Image is illustrative
|
Switch Amplifier KFA6-SR2-Ex2.W, 2-ch., input dry contact/NAMUR, output RO, LFD, SIL2, 230VAC, Pepperl+Fuchs Code:
103373
Cena (indicative)
Manufacturer
:
Availability:
21 days
|
Weight:
0.193 kg/pc
|
Volume:
0.0003 m3/pc
|
|
|
|
|
Switch Amplifier KFA6-SR2-Ex2.W, 2-ch., input dry contact/NAMUR, output RO, LFD, SIL2, 230VAC, Pepperl+FuchsSwitch Amplifier KFA6-SR2-Ex2.W
- 2-channel isolated barrier
- 230 V AC supply
- Dry contact or NAMUR inputs
- Relay contact output
- Line fault detection (LFD)
- Reversible mode of operation
- Up to SIL 2 acc. to IEC 61508/IEC 61511
Datasheet excerpt: Technical data of KFA6-SR2-Ex2.W
General specifications |
Signal type | Digital Input |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 2 |
Supply |
Connection | terminals 14, 15 |
Rated voltage | 207 ... 253 V AC, 45 ... 65 Hz |
Power dissipation | 1.2 W |
Power consumption | max. 1.3 W |
Input |
Connection side | field side |
Connection | terminals 1+, 2+, 3-; 4+, 5+, 6- |
Rated values | acc. to EN 60947-5-6 (NAMUR) |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
Line fault detection | breakage I ≤ 0.1 mA , short-circuit I > 6 mA |
Pulse/Pause ratio | min. 20 ms / min. 20 ms |
Output |
Connection side | control side |
Connection | output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12 |
Output I, II | signal ; relay |
Contact loading | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
Mechanical life | 107 switching cycles |
Transfer characteristics |
Switching frequency | ≤ 10 Hz |
Indicators/settings |
Display elements | LEDs |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Low voltage | |
| Directive 2014/35/EU | EN 61010-1:2010 |
Conformity |
Electromagnetic compatibility | NE 21:2006 |
Degree of protection | IEC 60529:2001 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 150 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-Type Examination Certificate | PTB 00 ATEX 2081 |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 |
International approvals |
FM approval | |
| Control drawing | 116-0035 |
UL approval | |
| Control drawing | 116-0145 |
CSA approval | |
| Control drawing | 116-0047 |
IECEx approval | IECEx PTB 11.0031 |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
|
|
|
|
|