Digital Contact Output Module Point I/O, in-cabinet, 2-ch., NO, NC 2A 5..28VDC leakage 2mA, TS35, Allen-Bradley Code:
1734-OX2
Cena (indicative)
Manufacturer
:
Availability:
ask for dd
|
Weight:
0.0567 kg/pc
|
Volume:
0 m3/pc
|
|
|
|
|
Digital Contact Output Module Point I/O, in-cabinet, 2-ch., NO˄NC 2A 5..28VDC leakage 2mA, TS35, Allen-Bradley
DESCRIPTIONS
-
Point I/O™ Digital Contact Output Module, Type: In-Cabinet, Number Of Channels: 2, Output: Form C, Isolated N. O./N.C. Relay, Voltage: 5 - 28 VDC At 2 A Resistive, 48 - 125 VDC At 0.5 - 0.25 A, 125 - 240 VAC At 2 A; Current(Resistive): 2 A At 5 - 28.8 VDC, 0.5 - 0.25 A At 48 - 125 VDC, 2 A At 125 - 240 VAC, Current(Inductive): 2 A Steady State At 5 - 28.8 VDC, 0.5 - 0.25 A Solid State At 48 - 125 VDC, 2 A At 125/240 VAC; Power: 250 - 480 W At 125 - 240 VAC, 31 W At 125 VDC, 480 VA At 240 VAC, 31 VA At 125 VDC, Current Rating: Off State Leakage: 2 MA, Isolation: 240 V Continuous, Enclosure: Open Type, Connection Cables: 22 - 14 AWG Solid/Stranded Copper Wire, Mounting: DIN Rail, Length: 0.47 IN, Width: 2.21 IN, Height: 2.97 IN, Temperature Rating: -20 To 55 DEG C, Environmental Conditions: 5 - 95% Non-Condensing Relative Humidity, Shock: 30 G Operating, 50 G Nonoperating, Vibration: 5 G At 10 - 500 HZ, Response Time: Delay Time: 10 MS (Off To On), 10 MS (ON To OFF), Bounce: 1.2 MS (Mean), Power Dissipation: 0.5 W, Operating Cycles: Contacts Life: 1000000 Operations Resistive, 100000 Operations Inductive, Indicator: 2 Yellow-Output Status, 2 Green/Red- Module/Network Status, Bus Rating: 100 MA, Resistance: Contact: 30 MIL-OHM, Keyswitch Position: 7, Standard/Approvals: CE-EMC marked, CE-LVD marked, C-Tick certified, GOST_R certified, KCC certified, MARINE-BVS certified, MARINE-DNV certified, MARINE-GL certified, MARINE-KRS certified, MARINE-LR certified, ROSTECHNADZOR certified, UL-US_HAZ listed, Application: For use with ControlLogix controller
SPECIFICATIONS
-
-
Item Name: Digital Contact Output Module
-
Type: In-Cabinet
-
Sub Brand: Point I/O™
-
Number Of Channels: 2
-
Output: Form C, Isolated N. O./N.C. Relay, Voltage: 5 - 28 VDC At 2 A Resistive, 48 - 125 VDC At 0.5 - 0.25 A, 125 - 240 VAC At 2 A; Current(Resistive): 2 A At 5 - 28.8 VDC, 0.5 - 0.25 A At 48 - 125 VDC, 2 A At 125 - 240 VAC, Current(Inductive): 2 A Steady State At 5 - 28.8 VDC, 0.5 - 0.25 A Solid State At 48 - 125 VDC, 2 A At 125/240 VAC; Power: 250 - 480 W At 125 - 240 VAC, 31 W At 125 VDC, 480 VA At 240 VAC, 31 VA At 125 VDC
-
Current Rating: Off State Leakage: 2 MA
-
Isolation: 240 V Continuous
-
Enclosure: Open Type
-
Connection Cables: 22 - 14 AWG Solid/Stranded Copper Wire
-
Mounting: DIN Rail
-
Length: 0.47 IN
-
Width: 2.21 IN
-
Height: 2.97 IN
-
Temperature Rating: -20 To 55 DEG C
-
Environmental Conditions: 5 - 95% Non-Condensing Relative Humidity, Shock: 30 G Operating, 50 G Nonoperating, Vibration: 5 G At 10 - 500 HZ
-
Response Time: Delay Time: 10 MS (Off To On), 10 MS (ON To OFF), Bounce: 1.2 MS (Mean)
-
Power Dissipation: 0.5 W
-
Operating Cycles: Contacts Life: 1000000 Operations Resistive, 100000 Operations Inductive
-
Indicator: 2 Yellow-Output Status, 2 Green/Red- Module/Network Status
-
Keyswitch Position: 7
-
Bus Rating: 100 MA
-
Resistance: Contact: 30 MIL-OHM
FEATURES
-
Bulletin 1734 POINT I/O™ is ideal for applications requiring flexibility and low cost of ownership. Granularity of one to eight points lets you buy only the I/O you need. The compact design makes installation easier in limited panel space. The family includes POINT Guard I/O™ safety-rated I/O modules that can be used side-by-side in a standard POINT I/O system - Cost savings modular design requires less enclosure space
- Up to 504 channels on a single network interface
- Removable terminations accelerate commissioning
- Remove and insert under power reduces maintenance time
- Local autonomous control
- Fast, simple configuration and integration
- Full Add-on-Profiles in RSLogix 5000, no other software is needed
- Channel-level diagnostics
- Greater flexibility
- Local control
- Controlled by a single GuardLogix controller
- Standards: CE-EMC marked, CE-LVD marked, C-Tick certified, GOST_R certified, KCC certified, MARINE-BVS certified, MARINE-DNV certified, MARINE-GL certified, MARINE-KRS certified, MARINE-LR certified, ROSTECHNADZOR certified, UL-US_HAZ listed
- Applications: For use with ControlLogix controller
|
|
|
|