Image is illustrative
|
Isolated RTD Input Module ControlLogix, 6points, 20pin, Rockwell Automation Code:
1756-IR6I
Cena (indicative)
Manufacturer
:
Availability:
21 days
|
Weight:
0.415 kg/pc
|
Volume:
0.002 m3/pc
|
|
|
|
|
Isolated RTD Input Module ControlLogix, 6points, 20pin, Rockwell Automation
ControlLogix® Analog RTD And Thermocouple Module, Number Of Channels: 6 (Isolated), Input: 1 - 487 OHM, 2 - 1000 OHM, 4 - 2000 OHM, 8 - 4020 OHM, Voltage Rating: Overvoltage Protection: 24 VAC/VDC, Current Rating: Drawn: 250 MA At 5.1 V, 125 MA At 24 V, Isolation: 250 V (Continuous), Basic Insulation Type, Input Channels-To-Backplane, And Input Channel-To-Channel, 1350 VAC For 2 SEC Routine Test, Power Rating: Backplane: 4.25 W, Enclosure: Open Type, Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2000 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 900 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 1890 MHZ, 1 V/M With 1 KHZ Sine-Wave 80% AM From 2000 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ On Shielded Signal Ports, Display: Module Health, In Calibration Mode, Interface: Removable Terminal Block, IEEE, Mounting: Chassis, Width: 1-23/64 IN, Height: 5-11/16 IN, Temperature Rating: 32 - 140 DEG F, Environmental Conditions: Relative Humidity: 5 - 95% Non-Condensing, Vibration: 2 G At 10 - 500 HZ , Shock: 30 G(Operating), 50 G (Non-Operating), Response Time: Open Circuit Detection Time: Negative Full Scale Reading Within 5 SEC With Any Combination Of Lost Wires, Except Input Terminal A Alone, If Input Terminal A Is Lost By Itself, The Module Reads A Positive Full Scale Reading Within 5 SEC, Settling Time: Less Than 80 MS To 5% Of Full Scale, Module Scan Time: 25 MS Min Floating Point, 50 MS Min Floating Point, 10 MS Min Integer, Accuracy: Calibrated: Better Than 0.1% Of Range At 25 DEG C, Power Dissipation: 4.3 W, Rejection Ratio: Normal Mode Noise Rejection: 60 DB At 60 HZ, Common Mode Noise Rejection: 120 DB At 60 HZ, 100 DB At 50 HZ, Slot Width: 1, Resolution: 16 Bits, 1 - 487 OHM: 7.7 MOHM/Bit, 2 - 1000 OHM: 15 MOHM/Bit, 4 - 2000 OHM: 30 MOHM/Bit, 8 - 4020 OHM: 60 MOHM/Bit, Surge Transient Immunity: Plus/Minus 2 KV Line-Earth (CM) On Shielded Signal Ports, Standard/Approvals: C/US UL listed, CSA certified, CE-ATEX, CE-EMC, CE-LVD, C-TICK, FM-US_HAZ, GOST_R, KCC certified, MARINE-ABS, MARINE-BVS, MARINE-DNV, MARINE-GL, MARINE-KRS, MARINE-LR, ROSTECHNADZOR, RUS_PAT_APPR, TUV-FS
|
|
Specifications
- Item Name: Analog RTD And Thermocouple Module
- Sub Brand: ControlLogix®
- Number Of Channels: 6 (Isolated)
- Input: 1 - 487 OHM, 2 - 1000 OHM, 4 - 2000 OHM, 8 - 4020 OHM
- Voltage Rating: Overvoltage Protection: 24 VAC/VDC
- Current Rating: Drawn: 250 MA At 5.1 V, 125 MA At 24 V
- Isolation: 250 V (Continuous), Basic Insulation Type, Input Channels-To-Backplane, And Input Channel-To-Channel, 1350 VAC For 2 SEC Routine Test
- Power Rating: Backplane: 4.25 W
- Enclosure: Open Type
- Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2000 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 900 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 1890 MHZ, 1 V/M With 1 KHZ Sine-Wave 80% AM From 2000 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ On Shielded Signal Ports
- Display: Module Health, In Calibration Mode
- Interface: Removable Terminal Block, IEEE
- Mounting: Chassis
- Width: 1-23/64 IN
- Height: 5-11/16 IN
- Temperature Rating: 32 - 140 DEG F
- Environmental Conditions: Relative Humidity: 5 - 95% Non-Condensing, Vibration: 2 G At 10 - 500 HZ , Shock: 30 G(Operating), 50 G (Non-Operating)
- Response Time: Open Circuit Detection Time: Negative Full Scale Reading Within 5 SEC With Any Combination Of Lost Wires, Except Input Terminal A Alone, If Input Terminal A Is Lost By Itself, The Module Reads A Positive Full Scale Reading Within 5 SEC, Settling Time: Less Than 80 MS To 5% Of Full Scale, Module Scan Time: 25 MS Min Floating Point, 50 MS Min Floating Point, 10 MS Min Integer
- Accuracy: Calibrated: Better Than 0.1% Of Range At 25 DEG C
- Power Dissipation: 4.3 W
- Surge Transient Immunity: Plus/Minus 2 KV Line-Earth (CM) On Shielded Signal Ports
- Resolution: 16 Bits, 1 - 487 OHM: 7.7 MOHM/Bit, 2 - 1000 OHM: 15 MOHM/Bit, 4 - 2000 OHM: 30 MOHM/Bit, 8 - 4020 OHM: 60 MOHM/Bit
- Rejection Ratio: Normal Mode Noise Rejection: 60 DB At 60 HZ, Common Mode Noise Rejection: 120 DB At 60 HZ, 100 DB At 50 HZ
- Slot Width: 1
Features
On-board data alarming
Scaling to engineering units
Real-time channel sampling
Data format: Integer mode (left justified, 2 SEC complement) IEEE 32-bit floating point
Module keying: Electronic software configurable
RTB keying: User-defined mechanical
Standards: C/US UL listed, CSA certified, CE-ATEX, CE-EMC, CE-LVD, C-TICK, FM-US_HAZ, GOST_R, KCC certified, MARINE-ABS, MARINE-BVS, MARINE-DNV, MARINE-GL, MARINE-KRS, MARINE-LR, ROSTECHNADZOR, RUS_PAT_APPR, TUV-FS
|
|
|
|