Image is illustrative
|
Power Feed Module KFD2-EB2, interface f. PR, current 4A, replaceable fuse, RO| NO/reversible, LED, 20..30VDC, Pepperl+Fuchs Code:
189783
Cena (indicative)
Manufacturer
:
Availability:
21 days
|
Weight:
0.1313 kg/pc
|
Volume:
0.0003 m3/pc
|
|
|
|
|
Power Supply KFD2-EB2, Pepperl+FuchsPower Feed Module KFD2-EB2
- Interface for Power Rail
- Supply current ≤ 4 A
- Replaceable fuse
- Relay contact output, reversible
- LED status indication
Datasheet excerpt: Technical data of KFD2-EB2
Product Description |
Power Feed Module |
Supply |
Connection | terminals 11+, 12- terminals 8+, 9- |
Rated voltage | 20 ... 30 V DC The maximum rated operating voltage of the devices plugged onto the Power Rail must not be exceeded. |
Fusing | 5 A recommended maximum utilization of the fuse: 80 % |
Power dissipation | ≤ 1 W |
Output |
Connection | Power Rail |
Output rated operating current | max. 4 A |
Fault signal | relay output: NO contact |
Contact loading | 30 V AC/ 2 A / cos φ ≥ 0.7 ; 40 V DC/ 2 A |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
Indicators/settings |
Display elements | LEDs |
Control elements | DIP-switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2006 |
Degree of protection | IEC 60529:2001 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 100 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
Certificate | TÜV 00 ATEX 1618 X |
| Marking | II 3G Ex nA nC IIC T4 |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
International approvals |
FM approval | |
| Control drawing | 116-0160 |
IECEx approval | IECEx UL 16.0051X |
| Approved for | Ex nA nC IIC T4 Gc |
|
|
|
|
|