Elit logo e-Elit - leading
electronic and automation component
online distributor
Elit shopping basket
Items: Total:
0
0,00 €
    search
Log in
Username/Email Address:

Password:
Show all products categ.
Need assistance?
Featured Products!
Busbar G-4L-1000/16, L1-N-L2-N-L3-N| 27x2/1000, 16mm², screw M5-M6, MaxPro
Busbar G-4L-1000/16, L1-N-L2-N-L3-N| 27x2/1000, 16mm², screw M5-M6, MaxPro



High Speed Counter Module ControlLogix, 2-ch., 4 outputs, Rockwell Automation
Image is illustrative
High Speed Counter Module ControlLogix, 2-ch., 4 outputs, Rockwell Automation
Code: 1756-HSC
Cena (indicative)
878,90 €  /pc
Manufacturer :
Availability:
21 days
Weight:
0.38 kg/pc
Volume:
0.0021 m3/pc
Quantity:
Plus sign Minus sign
 

 

High Speed Counter ControlLogix, 2 channels/ 4outputs, Allen-Bradley

ControlLogix® Specialty I/O Module, Type: Counter Input, Number Of Channels: 2 Counter, Each With 3 Input, 4 Output (2 Points/Group), Input: Operating Voltage Range - 5 V Operation: 4.5 - 5.5 VDC, 12/24 V Operation: 10 - 26.4 VDC, Input Frequency: 1 MHZ In Counter Modes (A Input), 500 KHZ In Rate Measurement Mode (A Input), 250 KHZ In Encoder Mode (A/B Inputs, X1 Or X4), 70 HZ With Filter Enabled, Counting Frequency: 1000 KHZ, Input Current: 4 - 15 MA, Output: Off-State Leakage: 300 MA, On-State Voltage Drop: 0.55 V, Output Current Rating, Per Point: 20 MA At 4.5 - 5.5 VDC, 1.0 A At 10 - 31.2 VDC, Load Current Per Point: 5 V Operation: 3 MA, 12/24 V Operation: 40 MA, Current Rating: Current Limit: Less Than 4 A, Isolation: 125 V (Continuous), Basic Insulation Type, Input Group-To-Backplane, 30 V (Continuous), Basic Insulation Type, Input Group-To-Input Group, 1900 VDC For 2 SEC Routine Test, Control: Output: Up To Two Outputs Are Assigned To Each Counter Channel, Each Output Can Have Two ’Turn-On’ And ’Turn-Off’ Preset Values, Power Rating: Backplane: 1.6 W, Enclosure: Open Type, Rfi Suppression: Radiated: 10 V/M With 1 KHZ Sine-Wave 80% AM From 80 - 2000 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 900 MHZ, 10 V/M With 200 HZ 50% Pulse 100% AM At 1890 MHZ 3 V/M With 1 KHZ Sine-Wave 80% AM From 2000 - 2700 MHZ, Conducted: 10 VRMS With 1 KHZ Sine-Wave 80% AM From 150 KHZ - 80 MHZ On Shielded Signal Ports, Display: Input, Output, Communication, Module Health And Operational Status, Interface: Removable Terminal Block, Mounting: Chassis, Temperature Rating: 32 - 140 DEG F, Environmental Conditions: Relative Humidity: 5 - 95% Non-Condensing, Vibration: 2 G, Shock: 30 G (Operating), 50 G (Non-Operating), Response Time: Delay (Off To On): 20 MIC-SEC Nominal/50 MIC-SEC Maximum, Delay (On To Off): 60 MIC-SEC Nominal/300 MIC-SEC Maximum, Power Dissipation: 5.6 W At 60 DEG C, Slot Width: 1, Surge Transient Immunity: Plus/Minus 1 KV Line-Line (DM) And Plus/Minus 2 KV Line-Earth (CM) On Unshielded Output/Power/Shielded Input Ports, Surge Current: 2 A For 10 MS Every 1 SEC At 60 DEG C, Standard/Approvals: C/US UL listed, CSA certified, CE-ATEX marked, CE-EMC marked, CE-LVD marked, C-TICK certified, GOST_R certified, KCC certified, MARINE-ABS certified, MARINE-DNV certified, MARINE-KRS certified, ROSTECHNADZOR
 
 
Elit OÜ | e-post: elit@elit.ee | +372 622 9119 | 2016 ©


 
X
 
X