC, On-State Voltage Drop: 1.5 V At 0.5 A, 5.7 V At Load Current Less Than 50 MA
-
Voltage Rating: 120/240 VAC, Commutating Voltage: 4 V/MICSEC For Loads Greater Than 50 MA, 0.2 V/MICSEC For Loads Less Than 50 MA
-
Current Rating: Drawn: 400 MA At 5.1 V, 2 MA At 24 V, Off-State Leakage Current: 3 MA Per Point, Current Per Point: 0.5 A At 60 DEG C, Current Per Group: 2 A At 60 DEG C, Current Per Module: 4 A At 60 DEG C, Load Current: 10 MA Per Point
-
Isolation: 250 V (Continuous), Basic Insulation Type, Outputs-To-Backplane, And Output Group-To-Group, No Isolation Between Individual Group Outputs, 1350 VAC For 2 SEC Routine Test
-
Power Rating: Backplane: 0.66 W
-
Enclosure: Open Type
-
Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2000 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 900 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 1890 MHZ, 3 V/M With 1 KHZ Sine-Wave 80% AM From 2000 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ
-
Display: Output, Module Health And Communication Status
-
Interface: Removable Terminal Block
-
Mounting: Chassis
-
Width: 1-23/64 IN
-
Height: 5-11/16 IN
-
Temperature Rating: 32 - 140 DEG F
-
Environmental Conditions: Relative Humidity: 5 - 95% Non-Condensing, Vibration: 2 G, Shock: 30 G(Operating), 50 G (Non-Operating)
-
Response Time: Delay (Off To On): 9.3 MS At 60 HZ, 11 MS At 50 HZ, Delay (On To Off): 9.3 MS At 60 HZ, 11 MS At 50 HZ
-
Power Dissipation: 6.5 W At 60 DEG C
-
Surge Transient Immunity: Plus/Minus 1 KV Line-Line (DM) And Plus/Minus 2 KV Line-Earth (CM) On Signal Ports
-
Surge Current: 5 A For 43 MS/Point, Repeatable Every 2 SEC At 60 DEG C/Point, 15 A For 43 MS/Point, Repeatable Every 2 SEC At 60 DEG C/Group
-
Slot Width: 1
FEATURES
-
- Variety of voltage interface capabilities
- Isolated and nonisolated module types
- Point-level output fault states
- Direct-connect or rack-optimized communication
- Field-side diagnostics on select modules
- Standards: C/US UL listed, CSA certified, CE-EMC, CE-LVD, C-TICK, FM-US_HAZ, GOST_R, KCC certified, MARINE-ABS, MARINE-BVS, MARINE-DNV, MARINE-GL, MARINE-KRS, MARINE-LR, ROSTECHNADZOR
|
|
|
|