Image is illustrative
|
Outside/ wet-room Temperature Sensor ATF2-PT100, sensor PT100, -50..+90°C, M16x1.5, 4-wire, IP65, S+S Regeltechnik Code:
1101-1050-1003-000
Cena
Manufacturer
:
Availability:
14 days
|
Weight:
0.156 kg/pc
|
|
|
|
|
|
Outside/ wet room temperature sensor ATF1-PT100, -50..+90°C, box 72x64x38 M16x1.5, 4-wire, IP65, S+S Regeltechnik
Outside wall resistance thermometer ⁄ weather sensor THERMASGARD® ATF 2 (external sensor) with passive output, with enclosure made of impact-resistant plastic and quick-locking screws.
It is used to measure outside temperatures, temperatures in wet rooms e.g. as an outdoor sensor, weather sensor for installation on outside walls, in cold storage buildings and greenhouses, in halls, in the industrial sector and in agriculture. In outdoor areas, the temperature sensor is installed preferably at the north side of a building or in a protected place.
In case of direct sun irradiation, the sunshade and ball game protection WS 01 (accessories) or the device variant with the installed sunshade SS 02 (available on request) must be used.
|
|
|
Technical data:
|
Sensor: |
PT100 |
Sensor -tolerance: |
±0.3 % at 0 °C according to DIN EN 60751 |
Operation range, temperature: |
-50 ... 70 °C |
Operation range, humidity: |
<95% r.H., non-precipitating air |
Storage temperature: |
-50 ... 70 °C |
Enclosure: |
Polyamide, 30% glass-globe reinforced,
with quick-locking screws (slotted ⁄ Phillips head combination),
Traffic white (similar to RAL 9016) |
Enclosure dimensions: |
72 x 64 x 37.8 mm (Tyr 1) |
Electrical connection: |
0.14 - 1.5 mm², 4-wire connection, via terminal screws |
|
|
|
|
|